BACnet
Default
Limit
®
Point #
Range
AV: 0
N/A
AV: 1
N/A
AV: 2
N/A
AV: 3
N/A
AV: 4
N/A
AV: 5
N/A
AV: 6
N/A
AV: 7
N/A
AV: 8
N/A
AV: 9
N/A
AV: 10
N/A
AV: 11
N/A
AV: 12
N/A
AV: 13
N/A
AV: 14
N/A
AV: 15
N/A
AV: 16
N/A
AV: 17
900
AV: 18
74
AV: 19
79
AV: 20
55
AV: 21
180
120-255
AV: 22
120
AV: 23
60
Table 9: BACnet
Legacy Parameter Analog Values
®
Pioneer Gold 1.10 & 2.05 Controller Technical Guide
BACnet
Legacy Analog Values
®
BACnet
®
Point Name
N/A
Entering Water
Temp
N/A
Liquid Line
Temp
N/A
Entering Hot
Water Temp
N/A
Air Coil Temp
N/A
Supply Air Temp
N/A
Space
Temperature
N/A
Space Relative
Humidity
N/A
CO
2
N/A
Firmware
Version
N/A
Discharge
Pressure
N/A
Suction Pressure
N/A
Water Valve/
Pump
Percentage
N/A
Hot Water Valve
Percentage
N/A
Supply Fan
Percentage
N/A
Damper
Override
Percentage
N/A
Compressor
Percentage
N/A
Network
Address
500-
CO
Setpoint
2
1500
55-85
Occupied
Cooling Setpoint
55-85
Unoccupied
Cooling Setpoint
45-65
Supply Cooling
Setpoint
Compressor On
Time
60-255
Compressor Off
Time
30-255
Compressor
Interstage On
Delay
BACNET
®
BACnet
BACnet
®
Temperature of the loop water entering the water coil
Temperature of the refrigerant liquid line
Temperature of the water entering the hot water coil
Temperature of the air coil
Temperature of the leaving discharge air
Temperature reading from the space sensor
Relative Humidity reading from the space sensor
CO
level reading from the space sensor
2
Version of the controller's firmware
Pressure reading from the discharge pressure transducer
Pressure reading from the suction pressure transducer
Percentage output to an analog water valve or pump
Percentage output to the hot water heat coil valve
Percentage output for a variable speed supply fan
Output percentage of the 0-10VDC damper override output
Current value of the compressor PID control loop
BACnet
device ID currently assigned to the controller
®
CO
setpoint to control the damper override output
2
Cooling mode enable setpoint when space is occupied
Cooling mode enable setpoint when space is unoccupied
Temperature setpoint of the leaving discharge air while in
cooling mode
Minimum on time setpoint for compressor(s)
Minimum off time setpoint for compressor(s)
Interstage on delay setpoint when unit has more than one
compressor stage
LEGACY PARAMETERS
Legacy Analog Values
®
Description
Unit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Relative
Humidity
PPM
No Units
PSI
PSI
Percent
Percent
Percent
Percent
Percent
No Units
PPM
Fahrenheit
Fahrenheit
Fahrenheit
Seconds
Seconds
Seconds
1-41