Commissioning Ethernet switch (modular) FN2012-A1
24
FN2012-A1 web interface
24.3 FN2012-A1 web interface
24.3.1 Commissioning a web interface
106 | 188
Building Technologies
Fire Safety
WARNING
Changing the initial password
When you first access the web interface, change the initial login password.
If you do not change the initial password, the security of the web interface cannot
be guaranteed. Network settings can be changed as a result of unauthorized
access. Changed network settings can cause the fire detection system to
malfunction.
Opening the web interface
ϖ Standalone FN2012-A1: You have pre-configured an IP address for the
FN2012-A1 using the rotary switch.
ϖ Integrated FN2012-A1: In Engineering Tool, you have configured an IP address
for the FN2012-A1 that is valid within the sub-net.
ϖ The FN2012-A1 and the PC are connected to the same Ethernet sub-net.
ϖ Where applicable, the PC is connected to the Ethernet sub-net via a GAP.
1. Open the Internet browser and enter the pre-configured IP address of the
FN2012-A1 in the address field.
The login window opens.
2. Enter the default login data in the Login window to log on:
–
User name = 'admin'
–
Password = 'fs20admin'
3. Select the 'Password' tab and set a customer-specific password.
4. Confirm the password you have set with 'Save changes'.
You have already commissioned the web interface.
See also
1 Specifying a pre-configured IP address [➙ 104]
009052_s_en_--