WaterMaster
Electromagnetic flowmeter
4.5.2 Environmental Protection
Fig. 4.12 Potting the Sensor Terminal Box
Warning.
Potting materials are toxic. Read the manufacturers' instructions carefully before preparing the
potting material and use suitable safety precautions.
Power up and check all connections before potting.
The remote sensor terminal box connections must be potted immediately on completion to
prevent the ingress of moisture.
Do not overfill or allow the potting material to come into contact with 'O' rings or grooves.
Do not let potting material enter conduit (if used).
22
4 Electrical Installation
IM/WM–EN Rev. M