hit counter script

Advertisement

Available languages

Available languages

Contactor

Operating Instructions

Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.

Mounting

For dimension drawings (dimensions in mm) see:
Fig. Ia
Fig. Ib
Snap onto 35 mm standard mounting rail to DIN EN 50022 or fix on a plain surface
with two M4 screws. With screw mounting, always use plain washers and spring
washers. Cover the contactors during installation if foreign particles, such as swarf,
can fall onto them. Install contactors in a housing if they are exposed to dirt, dust or
aggressive atmospheres.
For permissible mounting positions see:
Fig. IIa
Fig. IIb

Connection

The terminal screws can be tightened with a power screwdriver.
Screwdriver blade width: 5 to 6 mm.
Permissible Conductor Cross-sections for main conductor:
Solid
Finely stranded with end sleeve
Terminal pin in accordance with DIN 46231
AWG wires
Tightening Torque
Permissible Conductor Cross-sections for auxiliary conductor:
Solid
Finely stranded with end sleeve
Terminal pin in accordance with DIN 46231
AWG wires
Tightening Torque standard type
Tightening Torque auxiliary contact block
Use 75 °C copper wire only.
For circuit diagrams and positions of connection terminals see Fig. III.

Operation

Observe operating voltage (see rating plate of magnet coil).
The operating state of the contactor is shown at the position indicator; see Fig. IV.
.
When the system voltage is applied and the load is connected, do not
operate the contactor by pressing down the contact carrier.
Maintenance
The following components can be replaced:
magnet coil, single-pole auxiliary contact block 3TX3.
For Order No. see Catalog NSK.
Only use of original spare parts ensures the operational safety of contactors.
Cleaning
Remove dust by suction.
**Footnote: According to IEC 60947 / VDE 0660, the types of protection mean:
"Assignment type 1": Short circuits can cause damage to the contactors making replacement of the equipment necessary.
"Assignment type 2": Easily separable contact welding but no other damage.
A5E01050500A-02
Order No.: 3ZX3012-0TS33-0AY0
DIN VDE 0660, IEC 60947-4-1, Q/320500 SMS 009, GB14048.4
AC operation
DC operation
AC operation
DC operation
2
2 x 2.5~6 mm
2
2 x 1.5~4 mm
1 x 1~6
2 x AWG 14~10
1.0~1.5 Nm
2
2 x 0.5 to 1 mm
2
2 x 1 to 2.5 mm
2
2 x 0.75 to 2.5 mm
1 x 1~6
2 x AWG 18 to 12
0.8 to 1.4 Nm
0.8 to 1.1 Nm
Auxiliary contact block
For replacement see Fig. V.
In addition to the side-mounted auxiliary contact block, a maximum of 2 front-mounted
contact block can be snapped on to the contactor.
Operating range of the magnetcoils (with side-mounted aux. contact block):
3TX4011-8A or 3TX4011-8A + 1 front-mounted auxiliary contact block: AC / DC 0.8
to 1.1 X Us
3TX4011-8A + 1 front-mounted auxiliary contact block: ≤ (0.85~1.1)Us
Magnet coil
For coil replacement see Fig. VI:
Fig. VIa
Fig. VIb
Ensure that the pole faces of the magnet coil are clean. Do not use grease solvents
or sharp objects for cleaning.
Technical Data
Weight:
AC operation
DC operation
Permissible ambient temperature:
operation
storage
Main Circuit
Rated insulation voltage U
i
Rated operating current I
/ AC-1 (55°C)
e
Motor rating P
Rated operational voltage
- 230 V
kW
- 240 V
kW
- 400 V
kW
- 415 V
kW
- 500 V
kW
- 690 V
kW
Short-circuit protection:
Degree of protection to DIN VDE
0660 / IEC 60947-4-1 **
- assinment type 1
- assignment type 2
- non-welding
Auxiliary circuit
Auxiliary contact block 3TX3 / 4
Rated operating voltage
- 230 V
- 400 V
- 500 V
- 690 V
Rated operating voltage
- 24 V
- 48 V
- 110 V
- 220 V
- 440 V
- 600 V
Short-circuit protection:
Fuse-links NEOZED and DIAZED, gL (gG)
Circuit-breaker, C-char.
For further data and accessories see Catalog IC15.
3TS33,3TS34
English
AC coil
DC coil
approx. 430 g
approx. 630 g
-25 °C to +55 °C
-50 °C to +80 °C
AC 690 V
42 A
/ AC-3
N
3TS33
3TS34
5.5
8.5
5.5
9
11
15
11
17
11
21
11
23
Fuse-links Duty class gL (gG)
3TS33
3TS34
A
63
63
A
40
40
A
16
16
Rated operating currentI
/ AC-15 / AC-11
e
A
5.6
A
3.8
A
2.5
A
1.8
Rated operating currentI
/ DC-13 / DC-11
e
A
10
A
4.6
A
0.8
A
0.2
A
0.11
A
0.08
A
16
A
10
Last update: 01 April 2011

Advertisement

Table of Contents
loading

Summary of Contents for Siemens 3TS33

  • Page 1 3TS33,3TS34 Contactor DIN VDE 0660, IEC 60947-4-1, Q/320500 SMS 009, GB14048.4 English Operating Instructions Auxiliary contact block Read and understand these instructions before installing, For replacement see Fig. V. operating, or maintaining the equipment. In addition to the side-mounted auxiliary contact block, a maximum of 2 front-mounted contact block can be snapped on to the contactor.
  • Page 2 3TS33,3TS34 Контактор DIN VDE 0660, IEC 60947-4-1, Q/320500 SMS 009, GB14048.4 Инструкция по эксплуатации Русский Чистка Перед установкой, вводом в эксплуатацию или Удаление пыли производить пылесосом при отключенном электро-питании. обслуживанием устройства необходимо прочесть и понять Блок-контакт данную инструкцию. Замены блок-контакта: рис. V. Схема по замене смотри рис. V. Кроме блока...
  • Page 3 3TS33,3TS34 接触器 DIN VDE 0660, IEC 60947-4-1, Q/320500 SMS 009, GB14048.4 中文 使用说明 辅助触头组 安装、使用和维修本设备前必须先阅读并理解本说明。 更换示意图见图 V。除装在侧面的辅助触头组外 , 最多还可有 2 个前 置辅助触头组能装在接触器上。 危险 线圈工作电压范围 (附有装在侧面的辅助触头组) : 3TX4011-8A 或 3TX4011-8A + 1 个前置辅助触头组:AC / DC (0.8~1.1)Us 危险电压。 3TX4011-8A + 2 个前置辅助触头组:≤ (0.85~1.1)Us 可能导致生命危险或重伤危险。...
  • Page 4 M3,5 Ø4,8 Ø4,8 M3,5 M4 M3,5 Ø5 M3,5 Ø5 M3,5 Minimum clearance from earthed parts 10 mm Минимальное расстояние до заземленных частей - 10 мм 对地部件的最小距离 10 mm II a 22,5º 22,5º 22,5º 22,5º 90º 90º 3ZX3012-0TS33-0AY0...
  • Page 5 Technical Assistance: Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET) SIEMENS AG Fax: +49 (0) 911-895-5907 Technical Assistance E-mail: technical-assistance@siemens.com Würzburger Str. 121 Internet: www.siemens.com/industrial-controls/technical-assistance D-90766 Fürth Subject to change without prior notice. Store for use at a later date. Order No.: 3ZX3012-0TS33-0AY0 © Siemens AG 2011...

This manual is also suitable for: