Commissioning
6.3 Configuration
● 2 = email only
The measurement data will be sent by email if a data connection is available. If no data
connection is available or the mail server is down, the measurement data will not be lost.
The Wireless Communication Module will save the measurement data and will try to send
it together with the new measurement data at the next wakeup time.
● 3 = FTP and SMS
The measurement data will be sent to the customer's FTP server if a data connection is
available. If no data connection is available or the FTP server is down, 12 values of Totalizer
1 will be extracted from the measurement data and sent by SMS.
● 4 = FTP only
The measurement data will be sent to the customer's FTP server if a data connection is
available. If no data connection is available or the FTP server is down, the measurement
data will not be lost. The Wireless Communication Module will save the measurement data
and will try to send it together with the new measurement data at the next wakeup time.
● 5 = FTPS and SMS
The measurement data will be sent to the customer's FTPS server if a data connection is
available. If no data connection is available or the FTP server is down, 12 values of Totalizer
1 will be extracted from the measurement data and sent by SMS.
● 6 = FTPS only
The measurement data will be sent to the customer's FTPS server if a data connection is
available. If no data connection is available or the FTP server is down, the measurement
data will not be lost. The Wireless Communication Module will save the measurement data
and will try to send it together with the new measurement data at the next wakeup time.
● 7 = secured email (SMTPS) and SMS
The measurement data will be sent by secured email (SMTPS) if a data connection is
available. If no data connection is available or the mail server is down, 12 values of Totalizer
1 will be extracted from the measurement data and sent by SMS.
● 8 = secured email (SMTPS) only
The measurement data will be sent by secured email (SMTPS) if a data connection is
available. If no data connection is available or the mail server is down, the measurement
data will not be lost. The Wireless Communication Module will save the measurement data
and will try to send it together with the new measurement data at the next wakeup time.
6.3.4
Configuration of alarm/data SMS receiver
Two phone numbers can be programmed at parameters P7 and P8 to receive alarm messages
sent by the Wireless Communication Module.
Example:
Configuration;P7=+4911111111;P8=+4922222222;
One phone number can be programmed at parameter P9 to receive the SMS with
measurement data sent by the Wireless Communication Module.
Example:
Configuration;P9=+4911111111;
36
SITRANS FM MAG 8000 3G/UMTS add-on module
Operating Instructions, 03/2020, A5E03644134-AC