PRODUCT INFORMATION
PI−34.51
GLT − Non−Automatic Fire Detector Series 120
FMC−120−DKM−G−R / FMC−120−DKM−H−R
FMC−120−DKM−G−B / FMC−120−DKM−H−B /
FMC−120−DKM−G−Y
FMC−120−EST−G−B
BDL−F.01U.066.178
A2.en / 11.04.2007
1
Page
ST−FIR/ PRM1 / sib

Advertisement

loading

Summary of Contents for Bosch 120 Series

  • Page 1 PRODUCT INFORMATION PI−34.51 GLT − Non−Automatic Fire Detector Series 120 FMC−120−DKM−G−R / FMC−120−DKM−H−R FMC−120−DKM−G−B / FMC−120−DKM−H−B / FMC−120−DKM−G−Y FMC−120−EST−G−B BDL−F.01U.066.178 A2.en / 11.04.2007 Page ST−FIR/ PRM1 / sib...
  • Page 2 BDL−F.01U.066.178 A2.en/ 11.04.2007 ST−FIR/ PRM1 / sib Page 2 of 18...
  • Page 3 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en Table of contents Product description ....... Features .
  • Page 4 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 1. Product description The series 120 non−automatic fire detector is used for manual alarm triggering in conventional line technology (GLT). The line is monitored according to the principle of voltage reduction and increase.
  • Page 5 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 3. Planning notes D Non−automatic fire detectors must be mounted visibly along escape and rescue routes (e.g. exits, passageways, stairwells) and be easily accessible. D An installation height of 1400 mm ($200 mm), measured from the middle of the push button to the floor, must be maintained.
  • Page 6 Limiting values: D Detectors may only be operated with central units whose line output is energy−limited according to EN 50021. This applies to all Bosch fire panels (BMZ). D The line voltage (U ) must not exceed 33 V! D The maximum current (I...
  • Page 7 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 4. Order contents 4.1. Basic model Product ID Designation F01U011951 FMC−120−DKM−G−R, Manual call point for interior areas (Form G), red F01U011952 FMC−120−DKM−H−R, Manual call point for exterior areas (Form H), red F01U011953 FMC−120−DKM−G−B, Manual call point for interior areas (Form G), blue...
  • Page 8 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 5. Device structure The non−automatic fire detector is available in several variants and essentially consists of the following elements. Pos. Designation Plastic housing Cable ducts (interchangeable), for cable inlet and outlet. The cable can also be ducted through openings in the rear wall of the housing.
  • Page 9 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 6. Functional description 6.1. Manual call point Manual call point and stop device: In the event of an alarm, the glass pane (2) is broken first, then the manual call point (3) is pressed hard. This activates the microswitch for alarm triggering and the display LED (4) flashes.
  • Page 10 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 7. Installation d The non−automatic fire detector is designed for wall mounting. d The installation height, according to VdS regulations, is 1400 mm (± 200 mm) from the floor to the centre of the push button. d The connection cables can be surface or flush−mounted.
  • Page 11 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 7.3. Installation variants for fire hose cabinets 2.5 mm Pos. Description Installation depth version 1: min. 36 mm Installation depth version 2: 14 mm Installation depth version 3: approx. 30 mm With this version, it is not necessary to open the door of the hose box e.g.
  • Page 12 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 7.4. Connection Detailed wiring diagrams and bridge assignments for connection to different fire panels are shown in the wiring diagram manual. − − 1 2 3 4 5 6 7 8 9 10 a b a’...
  • Page 13 Germany; these regulations refer to the maintenance intervals as per the manufac- turer’s instructions. D Bosch ST recommends a functional and visual inspection at least once a year. D Maintenance and inspection work should be carried out regularly and by trained personnel.
  • Page 14 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 9. Technical specifications Technical specifications Operating voltage 24 V DC (16.2 V DC to 30 V DC) Current consumption specified by the respective security system Protection category as per EN 60529 −...
  • Page 15 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 10. Table of abbreviations = Wiring diagram manual = Fire panel = Fire detector = German Institute for Standardisation = Manual call point = Intrusion control panel = European standard = Danger detection system = Customer service information = Light Emitting Diode = Local Security Network...
  • Page 16 Produktinformation FMC−120−DKM / EST GLT PI − 34.51 en 11. Notes −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− BDL−F.01U.066.178 A2.en/ 11.04.2007 ST−FIR/ PRM1 / sib Page 16 of 18...
  • Page 17 Bosch Sicherheitssysteme GmbH Robert−Koch−Straße 100 D−85521 Ottobrunn, Germany www.bosch−sicherheitssysteme.de info.service@de.bosch.com Page 18 of 18...