BACNET
MS/TP & IP PARAMETERS
®
BACnet
MS/TP & IP Analog Values & Binary Inputs
®
BACnet
Default
®
Point #
Range
AV:23
35
AV:24
0
AV:25
0
AV:26
0
AV:27
0
AV:28
30
AV:29
120
AV: 30
10
AV: 31
10
AV: 32
70
Table 12: BACnet
MS/TP & IP Parameter Analog Values, continued
®
BACnet
®
Point #
BI: 1
G Thermostat Call
BI: 2
Y1 Thermostat Call
BI: 3
Y2 Thermostat Call
BI: 4
O Thermostat Call
BI: 5
W1 Thermostat Call
BI: 6
Dehumidistat Call
BI: 7
Night Setback Enable
BI: 8
Night Setback Override
BI: 9
Night Setback Tstat
BI: 10
Emergency Shutdown Status
BI: 11
Waterside Economizer
BI: 12
Compressor 1 Output
BI: 13
Compressor 1 2nd Step
BI: 14
Compressor 2 Output
BI: 15
Supply Fan Low Speed
BI: 16
Supply Fan High Speed
Table 13: BACnet
MS/TP & IP Parameter Binary Inputs
®
1-48
BACnet
MS/TP & IP Analog Values
®
Limit
BACnet
®
Point Name
35-100
Supply Fan Minimum
Percentage
-20 - 20
Space Temp Offset
-20 - 20
Supply Temp Offset
-20 - 20
Space RH Offset
0 - 10
Space Sensor
Maximum Setpoint
Offset
5 - 75
Water Valve Opening
Delay Time
30 -
User Occupancy
120
Override Time
10-255
Waterside Econo
Cooling Failure Time
10-255
Waterside Econo
Heating Failure Time
55-120
Supply Reheat
Setpoint
BACnet
MS/TP & IP Binary Inputs
®
BACnet
®
Point Name
Pioneer Gold 1.10 & 2.05 Controller Technical Guide
Description
Minimum allowed output for a variable speed supply fan
Temperature offset for the space sensor
Temperature offset for the supply temperature sensor
Relative humidity offset for the space sensor
Maximum allowed user setpoint adjustment on the
touchscreen temp/humidity sensor
Amount of time given for the water valve to open before
compressor operation is allowed
Amount of time unit stays in user occupancy override
Amount of time unit stays in economizer mode before going
into compressor cooling.
Amount of time unit stays in economizer mode before going
into compressor heating.
Temperature setpoint of the discharge air while in
dehumidification mode.
Status of the G input terminal
Status of the Y1 input terminal
Status of the Y2 input terminal
Status of the O input terminal
Status of the W1 input terminal
Status of the DH input terminal
Status of the night setback enable input terminal
Status of the night setback override input terminal
Status of the night setback thermostat input terminal
Status of the emergency shutdown input terminal
Status of the waterside economizer relay output
Status of the compressor 1 relay output
Status of the compressor 1 second step relay output for a 2 stage compressor
Status of the compressor 2 relay output for a unit with 2 compressors
Status of the low speed supply fan relay output
Status of the high speed supply fan relay output
BACnet
®
BACnet
®
Description
Unit
Percent
Fahrenheit
Fahrenheit
Fahrenheit
Fahrenheit
Seconds
Minutes
Minutes
Minutes
Fahrenheit