• Table 2.2 480Vac Wire Sizes and Connector Specifications Information in this document supercedes that contained in TM.E7.01 with dates 5/1/06, Rev: 06-05, and earlier. The data in this document reflects the most recent information provided by Yaskawa regarding these specific wire size tables.
Page 2
Chapter 2 Electrical Installation This chapter describes wiring terminals, main circuit terminal connections, main circuit terminal wiring specifications, control circuit terminals, and control circuit wiring specifications. Terminal Block Configuration ............. 2-2 Wiring Main Circuit Terminals ........... 2-3 Control Wiring................2-12 Electrical Installation 2 - 1...
Wiring Main Circuit Terminals Applicable Wire Sizes and Closed-loop Connectors Select the appropriate wires and crimp terminals from Table 2.1 to Table 2.2. Table 2.1 208-240Vac Wire Sizes and Connector Specifications Recommended Clamping Wire Size Drive Model Nominal Terminal Torque Wire Terminal Symbol CIMR-E7U...
Page 5
Table 2.1 208-240Vac Wire Sizes and Connector Specifications Recommended Clamping Wire Size Drive Model Nominal Terminal Torque Wire Terminal Symbol CIMR-E7U Screws lb. in. Type (N•m) R/L1, S/L2, T/L3, 1 U/T1, (22.5) (100) V/T2, W/T3, R1/L11, S1/L21, T1/L31 88.5 (10.0) (22) 2037 203.6...
Main Circuit Terminal Functions Main circuit terminal functions are summarized according to terminal symbols in Table 2.3. Wire the terminals correctly for the desired purpose. Table 2.3 Main Circuit Terminal Functions (208-240Vac and 480Vac) Model: CIMR-E7U _ _ _ _ Purpose Terminal Designation 208-240Vac...
Page 10
(See Appendix E) may result in damage to the wiring, Drive and/or personal injury. 2. Control power is supplied internally from the main circuit DC power supply for all Drives. 3. Consult your Yaskawa representative before using 12-pulse rectification. Electrical Installation 2 - 9...
Page 11
(See Appendix E) may result in damage to the wiring, Drive and/or personal injury. 2. Control power is supplied internally from the main circuit DC power supply for all Drives. 3. Consult your Yaskawa representative before using 12-pulse rectification. Electrical Installation 2 - 10...
Cable Length between Drive and Motor The E7 should be installed as close as possible to the motor to minimize the length of load side power cable needed between the Drive and the motor. If the cable between the Drive and the motor is long, the high-frequency leakage current will increase, causing the Drive output current to increase as well.
A2 signal employed is 4 to 20 mA with parameter H3-08 set for “2: 4 - 20 mA”. For 0 to 10 VDC, parameter H3-08 is set for “0: 0 - 10 VDC” and the E7 control board DIP switch S1-2 must be in the OFF position. (See Fig 2.4).
Wiring Checks After all wiring is completed, perform the following checks: Is all wiring correct? Have all wire clippings, screws or other foreign material been removed from the Drive enclosure? Are all terminal screws tight? Electrical Installation 2 - 13...
Control Circuit Terminal Functions The factory default functions of the control circuit terminals for 2-wire control are shown in Table 2.8. Table 2.8 Control Circuit Terminals Type Signal Name Description Signal Level Forward run/stop command Forward run when CLOSED; stopped when OPEN. Reverse run/stop command Reverse run when CLOSED;...
DIP Switch S1 DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in Table 2.9. Terminating resistance DIP Switch S1 located on terminal board. Fig 2.4 DIP Switch S1 Location Table 2.9 DIP Switch S1 Name Function Setting...
Page 17
Shunt Connector CN15 The shunt connector CN15 is described in this section. Shunt connector along with parameters H4-07 and H4-08 select the sig- nal range of the analog output terminals FM and AM. Shunt connector CN15 is only available when the optional Terminal Card with the 4-20mA Analog Output Monitor is installed (Model No.
Page 18
Sinking/Sourcing Mode The input terminal logic can be switched between sinking mode (0V common) and sourcing mode (+24V common) by using the terminals SN, SC, and SP. An external power supply can also be connected, providing more freedom in signal input methods.
Control Circuit Wiring Precautions Observe the following precautions when wiring control circuits: Separate control wiring from power/motor wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, 2, and 3) and other high-power lines. Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, and M4 (digital outputs) from wiring to other control circuit terminals.
Field Wiring Diagram Use this diagram to document field wiring. It may be helpful to copy this page. Fig 2.8 Field Wiring Diagram Electrical Installation 2 - 20...