Page 1
SmartLi User Manual Issue Date 2019-09-16 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
User Manual About This Document About This Document Purpose This document describes the SmartLi in terms of its features, performance, working principles, appearance as well as instructions for installation, and operation and maintenance (O&M). Intended Audience This document is intended for: ...
1.4 Battery Safety ................................ 5 1.5 Mechanical Safety ..............................7 1.6 Laying Out Cables ..............................8 1.7 Information About Foreign Objects near SmartLi Equipment Installation ............... 8 2 Overview ..........................10 2.1 Model Description ..............................10 2.2 Product Introduction ............................. 11 2.2.1 Product Structure ...............................
Page 6
5.1 Powering On Batteries ............................67 5.2 Powering Off Batteries ............................69 5.3 Performing EPO ..............................69 5.4 Clearing the EPO State ............................69 5.5 Adding a SmartLi ..............................70 5.6 Removing a SmartLi .............................72 5.7 Testing Batteries ..............................74 5.7.1 Shallow Discharge Test ............................74 5.7.2 Capacity Test ..............................76 5.7.3 Test Data Download............................77...
Follow the precautions and special safety instructions provided by Huawei when operating Huawei products. Huawei will not be liable for any consequences that are caused due to violations regarding general safety regulations and equipment design, production, and usage safety standards.
Page 9
User Manual 1 Safety Precautions Personal Requirements Only Huawei engineers or engineers certified by Huawei are allowed to perform SmartLi commissioning and maintenance. Otherwise, human injury or equipment damage may occur, and any resulting SmartLi faults will be beyond warranty scope.
Replace danger signs that have worn out or are unreadable. Do not alter the SmartLi internal structure or installation procedure unless consent from the manufacturer is given. Never use water to clean electrical components inside or outside the SmartLi.
If any liquid is detected inside the product, immediately disconnect the power supply and contact the administrator. 1.3 Operating Environment The SmartLi operating environment must meet the requirements for the climate indicator, mechanically active substance indicator, and chemically active substance indicator in ETSI EN 300 019-1 class 3.6.
Page 13
When installing and maintaining batteries, pay attention to the following points: Use dedicated insulated tools. Keep the SmartLi loop disconnected during installation and maintenance. Avoid skin contact with electrolyte overflow. Before installing or maintaining batteries, wear goggles, rubber gloves, and protective clothing.
The purpose of this note is to provide information and warnings about the potential risks of the operational integrity of an installed SmartLi. These risks are caused by foreign objects in or near the battery modules and relevant auxiliary equipment/components.
Page 16
SmartLi User Manual 1 Safety Precautions It is common to have someone working in the same room as the SmartLi during onsite installation. Sometimes some people may be working above the SmartLi and relevant auxiliary equipment/components. To avoid serious damage to the onsite operation, property hazards, and personal injury...
The SmartLi provides backup power for a medium- and large-power UPS. With a neutral wire, the SmartLi is compatible with a UPS system with or without a neutral wire. The lithium battery cabinet supports power backup, battery management, and output DC-DC adjustment.
Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Green The SmartLi is running properly or a warning has been generated. The MDU is powered off. The ports of the MDU are located at the side of the LCD screen.
CAN communication build-out resistor in a parallel system Functions The monitor display unit (MDU) allows for general SmartLi operations, parameter setting, viewing of running status and alarms, and so on. Specifications Dimensions (H x W x D): 175 mm x 264 mm x 40 mm 2.2.6 Fire Detection and Extinguishing Equipment...
Reserve at least 500 mm from the top of the cabinet. The SmartLi can be installed against a wall and no space needs to be reserved at the rear. If an antiseismic kit is deployed, at least 500 mm space should be reserved at the rear for operations.
3.1.3 Unpacking and Checking Context To prevent the SmartLi from falling over, secure it to a pallet truck using ropes before moving it. To prevent shocks or falls, move the SmartLi gently. After placing the SmartLi in the installation position, unpack it and take care to prevent scratches.
Page 29
Step 5 Remove the plastic bag and take out the fittings box. Step 6 Check that the SmartLi is intact. Visually inspect the SmartLi appearance for shipping damage. If it is damaged, notify the carrier immediately. Check that all fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record this information and contact your local Huawei office immediately.
Step 2 Check the cabinet levelness using a level instrument. If the cabinet is not level, wrench the anchor bolts. ----End 3.2.3 Routing Cables 3.2.3.1 SmartLi Cable Connection Reference Context Keep away from cabinets when preparing cables to prevent cable scraps from entering the cabinets.
----End 3.2.3.4 Remote EPO Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG. Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
----End 3.3 Combining Cabinets Prerequisites The SmartLi supports the combination of up to five cabinets. When multiple cabinets are connected in parallel, only the basic cabinet has an LCD. When cabinets are combined, a battery bus bar box (BBB box) is required. For details about how to install a BBB box, see PDU8000-(0630, 1250, 2000) DCV8-BGA001 BBB Box User Manual.
3.4 Installation Verification Table 3-2 Installation checklist Item Acceptance Criteria SmartLi The SmartLi is securely installed and does not tilt due to installation vibration. Neat arrangement The SmartLi and its adjacent cabinets are neatly arranged and secured with connecting plates.
Page 59
Manual: Check that their IP addresses are two different values on the same network segment. Set the SmartLi IP address to be in the same subnet as the PC IP address. Perform the bitwise AND operation for the UPS IP address and the PC IP address with the subnet mask respectively.
Page 60
After you restart the device, IP address allocation changes back to Manual. The IP address is set to the IP address set previously. Ensure that the SmartLi IP address is unique on the network segment. Otherwise, the WebUI display function may not function properly. Table 4-5 System Settings...
Page 64
User name and Password, and click Login. The system supports Internet Explorer 11 and Firefox 31.0. The preset SmartLi IP address is 192.168.0.10. You can set the SmartLi Ethernet IP address on the LCD or WebUI. The value range is 1.0.0.0–223.255.255.255.
2s. The green indicator of the battery management module blinks at 4 Hz. The BCB off alarm is displayed on the UPS LCD and SmartLi LCD. No action is required. After the battery circuit breaker is closed, the alarm is automatically cleared.
Page 75
SmartLi. In this case, the green indicators of all battery management modules are on for 1s and then off for 4s, you cannot turn on the battery circuit breakers on other SmartLi cabinets or start the UPS in cold mode.
5.2 Powering Off Batteries Procedure Step 1 Switch off the battery circuit breakers. (Perform this operation for multiple SmartLi cabinets one by one.) Step 2 Press and hold the POWER ON/OFF button on the battery management module for more than 5s.
Page 78
Figure 5-3 Adding a SmartLi Procedure Step 1 Install the new SmartLi. Step 2 Remove the terminal of parallel port 1 on SmartLi 4 and connect the terminal to parallel port 1 on SmartLi 5. On the monitoring module, PARALLEL1 is above PARALLEL2.
After pressing and holding the POWER ON/OFF button on the battery management module of the new SmartLi for more than 2s, you need to confirm that the Cabinet quantity mismatch alarm is cleared before turning on the battery circuit breaker.
Page 80
5s. Step 3 Remove the parallel cable between SmartLi 3 and SmartLi 4. Step 4 Remove the terminal from parallel port 2 on SmartLi 3 and connect the terminal to parallel port 2 on SmartLi 4. Issue 04 (2019-09-16)
Page 82
The mains, batteries, charger, and discharger are normal. No overload alarm is generated. The SmartLi has generated no alarms related to lithium batteries. Automatic Shallow Discharge Test On the home screen of the UPS LCD, choose System Info > Settings > Battery Settings and set Sched.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated. The SmartLi has generated no alarms related to lithium batteries. Procedure Step 1 On the home screen of the UPS LCD, choose System Info > Maintenance > Battery Maint.
Check Item Handling Measures Interval Monthly Operating Keep the SmartLi far away from heat sources and avoid direct environment exposure to sunlight. Appearance If a battery module experiences damage, leakage, or deformity, disconnect, take pictures, and then replace the battery module.
Materials: a new and intact MDU The MDU can be replaced online without cutting off the power supply to the SmartLi. Before the replacement, ensure that the load services are not affected or obtain written consent from the customer.
If the Version incompatible alarm is generated, you need to upgrade the version before turning on the battery circuit breaker. Step 7 After the green indicator of the battery management module blinks at 10 Hz, turn on the battery circuit breaker on the SmartLi. ----End 8.3 Replacing the Battery Module Prerequisites ...
Page 101
2s. The green indicator of the battery management module blinks at 4 Hz. Step 16 After the green indicator of the battery management module blinks at 10 Hz, switch on the battery circuit breaker on the SmartLi. ----End Issue 04 (2019-09-16)