hit counter script
Mitsubishi Electric CITY MULTI PUHY-M200-300YNW-A1 Data Book

Mitsubishi Electric CITY MULTI PUHY-M200-300YNW-A1 Data Book

Air conditioning systems

Advertisement

AIR CONDITIONING SYSTEMS
MODEL
PUHY-M200-300YNW-A1(-BS)
PUHY-EM200-300YNW-A1(-BS)

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CITY MULTI PUHY-M200-300YNW-A1

  • Page 1 AIR CONDITIONING SYSTEMS MODEL PUHY-M200-300YNW-A1(-BS) PUHY-EM200-300YNW-A1(-BS)
  • Page 2 GENERAL LINE-UP GENERAL LINE-UP I.GENERAL LINE-UP Line-up of Outdoor Units of R32 CITY MULTI Heat Pump Y-Series PUHY-M200YNW-A1(-BS) PUHY-M250YNW-A1(-BS) PUHY-M300YNW-A1(-BS) 8, 10, 12HP Heat Pump High efficiency Y-Series PUHY-EM200YNW-A1(-BS) PUHY-EM250YNW-A1(-BS) PUHY-EM300YNW-A1(-BS) 8, 10, 12HP MEES19K116...
  • Page 3: Table Of Contents

    CONTENTS Y-Series PUHY-M-YNW-A1, PUHY-EM-YNW-A1 I.Y-Series 1. SPECIFICATIONS ............................ 2 2. EXTERNAL DIMENSIONS ........................8 3. CENTER OF GRAVITY ..........................12 4. ELECTRICAL WIRING DIAGRAMS ......................13 5. SOUND LEVELS ............................14 5-1. Sound levels in cooling mode ......................14 5-2. Sound levels in heating mode......................16 6.
  • Page 4: Specifications

    1. SPECIFICATIONS Y-Series I.Y-Series 1. SPECIFICATIONS Model PUHY-M200YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 22.4 (Nominal) kcal/h 20,000 BTU/h 76,400 Power input 4.72 Current input 7.9-7.5-7.2 kW/kW 4.74 SEER kW/kW Temp. range of Indoor W.B.
  • Page 5 1. SPECIFICATIONS Y-Series Model PUHY-M250YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 28.0 (Nominal) kcal/h 25,000 BTU/h 95,500 Power input 6.96 Current input 11.7-11.1-10.7 kW/kW 4.02 SEER kW/kW Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling Outdoor D.B.
  • Page 6 1. SPECIFICATIONS Y-Series Model PUHY-M300YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 33.5 (Nominal) kcal/h 30,000 BTU/h 114,300 Power input 8.54 Current input 14.4-13.6-13.2 kW/kW 3.92 SEER kW/kW Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling Outdoor D.B.
  • Page 7 1. SPECIFICATIONS Y-Series Model PUHY-EM200YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 22.4 (Nominal) kcal/h 20,000 BTU/h 76,400 Power input 4.38 Current input 7.3-7.0-6.7 kW/kW 5.11 SEER kW/kW Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling Outdoor D.B.
  • Page 8 1. SPECIFICATIONS Y-Series Model PUHY-EM250YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 28.0 (Nominal) kcal/h 25,000 BTU/h 95,500 Power input 6.36 Current input 10.7-10.1-9.8 kW/kW 4.40 SEER kW/kW Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling Outdoor D.B.
  • Page 9 1. SPECIFICATIONS Y-Series Model PUHY-EM300YNW-A1 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 33.5 (Nominal) kcal/h 30,000 BTU/h 114,300 Power input 7.44 Current input 12.5-11.9-11.5 kW/kW 4.50 SEER kW/kW Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling Outdoor D.B.
  • Page 10: External Dimensions

    2. EXTERNAL DIMENSIONS Y-Series 2. EXTERNAL DIMENSIONS PUHY-M200, 250, 300YNW-A1(-BS) Unit: mm MEES19K116...
  • Page 11 2. EXTERNAL DIMENSIONS Y-Series PUHY-M200, 250, 300YNW-A1(-BS) Unit: mm MEES19K116...
  • Page 12 2. EXTERNAL DIMENSIONS Y-Series PUHY-EM200, 250, 300YNW-A1(-BS) Unit: mm MEES19K116...
  • Page 13 2. EXTERNAL DIMENSIONS Y-Series PUHY-EM200, 250, 300YNW-A1(-BS) Unit: mm MEES19K116...
  • Page 14: Center Of Gravity

    3. CENTER OF GRAVITY Y-Series 3. CENTER OF GRAVITY PUHY-M200, 250, 300YNW-A1 (-BS) Unit: mm Model PUHY-M200YNW-A1(-BS) PUHY-M250YNW-A1(-BS) PUHY-M300YNW-A1(-BS) PUHY-EM200, 250, 300YNW-A1 (-BS) Unit: mm Model PUHY-EM200YNW-A1(-BS) PUHY-EM250YNW-A1(-BS) PUHY-EM300YNW-A1(-BS) MEES19K116...
  • Page 15: Electrical Wiring Diagrams

    4. ELECTRICAL WIRING DIAGRAMS Y-Series 4. ELECTRICAL WIRING DIAGRAMS PUHY-(E)M200, 250, 300YNW-A1(-BS) MEES19K116...
  • Page 16: Sound Levels

    5. SOUND LEVELS Y-Series 5-1. Sound levels in cooling mode 5. SOUND LEVELS Sound level of PUHY-M300YNW-A1(-BS) Measurement condition PUHY-M200, 250, 300YNW-A1(-BS) Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard...
  • Page 17 5. SOUND LEVELS Y-Series Sound level of PUHY-EM300YNW-A1(-BS) Measurement condition PUHY-EM200, 250, 300YNW-A1(-BS) Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 76.0 62.5 63.0 60.0 54.0 49.5 44.5 40.0 61.0...
  • Page 18: Sound Levels In Heating Mode

    5. SOUND LEVELS Y-Series 5-2. Sound levels in heating mode Sound level of PUHY-M300YNW-A1(-BS) Measurement condition PUHY-M200, 250, 300YNW-A1(-BS) Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 75.0 68.5 65.5 63.0 57.5 54.0...
  • Page 19 5. SOUND LEVELS Y-Series Sound level of PUHY-EM300YNW-A1(-BS) Measurement condition PUHY-EM200, 250, 300YNW-A1(-BS) Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 75.5 68.5 66.0 63.0 58.0 54.0 50.0 47.5 64.5...
  • Page 20: Vibration Level

    6. VIBRATION LEVEL Y-Series [PUHY-M200-300YNW-A1, PUHY-EM200-300YNW-A1] 6. VIBRATION LEVEL Measurement condition Measurement frequency: 1 Hz-80 Hz Measurement point: Ground surface 20 cm away from the unit leg Installation condition: Direct installation on the concrete floor Power source: 3-phase 4-wire 380-400-415 V 50/60 Hz Operation condition: JIS condition (cooling, heating) Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product) Service panel side...
  • Page 21: Operation Temperature Range

    7. OPERATION TEMPERATURE RANGE Y-Series 7. OPERATION TEMPERATURE RANGE Cooling only Range for continuous operation Continuous operation not recommended Outdoor temperature Heating only Continuous operation not recommended Range for continuous operation Continuous operation not recommended Outdoor temperature MEES19K116...
  • Page 22: Capacity Tables

    8. CAPACITY TABLES Y-Series 8-1. Selection of Cooling/Heating Units 8. CAPACITY TABLES How to determine the capacity when less than or equal 100% indoor model size units are connected in total: The purpose of this flow chart is to select the indoor and outdoor units. For other purposes, this flow chart is intended only for reference. Determine the load (L) and the Indoor/Outdoor Temperature Temporarily select the Indoor/Outdoor Units...
  • Page 23 8. CAPACITY TABLES Y-Series How to determine the capacity when greater than 100% indoor model size units are connected in total: The purpose of this flow chart is to select the indoor and outdoor units. For other purposes, this flow chart is intended only for reference. Determine the load (L) and the Indoor/Outdoor Temperature Temporarily select the indoor/outdoor units...
  • Page 24 8. CAPACITY TABLES Y-Series <Cooling> Design Condition Outdoor Design Dry Bulb Temperature 37 ºC Total Cooling Load 19.0 kW Room1 Indoor Design Dry Bulb Temperature 27 ºC Indoor Design Wet Bulb Temperature 20 ºC Cooling Load 9.0 kW Room2 Indoor Design Dry Bulb Temperature 24 ºC Indoor Design Wet Bulb Temperature 18 ºC...
  • Page 25 8. CAPACITY TABLES Y-Series <Heating> Design Condition Outdoor Design Wet Bulb Temperature -3 ºC Total Heating Load 18.5 kW Room1 Indoor Design Dry Bulb Temperature 25 ºC 9.5 kW Heating Load Room2 Indoor Design Dry Bulb Temperature 25 ºC Heating Load 9.0 kW <Other>...
  • Page 26 8. CAPACITY TABLES Y-Series 3. Power input of outdoor unit <Cooling> (1) Rated power input of outdoor unit 5.19 kW (2) Calculation of the average indoor temperature power input coefficient Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 37 °CD.B., Indoor temp. 20 °CW.B.) 1.07 Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp.
  • Page 27 8. CAPACITY TABLES Y-Series <Heating> (1) Rated power input of outdoor unit 5.73 kW (2) Calculation of the average indoor temperature power input coefficient Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. -3 °CW.B., Indoor temp. 25 °CD.B.) 1.08 Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp.
  • Page 28: Correction By Temperature

    8. CAPACITY TABLES Y-Series 8-2. Correction by temperature CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value and the ratio below, the capacity can be observed at various temperature. Indoor unit temperature correction PUHY- M200YNW-A1 M250YNW-A1...
  • Page 29 8. CAPACITY TABLES Y-Series Indoor unit temperature correction PUHY- M200YNW-A1 M250YNW-A1 Nominal To be used to correct indoor unit capacity only 25.0 31.5 Heating 85,300 107,500 Capacity BTU/h Input 5.08 7.14 PUHY- EM200YNW-A1 EM250YNW-A1 Nominal 25.0 31.5 Heating 85,300 107,500 Capacity BTU/h Input...
  • Page 30 8. CAPACITY TABLES Y-Series Indoor unit temperature correction PUHY- M300YNW-A1 Nominal To be used to correct indoor unit capacity only 33.5 Cooling 114,300 Capacity BTU/h Input 8.54 PUHY- EM300YNW-A1 Nominal 33.5 Cooling 114,300 Capacity BTU/h Input 7.44 Indoor Temperature [°CW.B.] Outdoor unit temperature correction To be used to correct outdoor unit only Outdoor unit capacity is NOT affected by the indoor temperature.
  • Page 31 8. CAPACITY TABLES Y-Series Indoor unit temperature correction PUHY- M300YNW-A1 To be used to correct indoor unit capacity only Nominal 37.5 Heating 128,000 Capacity BTU/h Input 8.33 PUHY- EM300YNW-A1 Nominal 37.5 Heating 128,000 BTU/h Capacity Input 7.94 Indoor Temperature [°CD.B.] Outdoor unit temperature correction To be used to correct outdoor unit only Outdoor unit capacity is NOT affected by the indoor temperature.
  • Page 32 8. CAPACITY TABLES Y-Series Correction by temperature (Capacity Priority Mode only for heating) CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures. To select capacity priority mode, DipSW 6-2 must be set to ON.
  • Page 33 8. CAPACITY TABLES Y-Series Capacity Priority Mode Indoor unit temperature correction PUHY- M200YNW-A1 M250YNW-A1 To be used to correct indoor unit capacity only Nominal 25.0 31.5 Heating 85,300 107,500 Capacity BTU/h Input 5.08 7.14 PUHY- EM200YNW-A1 EM250YNW-A1 Nominal 25.0 31.5 Heating 85,300 107,500...
  • Page 34 8. CAPACITY TABLES Y-Series Indoor unit temperature correction PUHY- M300YNW-A1 Nominal To be used to correct indoor unit capacity only 33.5 Cooling 114,300 Capacity BTU/h Input 8.54 PUHY- EM300YNW-A1 Nominal 33.5 Cooling 114,300 Capacity BTU/h Input 7.44 Indoor Temperature [°CW.B.] Outdoor unit temperature correction To be used to correct outdoor unit only Outdoor unit capacity is NOT affected by the indoor temperature.
  • Page 35 8. CAPACITY TABLES Y-Series Capacity Priority Mode Indoor unit temperature correction PUHY- M300YNW-A1 To be used to correct indoor unit capacity only Nominal 37.5 Heating 128,000 Capacity BTU/h Input 8.33 PUHY- EM300YNW-A1 Nominal 37.5 Heating 128,000 Capacity BTU/h Input 7.94 Indoor Temperature [°CD.B.] Outdoor unit temperature correction To be used to correct outdoor unit only...
  • Page 36: Correction By Total Indoor

    8. CAPACITY TABLES Y-Series 8-3. Correction by total indoor CITY MULTI system has different capacities and inputs when many combinations of indoor units with different total capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for a particular application.
  • Page 37 8. CAPACITY TABLES Y-Series PUHY-M300YNW-A1 PUHY-(E)M300YNW-A1 33.5 Cooling Capacity BTU/h 114,300 Input 8.54 PUHY-M300YNW-A1 37.5 Heating Capacity BTU/h 128,000 Input 8.33 PUHY-EM300YNW-A1 Cooling 33.5 Capacity BTU/h 114,300 Input 7.44 PUHY-EM300YNW-A1 37.5 Heating Capacity BTU/h 128,000 Input 7.94 Cooling Heating Total capacity of indoor units MEES19K116...
  • Page 38: Correction By Refrigerant Piping Length

    8. CAPACITY TABLES Y-Series 8-4. Correction by refrigerant piping length CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. However, a decrease of cooling/ heating capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at 8-4-1 and 8-4-2, the capacity can be observed.
  • Page 39: Correction At Frost And Defrost

    8. CAPACITY TABLES Y-Series 8-5. Correction at frost and defrost Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be calculated by multiplying the correction factor shown in the table below. Table of correction factor at frost and defrost Outdoor inlet air temp.
  • Page 40: Optional Parts

    9. OPTIONAL PARTS CITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Refer to section "Piping Design" or the Installation Manual that comes with the Joint set for how to install the Joint set.
  • Page 41: Header

    9-2. HEADER CITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Refer to section "Piping Design" or the Installation Manual that comes with the Header set for how to install the Header set.
  • Page 42: Fin Guard

    9. OPTIONAL PARTS Y-Series 9-3. FIN GUARD PAC-FG01S-E For side surfaces of S module (a set of two pieces) ■Left side of the unit ■Right side of the unit (20) (384) (20) (384) (15.5) (15.5) 389.5 (206.5) 389.5 (206.5) (30) (30) PAC-FG01B-E For rear surface of S module...
  • Page 43: Electrical Work

    10. ELECTRICAL WORK Y-Series 10-1. General cautions 10. ELECTRICAL WORK Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power company. Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power source wiring so that it is not influenced by electric noise from power source wiring.
  • Page 44: 10-2.Power Supply For Outdoor Unit

    10. ELECTRICAL WORK Y-Series 10-2. Power supply for Outdoor unit 10-2-1. Electrical characteristics of the outdoor unit in cooling mode Symbols: MCA: Max Circuit Amps RLA: Rated Load Amps SC: Starting Current Power Units Compressor RLA (A) (50/60Hz) supply PUHY-M-YNW-A1 Unit Combination Voltage Output...
  • Page 45: 10-3.Power Cable Specifications

    Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.  The breakers for current leakage should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S-Series or equivalent). If no earth leakage breaker is installed, it may cause an electric shock. ...
  • Page 46: 10-4.Power Supply Examples

    PUHY-(E)M300YNW-A1 30A 100mA 0.1sec. or less Over-current protector Wiring breaker *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S-Series or equivalent). Non-fuse breaker *2 Ground-fault interrupter should combine using of local switch or wiring breaker. *3 It shows data for B-type fuse of the breaker for current leakage.
  • Page 47: M-Net Control

    11. M-NET CONTROL Y-Series 11-1. Transmission cable length limitation 11. M-NET CONTROL 11-1-1. Using MA Remote controller Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission. Max. length via Outdoor (M-NET cable) L1+L2+L3, L1+L2+L4+L5, L3+L4+L5, L6+L2+L3, L6+L2+L4+L5 <=500m(1000m*1)[1640ft.(3280ft.*1)] 1.25mm [AWG16] or thicker Max.
  • Page 48: 11-2.Transmission Cable Specifications

    11. M-NET CONTROL Y-Series 11-2. Transmission cable specifications Transmission cables (L M-NET remote controller cables (e MA Remote controller cables (a Shielding wire (2-core) Type of cable Sheathed 2-core cable (unshielded) CVV CVVS, CPEVS or MVVS Cable size More than 1.25 mm [AWG16] 0.3 1.25 mm [AWG22 16] 0.3 1.25 mm [AWG22 16]*1...
  • Page 49: 11-3.System Configuration Restrictions

    11. M-NET CONTROL Y-Series 11-3. System configuration restrictions 11-3-1. Common restrictions for the CITY MULTI system For each Outdoor/Heat source unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units; *OA processing unit GUF-RD(H) is considered as Indoor unit.
  • Page 50 11. M-NET CONTROL Y-Series Table 2 The equivalent power supply Category Model The equivalent power supply Transmission Booster PAC-SF46EPA-G 25 *1 Power supply unit PAC-SC51KUA Expansion controller PAC-YG50ECA BM ADAPTER BAC-HD150 AE-200E/AE-50E 0.75 System controller EW-50E LM-AP TB3 and TB7 total TB7 only TB3 only 32 *1-equivalent power...
  • Page 51 11. M-NET CONTROL Y-Series 11-3-3. Ensuring proper power supply to System controller The power to System controller (excluding AE-200E, AE-50E, EW-50E, BAC-HD150, LM-AP) is supplied via M-NET transmission line. M-NET transmission line at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor/Heat source transmission line.
  • Page 52 11. M-NET CONTROL Y-Series 11-3-4. Power supply to LM-AP 1-phase 220-240VAC power supply is needed. The power supply unit PAC-SC51KUA is not necessary when connecting only the LM-AP. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM-AP. 11-3-5.
  • Page 53: 11-4.Address Setting

    11. M-NET CONTROL Y-Series 11-4. Address setting 11-4-1. Switch operation In order to constitute CITY MULTI in a complete system, switch Rotary switch operation for setting the unit address No. and connection No. is Branch Unit address No. setting required. No.
  • Page 54 11. M-NET CONTROL Y-Series 11-4-2. Rule of setting address Unit Address setting Example Note Indoor unit Use the most recent address within the same group of indoor units. Make the indoor units address connected System control interface to the BC controller (Sub) larger than the indoor units (MAC-333IF-E) address connected to the BC controller (Main).
  • Page 55 11. M-NET CONTROL Y-Series 11-4-3. System examples Factory setting Original switch setting of the outdoors, indoors, controllers, LM-AP and BM ADAPTER at shipment is as follows. Outdoor unit : Address: 00, CN41: ON (Jumper), DipSW5-1: OFF Indoor unit : Address: 00 ME remote controller : Address: 101 LM-AP...
  • Page 56 11. M-NET CONTROL Y-Series 11-4-3-2. MA remote controller, Single-refrigerant-system, System Controller <Three outdoor units> <Two outdoor units> <One outdoor unit> CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 Group 1 Group 2 Group 3 Group 4...
  • Page 57 11. M-NET CONTROL Y-Series 11-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 Group 1 Group 2 Group 21 Indoor unit TB15...
  • Page 58 11. M-NET CONTROL Y-Series 11-4-3-4. ME remote controller, Single-refrigerant-system, No system controller <Three outdoor units> <Two outdoor units> <One outdoor unit> CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 Group 1 Group 2 Group 3 Group 4...
  • Page 59 11. M-NET CONTROL Y-Series 11-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, Lossnay, Booster for long M-NET wiring CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 Group 1 Group 2 Group 21 Indoor unit...
  • Page 60 11. M-NET CONTROL Y-Series 11-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 Group 1 Group 2 ME R/C ME R/C Group 4 Group 3 ME R/C ME R/C NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system.
  • Page 61 11. M-NET CONTROL Y-Series 11-4-3-9. AE-200E + AE-50E/EW-50E AE-200E can control max. 200 indoor units/via AE-50E/EW-50E. <Three outdoor units> <Two outdoor units> <One outdoor unit> AE-200E CN21 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1...
  • Page 62 11. M-NET CONTROL Y-Series 11-4-3-10. LM-AP LM-AP can transmit for max. 50 indoor units; If system controller (SC) is used, DipSW1-2 at LM-AP and DipSW5-1 at Outdoor unit should set to "ON". Change Jumper from CN41 to CN40 to activate power supply to LM-AP itself for those LM-AP connected without system controller (SC).
  • Page 63 11. M-NET CONTROL Y-Series ® 11-4-3-11. BACnet EW-50E (AE-200E) can control up to 50 units/groups (including Lossnay). *To use the BACnet ® function on EW-50E (AE-200E), BACnet ® license registration is required. EW-50E(01) <Three outdoor units> <Two outdoor units> <One outdoor unit> CN40 CN41 LAN2...
  • Page 64: Piping Design

    The maximum operation pressure of R32 air conditioner is 4.30 MPa [623psi]. The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table 1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
  • Page 65 12. PIPING DESIGN Y-Series Procedures for installing the branched pipes Refer to the instructions that came with the branched pipe kit (separately sold) for details. [1] Branches on the indoor-unit side ■Joint To branch pipe or indoor unit To outdoor/heat source unit Vertical installation Horizontal installation (The branched pipes must face up.)
  • Page 66: 12-2.Piping Design

    12. PIPING DESIGN Y-Series 12-2. Piping Design Rule for piping size selection Header 1st Joint Capped Joint IU: Indoor unit , OU: Outdoor unit 1. Selecting joints Select joints from Table 4-1 [Selection criteria for joints] based on the total capacity of indoor units on the downstream side. When selecting the first joint for the system to which the outdoor unit listed in Table 4-2 [See the table below for the first joint of the outdoor unit described below.] is connected, select the first joint from Table 4-2.
  • Page 67 12. PIPING DESIGN Y-Series 12-2-1. PUHY-(E)M200-300YNW-A1 Piping Note1. No Joint after Header; Piping direct to Indoor Unit from Header; Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length (m)=Actual piping length+"M"...
  • Page 68 12. PIPING DESIGN Y-Series Table 1 Piping "A" size selection rule (mm [in.]) Table 4-1 Selection criteria for joints Outdoor unit Pipe(Liquid) Pipe(Gas) Total down-stream Indoor capacity Joint PUHY-(E)M200YNW-A1 ø9.52 [3/8"] ø22.20 [7/8"] ~ M200 CMY-Y102SS-G2 PUHY-(E)M250YNW-A1 ø9.52 [3/8"] ø22.20 [7/8"] M201 ~ M400 CMY-Y102LS-G2 PUHY-(E)M300YNW-A1...
  • Page 69: 12-3.Refrigerant Charging Calculation

    12. PIPING DESIGN Y-Series 12-3. Refrigerant charging calculation At the time of shipping, the outdoor unit is charged with the refrigerant. As this charge does not include the amount needed for extended piping, additional charging for each refrigerant line will be required on site. In order that future servicing may be properly provided, always keep a record of the size and length of each refrigerant line and the amount of additional charge by writing it in the space provided on the outdoor unit.
  • Page 70 12. PIPING DESIGN Y-Series Example: PUHY-(E)M300YNW-A1 Indoor 1: M100 A: ø9.52 40 m a: ø9.52 10 m 2: M100 B: ø9.52 10 m b: ø9.52 3: M50 C: ø9.52 15 m c: ø6.35 10 m D: ø9.52 d: ø6.35 4: M40 10 m 10 m 5: M71...
  • Page 71: Outdoor Installation

    13. OUTDOOR INSTALLATION Y-Series 13-1. Requirement on installation site 13. OUTDOOR INSTALLATION 1. No direct thermal radiation to the unit. 2. No possibility of annoying the neighbors by the sound of the unit. Valves and refrigerant flow on the outdoor unit may generate noise. 3.
  • Page 72: 13-2.Spacing

    13. OUTDOOR INSTALLATION Y-Series 13-2. Spacing In case of single installation (1) When all walls are within their height limits*. [mm (in)] * Height limit Front/Right/Left/Rear Same height or lower than the overall height of the unit Required minimum distance [mm (in)] L1 (Front) L2 (Rear) L3 (Right/Left)
  • Page 73 13. OUTDOOR INSTALLATION Y-Series In case of collective installation and continuous installation • When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through, ample space between blocks of units, and sufficient space for airflow. (The areas marked with [A] in the figures below must be left open.) •...
  • Page 74: 13-3.Piping Direction

    13. OUTDOOR INSTALLATION Y-Series 13-3. Piping direction 13-3-1. Lifting method • Always use two slings to lift up the unit. Each sling must be at least 8 m (26 ft) long and must be able to support the weight of the unit. •...
  • Page 75 13. OUTDOOR INSTALLATION Y-Series 13-3-2. Installation · Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or during an earthquake. · Install the unit on a durable base made of such materials as concrete or angle steel. ·...
  • Page 76 13. OUTDOOR INSTALLATION Y-Series 13-3-4. Installation When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of the unit does not get blocked with the installation base. When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height. (Unit: mm[in.]) (E)M200, 250, 300 2×2-14[9/16]×31[1-1/4] Oval hole...
  • Page 77: 13-4.Countermeasure To Wind

    13. OUTDOOR INSTALLATION Y-Series 13-4. Countermeasure to wind Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation. A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds. To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away from the direction of the wind.
  • Page 78 Y-Series MEES19K116...
  • Page 79 - Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit. - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.

Table of Contents