Page 1
Preface Bus specific parameters Execution of switching operations via SIPROTEC4 PROFIBUS-DP Response in the event of disturbed Multifunction protection with communication to the PROFIBUS- DP master control Annunciations to the PROFIBUS-DP 7SJ61/62/63 master Input/Output unit with local Data type definitions control PROFIBUS-DP –...
Page 2
Registered trademarks Subject to change without prior notice. SIPROTECâ und DIGSIâ are registered trademarks of Siemens AG. Other designations in this manual may be trademarks that if used by third parties for their own purposes may violate the rights of the owner.
Page 3
Preface The manual is devided into the following topics: Contents of this manual • Bus specific parameters • Execution of switching operations via PROFIBUS-DP • Response in the event of disturbed communication to the PROFIBUS-DP master • Data type definitions •...
Page 4
See our catalog of courses for a list of available courses or contact our Training courses Training center in Nuremberg. Questions If you have questions to the SIPROTEC devices, contact your Siemens representative. 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile C53000-L1840-B001-02...
Page 5
Revision index Modified chapters / Edition Reasons of modification pages First edition, Doc.-No.: C53000-L1840-B001-02 Sep 11 , 2000 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP - Communication profile C53000-L1840-B001-02...
Page 6
Revision index 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile C53000-L1840-B001-02...
Table of contents Bus specific parameters....................1-1 Execution of switching operations via PROFIBUS-DP ..........2-1 Command output modes..................2-1 Behaviour under special operating conditions............. 2-3 Response in the event of disturbed communication to the PROFIBUS-DP master 3-1 Annunciations to the PROFIBUS-DP master............... 4-1 Data type definitions......................
Page 8
Table of contents List of figures Figure 5-1 Data type single-point indication................5-2 Figure 5-2 Data type single command.................. 5-2 Figure 5-3 Data type double-point indication / double command ......... 5-3 Figure 5-4 Data type measured value (signed integer) ............5-3 Figure 5-5 Data type metered measurand (unsigned long) ..........
Bus specific parameters Bus specific parameters The following settings for the serial communication between the PROFIBUS-DP master and the PROFIBUS-DP slave of the SIPROTEC device have to be defined when programming the device. The PROFIBUS-DP slave address of the SIPROTEC device is set using Slave address the parameterization system DIGSI.
Page 10
Bus specific parameters Configuration data The DDB file characterises the SIPROTEC communication module as a “slave with modular design“, i.e. depending on the selected mapping, the number of input and output data is modified without changing the DDB file. The configuration data to the various devices are contained in the corresponding bus mapping documents (ref.
Execution of switching operations via PROFIBUS-DP Execution of switching operations via PROFIBUS-DP Command output modes The following types of commands are available in the SIPROTEC device: Double commands Execution of the double commands, output to the switching devices and checkback signal are processed through two outputs respectively two bits, which are defined by “01“...
Page 12
Execution of switching operations via PROFIBUS-DP Note For the definition of the values for “quiescent status“, ON and OFF ref. to chap. 5.2 and 5.3. Output of a control pulse to switch a switching device incl. monitoring the Commands with programmed times is executed autonomously by the SIPROTEC device.
Execution of switching operations via PROFIBUS-DP Behaviour under special operating conditions • A change of the switching device status which was not initiated by the PROFIBUS-DP master (e.g. circuit breaker trip) is recognized by the PROFIBUS-DP master by a change of the value of the switching device status in the corresponding bit positions of the input message.
Page 14
Execution of switching operations via PROFIBUS-DP 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile C53000-L1840-B001-02...
Response in the event of disturbed communication to the PROFIBUS-DP master Response in the event of disturbed communication to the PROFIBUS-DP master The following response is defined for the SIPROTEC devices: After detecting 1. The tagging S (Error Systeminterface) in the SIPROTEC device is set to ON (registration in the operations event log, the interrupted processing in CFC is possible).
Page 16
Response in the event of disturbed communication to the PROFIBUS-DP master 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile C53000-L1840-B001-02...
Annunciations to the PROFIBUS-DP master Annunciations to the PROFIBUS-DP master Note When analysing the annunciations of the SIPROTEC device in the PROFIBUS-DP master, it should be noted that due to the cycle period of the PROFIBUS-DP system or due to the cyclic processing time of a PLC, temporary changes of an annunciation’s value (ON and OFF within one cycle) may eventually not be recognized.
Page 18
Annunciations to the PROFIBUS-DP master 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile C53000-L1840-B001-02...
Data type definitions Data type definitions Data type definitions Following data types are used for storage of variables in PROFIBUS-DP messages: • Single-point indications • Single commands • Double-point indications • Double commands • Measured values (signed integer) • Metered measurands (unsigned long) Note The storage of variables of more complex data types (measured values, metered measurands) in the PROFIBUS-DP messages is processed...
Data type definitions Single-point indication (SP, Input) Number of byte-values : (1 bit) Range of values : 0 and 1 ...2 Message head..Message end Bit x+2 Bit x+1 Bit x SP 3 SP 2 SP 1 max. 8 SP per octet/byte Figure 5-1 Data type single-point indication Single command (SC, Output)
Data type definitions Double-point indication (DP, Input) / Double command (DC, Output) Number of byte-values : ¼ (2 bits) Range of values : 0 to 3 0 (bit 1 = 0 and bit 0 = 0) - „Not applicable“ for DP, Quiescent status for DC 1 (bit 1 = 0 and bit 0 = 1) - OFF 2 (bit 1 = 1 and bit 0 = 0) - ON...
Data type definitions Note The value –32768 for signalling of „Overflow“ or „Invalid“ is only used for measured values in input direction. If an evaluation of the status of a measured value in output direction is required in the SIPROTEC device then a separate telegram position is to use to this (e.g.
PROFIBUS-DP – Parameterization in DIGSI PROFIBUS-DP – Parameterization in DIGSI Mapping files The parameterization of PROFIBUS-DP for a SIPROTEC device requires the selection of a mapping file which fixes the allocation of the data objects of the SIPROTEC device to the positions in the PROFIBUS- DP messages.
Page 24
PROFIBUS-DP – Parameterization in DIGSI Note The size of the PROFIBUS-DP messages (number of commands, annunciations, measured values, metered measurands) in output or input direction is exclusively fixed by the selection of a standard mapping. The standard mappings 1 to standard mapping m (m = device type dependent number of standard mappings) enclosed to DIGSI 4.1 are offered for selection furthermore but shouldn't be used for new device parameterizations.
PROFIBUS-DP – Parameterization in DIGSI Customization of the allocations The identification whether an information is routed on system interface (PROFIBUS-DP) is shown in the columns "Source system interface" and "Destination system interface" in the DISGI Configuration matrix. A cross ('X') in this column indicates the associated information as "routed on system interface".
PROFIBUS-DP – Parameterization in DIGSI To add or remove an information to "Source system interface" or "Destination system interface" set/reset the cross ('X') in the associated column of the DIGSI configuration matrix (pop-up menu when pressing the right mouse button). Note The max.
Page 27
PROFIBUS-DP – Parameterization in DIGSI Change of an If an information already routed on system interface shall get another (empty) position in the PROFIBUS-DP message, then the "Object existing allocation properties" dialog window (ref. to Figure 6-2) has to be selected to this ("Properties ..."...
Page 28
PROFIBUS-DP – Parameterization in DIGSI Binary incoming Binary incoming annunciations (marked with the sign '>' in the name, e.g. ">BLOCK 81-1") cannot be routed directly as "Source system annunciations interface". A control of these objects via PROFIBUS-DP as a substitute for using binary inputs is however often meaningful.
PROFIBUS-DP – Parameterization in DIGSI Scaling of measured values Measured values will be transferred via PROFIBUS-DP between the SIPROTEC device and the PROFIBUS-DP master as integer values (two bytes, ref. to chap. 5.4) but they are in general available in the SIPROTEC device in floating-point format as a percentage referred to the parameterized nominal values of the primary equipment.
PROFIBUS-DP – Parameterization in DIGSI 6.3.2 Number representation in dependence of the parameterization For specification of the scaling of a measured value it must be known in which number format (number of the relevant fractional digits) the measured value is available in the SIPROTEC device and to which unit it refers.
Page 31
PROFIBUS-DP – Parameterization in DIGSI Ground currents: I Parameter: 0204 Current transducer – Rated primary current 0207 Ratio factor I or (dependent on the device type) 0208 Ration factor I Product of parameters 0204 and 0207 Number representation / unit or 0204 and 0208 0.0 ...
PROFIBUS-DP – Parameterization in DIGSI 6.3.3 Parameterization of scaling values in DIGSI The "Object properties" dialog window contains for measured values - besides the property sheet "Protocol info source" or "Protocol info destination" – an additional property sheet titled "Measured value destination".
PROFIBUS-DP – Parameterization in DIGSI Printing of the allocations on system interface The allocations on system interface incl. the scalings adjusted at measured values can be printed in two different views: • Configuration – complete (sortet by line), • Routing – short (column-oriented). 6.4.1 Configuration –...
PROFIBUS-DP – Parameterization in DIGSI Figure 6-5 and Figure 6-6 show examples of the printout of annunciations and measured values for a SIPROTEC device 7SJ63. Figure 6-5 Annunciations in the printout "Configuration – complete (sorted by line)" Figure 6-6 Measured values in the printout "Configuration – complete (sorted by line)" 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP –...
PROFIBUS-DP – Parameterization in DIGSI 6.4.2 Routing – short (column-oriented, only BE, BA, LED, syst. interface) Call Menu item "File – Print" and selection of "Routing – short (column- oriented, only BE, BA, LED, syst. interface) in the "Print options" dialog window.
PROFIBUS-DP – Parameterization in DIGSI Figure 6-8 and Figure 6-9 show examples of the printout of information routed on system interface for a SIPROTEC device 7SJ63. Figure 6-8 Annunciations in the printout " Routing – short (column-oriented)" Figure 6-9 Measured values in the printout " Routing – short (column-oriented)" 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP –...
Hardware interface Hardware interface Two communication modules are available for the connection of PROFIBUS-DP to the devices 7SJ61, 7SJ62, 7SJ63, 6MD63 and 7UM61: • PROFIBUS module with isolated RS485 interface (PSE module), • PROFIBUS module with fibre-optical interface (PSO module). Technical data of the connection via the PSE module Connections 9-pole D-SUB outlet (ref.
Hardware interface Signal Meaning Shield Shield / operational ground RxD/TxD-P (B) Reception data / transmission data - positive RTS/CNTR-P Directions control (TTL level) GND1 Data transmission level (ground towards +5 V) VCC1 Supply voltage of the terminating resistors (max. 100 mA) RxD/TxD-N (A) Reception data / transmission data –...
PROFIBUS Nutzerorganisation PROFIBUS - Decentralized Peripherals PROFIBUS-DP PROFIBUS interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. PROFIBUS interface module with optical interface for the SIPROTEC devices from Siemens. Single Command Single-point Indication 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP – Communication profile...
Index Index Additional literature ........i parameterization ........6-1 allocation...........6-4 percentage value ........6-8 Plug............7-1 primary value ..........6-8 protection annunciations......4-1 baud rate...........1-1 Protection pickup ........4-1 Binary incoming annunciations ....6-6 Protection TRIP ........4-1 bit mask ............6-5 PSE module..........
Page 42
Index 7SJ61/62/63, 6MD63, 7UM61 PROFIBUS-DP - Communication profile C53000-L1840-B001-02...