BACNET

LEGACY PARAMETERS
®
BACnet
Legacy Analog Values
®
BACnet
Default
®
Point #
Range
AV: 24
60
AV: 25
75
AV: 26
72
AV: 27
57
AV: 28
53
AV: 29
70
AV: 30
65
AV: 31
90
AV: 32
72
AV: 33
69
AV: 34
100
AV: 35
90
AV: 36
50
AV: 37
5
AV: 38
100
AV: 39
40
AV: 40
0
AV: 41
0
AV: 42
0
AV: 43
N/A
AV: 44
45
AV: 45
50
AV: 46
N/A
Table 9: BACnet
Legacy Parameter Analog Values, continued
®
1-42
BACnet
Legacy Analog Values
®
Limit
BACnet
®
Point Name
30-255
Compressor
Interstage Off
Delay
55-85
Space Cooling
Hi Reset
55-85
Space Cooling
Lo Reset
45-65
Supply Cooling
Hi Reset
45-65
Supply Cooling
Lo Reset
55-85
Occupied
Heating Setpoint
55-85
Unoccupied
Heating Setpoint
55-120
Supply Heating
Setpoint
55-85
Space Heating
Hi Reset
55-85
Space Heating
Lo Reset
55-120
Supply Heating
Hi Reset
55-120
Supply Heating
Lo Reset
40-60
Dehum Enable
Setpoint
1-10
Aux Heat
Deadband
35-100
Supply Fan Max
Percentage
40-100
Supply Fan
Minimum
Percentage
-20 - 20
Space Temp
Offset
-20 - 20
Supply Temp
Offset
-20 - 20
Space RH Offset
N/A
Leaving Water
Temp
40-60
Suction Temp
Setpoint
50-100
Compressor
Minimum
Percentage
N/A
Water Flow
Pioneer Gold 1.10 & 2.05 Controller Technical Guide
BACnet
®
Interstage off delay setpoint when unit has more than one
compressor stage
High space temperature setpoint when using space/supply reset
control in cooling mode
Low space temperature setpoint when using space/supply reset
control in cooling mode
High supply temperature setpoint when using space/supply reset
control in cooling mode
Low supply temperature setpoint when using space/supply reset
control in cooling mode
Heating mode enable setpoint when space is occupied
Heating mode enable setpoint when space is unoccupied
Temperature setpoint of the leaving discharge air while in
heating mode
High space temperature setpoint when using space/supply reset
control in heating mode
Low space temperature setpoint when using space/supply reset
control in heating mode
High supply temperature setpoint when using space/supply reset
control in heating mode
Low supply temperature setpoint when using space/supply reset
control in heating mode
Relative humidity setpoint for enabling dehumidification mode
Degrees Fahrenheit that the supply air must be under setpoint for
auxiliary heat to enable
Maximum allowed output for a variable speed supply fan
Minimum allowed output for a variable speed supply fan
Temperature offset for the space sensor
Temperature offset for the supply temperature sensor
Relative humidity offset for the space sensor
Temperature of the loop water leaving the water coil
Not Used
Not Used
GPM reading from the water flow sensor
Description
Unit
Seconds
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Relative
Humidity
Fahrenheit
Percent
Percent
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Percent
GPM