hit counter script

Exit Test Mode; Basic Ied Functions; Parameter Setting Group Handling Setgrps; Verifying The Settings - ABB Relion 670 Series Installation And Commissioning Manual

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 502 029-UEN A
15.2.9
15.3
15.3.1
15.3.1.1
15.3.1.2
Installation and commissioning manual

Exit test mode

The following procedure is used to return to normal operation.
1.
Navigate to the test mode folder.
2.
Change the On setting to Off. Press the 'E' key and the left arrow key.
3.
Answer YES, press the 'E' key and exit the menus.

Basic IED functions

Parameter setting group handling SETGRPS

Prepare the IED for verification of settings as outlined in section
section
"Preparing for test"

Verifying the settings

1.
Check the configuration of binary inputs that control the selection of the
active setting group.
2.
Browse to the ActiveGroup menu to achieve information about the active
setting group.
The ActiveGroup menu is located on the local HMI underMain menu/Test/
Function status/Setting groups/ActiveGroup
3.
Connect the appropriate dc voltage to the corresponding binary input of the
IED and observe the information presented on the local HMI.
The displayed information must always correspond to the activated input.
4.
Check that the corresponding output indicates the active group.
Operating procedures for the PC aided methods of changing the active setting
groups are described in the corresponding PCM600 documents and
instructions for the operators within the SCS are included in the SCS
documentation.

Completing the test

Continue to test another function or end the test by changing the Test mode setting
to Off. Restore connections and settings to their original values, if they were
changed for testing purposes.
Verifying settings by secondary injection
in this chapter.
Section 15
"Overview"
and
155

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reg670

Table of Contents