F.2
BACNET BINARY INPUT POINT MAPPING FOR 5000 NEMA 3R
ALL – BACnet Object: Binary Input
Access:
Read Only
Inst. ID
Object Name & Description
1
RemotEye 4 Data Link
2
RemotEye 4 Network Link
3
Online Mode
4
Backup Mode
5
Bypass Mode
6
Shutdown Mode
7
Battery Test Mode
8
Pre-Charge Mode
9
Gate-Check Mode
10
UPS Battery Status Unknown
11
UPS Battery Status Normal
12
UPS Battery Status Low
13
UPS Battery Status Depleted
14
UPS Battery Status Discharging
15
UPS Battery Status Test Failure
16
Protective Charging Set
17
Equalized Charging Set
18
Battery Charger Status Normal Charging
19
Battery Charger Status Stop Charging
20
Battery Charger Status Discharging
21
Battery Test Disabled
22
Battery Test in Progress
23
EMD Enabled
24
EMD Alarm-1
25
EMD Alarm-2
196
BACnet Property: Present Value
Status Flags:
Normal
5000 NEMA 3R BACnet Binary Input Point Mapping
Units
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
Out of Service: FALSE
Comments
0 = Link Up; 1 = Link Down
0 = Link Up; 1 = Link Down
0 = no Alarm; 1 = Alarm Triggered (upsAlarmEMDSensor1AlarmTriggered)
0 = no Alarm; 1 = Alarm Triggered (upsAlarmEMDSensor2AlarmTriggered)
RemotEye 4 User Manual – 90988-007