Page 1
Options for ABB drives User’s manual CDPI-01 communication adapter module...
Page 2
Drive manuals and guides Code (EN/Multilingual) ACS580-01 manuals 9AKK105713A8085 Option manuals and guides CDPI-01 communication adapter 3AXD50000009929 module user’s manual ACS-AP-x Assistant control panels 3AUA0000085685 user’s manual You can find manuals and other product documents in PDF format on the Internet.
Target audience This manual is intended for people who plan the installation, install, start up, use and service the CDPI-01 communication adapter module. Before you do work on the module, read this manual and the applicable drive manual that contains the hardware and safety instructions for the product in question.
6 CDPI-01 communication adapter module Product overview The CDPI-01 communication adapter module can be used to connect a remote ACS-AP-x control panel to the drive, or to chain the control panel or a PC to several drives on a panel bus. The panel bus can have a maximum of 32 nodes.
Page 7
CDPI-01 communication adapter module 7 Item Description LEDs mirrored from the drive control unit Connector X100 to the drive control unit Termination switch (S100) Bias switch (S101) Connector X101 for connecting a control panel or a PC Connector X102 for chaining a panel bus Cable hole locations.
8 CDPI-01 communication adapter module Planning the installation There are two ways to route the cabling to the communication adapter module: • Inside the drive and via the drive bottom plate. See page 10. • Outside the drive. See page 13.
CDPI-01 communication adapter module 9 Installation Unpacking and checking the delivery 1. Open the option package. 2. Make sure that the package contains: • CDPI-01 communication adapter module • this manual. 3. Make sure that there are no signs of damage.
10 CDPI-01 communication adapter module Connecting the panel cabling to the drive Alternative 1: Routing the cabling inside the drive If you have several drives on the panel bus, repeat these steps in all drives. 1. Stop the drive and disconnect it from the power line. Wait for 5 minutes to let the intermediate circuit capacitors discharge before you continue.
Page 11
CDPI-01 communication adapter module 11 8. Adjust the switches at the back of the module. Termination switch (S100): • If the module is connected to one drive only, set the switch to OFF. • If you have several drives on the panel bus, set the switch to ON in the last module of the bus, OFF in all other modules.
Page 12
12 CDPI-01 communication adapter module...
CDPI-01 communication adapter module 13 Alternative 2: Routing the cabling outside the drive If you have several drives on the panel bus, repeat these steps in all drives. 1. If the drive is running, stop the drive. 2. Make a hole for the panel cable on the left side of the communication adapter module.
Page 14
14 CDPI-01 communication adapter module...
Page 15
CDPI-01 communication adapter module 15...
Page 16
16 CDPI-01 communication adapter module...
CDPI-01 communication adapter module 17 Bus termination and chaining examples Bus termination is required to prevent signal reflections from the bus cable ends. Example: Chaining a control panel This figure shows how to chain a control panel to several drives.
18 CDPI-01 communication adapter module Example: Chaining a PC through a control panel This figure shows how to chain a PC to several drives through a control panel. Note: When a control panel is used for a panel-to-PC connection, it cannot be used for operating the drive.
CDPI-01 communication adapter module 19 Example: Chaining a PC through a commercial converter This figure shows how to chain a PC to several drives through a commercial converter. … Drive 1 Drive 2 Drive n (max. 32) CDPI-01 CDPI-01 CDPI-01...
20 CDPI-01 communication adapter module Start-up Before you start Make sure that you have completed the drive start-up. Setting the parameters – Example for ACS580 Standard control program If the communication adapter module is used to chain a control panel or a PC to several drives, set the parameters of group 49 Panel port communication for each drive before you connect the drives to the bus.
CDPI-01 communication adapter module 21 Diagnostics Faults and warning messages For the fault and warning messages concerning the communication adapter module, see the drive manual. LEDs The communication adapter module has two diagnostic LEDs. Name Color Description POWER Green Drive control unit is powered.
22 CDPI-01 communication adapter module Pin allocation of connectors X101 and X102 Pin No. Signal Direction Description In / Out / Hi-Z Data A (+) In / Out / Hi-Z Data B (-) /TRANS Not connected /FAULT Not connected Ground...
Page 23
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
Page 24