hit counter script
Honeywell SmartLine RMA800 User Manual
Honeywell SmartLine RMA800 User Manual

Honeywell SmartLine RMA800 User Manual

Foundation fieldbus remote indicator
Table of Contents

Advertisement

Foundation Fieldbus
RMA803 Remote Indicator
User's Guide
34-ST-25-51
Revision 4
March 2020
Honeywell Process Solutions

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SmartLine RMA800

  • Page 1 Foundation Fieldbus RMA803 Remote Indicator User's Guide 34-ST-25-51 Revision 4 March 2020 Honeywell Process Solutions...
  • Page 2 © Copyright 2020 by Honeywell, Inc. Revision 4, March 2020 While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
  • Page 3 About This Document This guide provides the details of programming Honeywell RMA803 Remote Indicator for applications involving FOUNDATION Fieldbus protocol. For installation, wiring, and maintenance information, refer to the RMA803 Remote Indicator User Manual. The configuration of your Remote Indicator depends on the mode of operation and the options selected for it with respect to operating controls, displays and mechanical installation.
  • Page 4 Patent Notice The Honeywell Remote Indicator family is covered by one or more of the following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending. Support and Contact Information For Europe, Asia Pacific, North and South America contact details, see back page or refer to the appropriate...
  • Page 5 Symbol Definitions The following table lists those symbols used in this document to denote certain conditions. Symbol Definition ATTENTION: Identifies information that requires special consideration. TIP: Identifies advice or hints for the user, often in terms of performing a task. REFERENCE -EXTERNAL: Identifies an additional source of information outside of the bookset.
  • Page 6 Symbol Definition Earth Ground: Functional earth connection. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
  • Page 7 Terms and Acronyms Term Definition Alarm The detection of a block leaving a particular state and when it returns back to that state. Analog Input (function One of the standard function blocks define by the block) Foundation Fieldbus Absolute Pressure Application A software program that interacts with blocks, events and objects.
  • Page 8 Term Definition Flash Download Tool Foundation Fieldbus Foundation Fieldbus Communications protocol for a digital, serial, two-way system which interconnects industrial field equipment such as sensors, actuators and controllers. Field Termination Assembly Function Block An executable software object that performs a specific task, such as measurement or control, with inputs and outputs that connect to other function blocks in a standard way.
  • Page 9 Term Definition Object Dictionary Definitions and descriptions of network visible objects of a device. There are various object dictionaries within a device. The dictionaries contain objects and their associated parameters which support the application in which they are contained. Objects Entities within the FBAP, such as blocks, alert objects, trend objects, parameters, display lists, etc.
  • Page 10 Term Definition Upper Range Value Universal Station Volts Alternating Current Volts Direct Current Virtual A defined communication endpoint. Fieldbus Communication communications can primarily only take place along an Reference active communications "path" that consists of two VCR endpoints. Virtual Field Device A logical grouping of "user layer"...
  • Page 11: Table Of Contents

    Contents INTRODUCTION ................1 About the RMA803 Remote Indicator ............1 Features and Options ..................3 RMA803 major assembly and electronic housing components....4 Features of a Remote Indicator ..............5 RMA803 Remote Indicator Nameplate ............6 Safety Certification Information ..............6 Display Options ....................
  • Page 12 Editing a Numeric Value ................17 Selecting a new setting from a list of choices ..............17 The Advanced Display Menus ..................... 18 Advanced Displays ..................25 Button operation during monitoring ..................27 RMA803 FF REMOTE INDICATOR CONFIGURATION ..... 28 Importing the RMA803 FF Device Description (DD) files ......
  • Page 13 5.11 MAO Block ....................87 Execution ..........................87 Parameter list ........................88 Attributes ..........................89 5.12 Configuring the Remote Indicator using Field Device Manager (FDM) system RMA803 FF REMOTE INDICATOR OPERATION ...... 90 Operational considerations................90 LAS Capability ........................90 Special Non-volatile parameters and NVM Wear-out ............
  • Page 14 Restoring the Remote Indicator to default settings ........ 111 Remote Indicator Diagnostics .................... 111 Function Block Faults ......................111 Understanding simulation mode ............... 112 About simulation mode jumper ..................112 Setting simulation jumper ....................112 Enabling simulation mode ....................113 Simulation mode truth table ....................
  • Page 15 Tables Table 1: Feature and Options ..................3 Table 2: Available Display Characteristics ..............6 Table 3: Remote Indicator installation verification tasks ..........7 Table 4: Remote Indicator parameters ................8 Table 5: Three-Button Option Functions ............... 16 Table 6: Three-Button Data Entry.................. 17 Table 7: Advanced Display Main Menu Structure ............
  • Page 16 Figures Figure 1: RMA803 Major assemblies ................4 Figure 2: Electronic Housing components............... 4 Figure 3: Typical Bracket Mounted Installations............11 Figure 4: Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe ....12 Figure 5: Two Position FF Terminal Block ..............13 Figure 6: Three-Button Option ..................
  • Page 17: Introduction

    1. Introduction About the RMA803 Remote Indicator The Honeywell RMA803 is a Foundation Fieldbus Remote Indicator that provides the following benefits to the user: Connectivity The RMA803 can be used with any Foundation Fieldbus device. The values from these Fieldbus devices can be connected to the RMA803 via the MAO function block (for example) and then sent to the LCD display via the LCD Transducer block.
  • Page 18 Additional Function Blocks The RMA803 consists of two Application Software options, which are: Standard Operating Software – Consists of Resource block, AI block, LCD Transducer block, • Diagnostic Transducer block, and MAO (Multiple Analog Output) function block • Additional Function Blocks – Consists of PID block, Signal Characterizer block, Arithmetic block, Input Selector block and Integrator block.
  • Page 19: Features And Options

    Features and Options The RMA803 Foundation Fieldbus Remote Indicator has the following features: Table 1: Feature and Options Feature/Option Standard/Available Options Communication Protocols Fieldbus and only Advanced Display Human-Machine Interface (HMI) Advanced Digital Display: Options (Advanced Display) 0, 90, 180, & 270 degree viewing position adjustments Standard and custom measurement units available.
  • Page 20: Rma803 Major Assembly And Electronic Housing Components

    RMA803 major assembly and electronic housing components The following illustrations depict the major assembly and electronic housing components. Figure 1: RMA803 Major assemblies Figure 2: Electronic Housing components Page 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 21: Features Of A Remote Indicator

    Features of a Remote Indicator The Remote Indicator is a configurable intelligent field device which functions as an output and status indicator for any FF device. The core functionalities of the field device include: • Displaying Process Variable (PV) • Function Block Application Process (FBAP) •...
  • Page 22: Rma803 Remote Indicator Nameplate

    RMA803 Remote Indicator Nameplate The Remote Indicator nameplate mounted on the bottom of the electronics housing (see Figure 1) lists its model number, physical configuration, electronics options, accessories, certifications, and manufacturing specialties. Figure 3 –Typical RMA803 Nameplate You can readily identify the series and basic Remote Indicator type from the last digit in the key number.
  • Page 23: Getting Started

    2. Getting started Verifying the installation Verifying Remote Indicator installation tasks After the Remote Indicator is installed and powered up, you can verify communication between the Remote Indicator and the field devices on the network. Table 3 outlines the steps for identifying and checking the Remote Indicator on a Fieldbus network.
  • Page 24: Verifying Communication With The Remote Indicator

    Verifying communication with the Remote Indicator On the operator interface, establish communication with the device on the Fieldbus network. If the device is not visible on the network, verify that the device has been installed properly. Identify the Remote Indicator Verify the Device ID of the Remote Indicator by checking the device parameters.
  • Page 25: Establishing Communication With Host Systems

    Establishing communication with host systems The RMA803 Remote Indicator establishes communication with the host systems using a DD or DTM. Device Description (DD) DD is a binary file that provides the definition for parameters in the FBAP of the RMA803 Remote Indicator.
  • Page 26 This page is left blank intentionally. Page 10 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 27: Installation And Startup

    Mounting Remote Indicator Summary Remote Indicator models can be attached to a two-inch (50 millimeter) vertical or horizontal pipe using Honeywell’s optional pipe mounting bracket. Honeywell’s optional wall mounting bracket is also shown below. Figure 3 shows typical bracket-mounted installations.
  • Page 28: Mounting Dimensions

    Remote Indicator. * Honeywell drawings can be supplied on request. Bracket Mounting Procedure Align the two mounting holes in the Remote Indicator with the two slots in the mounting bracket and assemble the (2) M8 hex cap screws, (2) lockwashers and (2) flat washers provided.
  • Page 29: Wiring A Remote Indicator

    Wiring a Remote Indicator Overview The Remote Indicator is designed to operate as part of a Fieldbus Network. Loop wiring is connected to the Remote Indicator by simply attaching the loop wires to the terminals on the Remote Indicator terminal block in the Electronics Housing shown in Figure 5. Connect the Loop Power wiring shield to earth ground only at the power supply end.
  • Page 30: Fieldbus Network Wiring

    Feed both loop powered leads through the Ferrite core, 32301350-001, and then back around and through a second time. Connect both loop power leads to the loop terminals. Torque terminal screws to 0,6 N.m (5.3 lbf.in) to 0.8 N.m (7.0 lbf.in). Note.
  • Page 31: Operation

    4. Operation 4.1 Overview This section provides the information and processes involved for Fieldbus device operation using the 3-button option. 4.2 Three-Button Operation The RMA803 optional three-button interface provides a user interface and operation capability without opening the Remote Indicator. Figure 6 shows the location of the three-button option and the labels for each button.
  • Page 32: Menu Navigation

    Table 5: Three-Button Option Functions Physical Advanced Action Display Button Increment Scroll to previous menu item in an active list.  Left Scroll through alphanumeric list to Move cursor Up desired character (ex. for entering Tag names or numeric values) Decrement Scroll to next menu item in an active list.
  • Page 33: Editing A Numeric Value

    Table 6: Three-Button Data Entry Screen Numeric data entry Text entry Symbol Display the high limit for this parameter. ▲ Not Available This symbol only appears in the left-most position of the data entry field. Display the low limit for this parameter. ▼...
  • Page 34: The Advanced Display Menus

    The Advanced Display Menus The Advanced Display menus are organized into three levels, as shown by Table 7. There is a <Return> menu item at each level that allows the user to return to the previous level. Table 7: Advanced Display Main Menu Structure Level 1 Level 2 Level 3...
  • Page 35: Table 9: Display Setup Menus

    Table 9: Display Setup Menus <Return> Return to the Level 1 menu <Return> Press ↵ to enter Adjust the LCD menu selection contrast level. ↑ and ↓ to select Range from 1 to 9. Contrast Set Contrast number. Default: 5 ↵...
  • Page 36 Pressure inH2O inHg ftH2O mmH2O mmHg mbar gf/cm2 kgf/cm2 Torr inH2O inH2O mmH2O Temperature Screens 1 thru 8 °C (continued) °F °R Shows the selected Display Units Read Only Display Units. Volumetric Flow gal/min L/min m3/h Mgal/d gal/h Mass Flow kg/min kg/h lb/min...
  • Page 37 mile Shows the selected Custom Units Read Only units. None Shows the selected Decimal Read Only Screens decimal value. X.XX 1 thru 8 X.XXX (continued) Shows the selected low limit. Disp Low Limit ######### Read Only Shows the selected Disp High Limit ######### high limit.
  • Page 38: Table 10: Information Menus

    Table 10: Information Menus <Return> Return to the Level 1 menu <Return> Display The firmware version of the Display Firmware Version Read Only Module <Return> The firmware version of the Electronics Firmware Version Read Only Module Elec Module The communications protocol of the Remote Indicator: Protocol Read Only...
  • Page 39: Figure 7: Locating Simulation And Write Protect Jumpers

    The following procedure outlines the steps for positioning the write protect and failsafe jumpers on the electronics module. See Figure 7 for the locations of the failsafe and write protect jumpers. Figure 7: Locating Simulation and Write Protect Jumpers Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 23...
  • Page 40 Table 11: Fieldbus Simulation and Write Protect Jumpers Image Description Fieldbus Simulation Mode = OFF Write Protect = OFF (Not Protected) Fieldbus Simulation Mode = OFF Write Protect = ON (Protected) Fieldbus SIM Mode = ON Write Protect = ON (Protected) Turn OFF Remote Indicator power (Power removal is only required in accordance with area safety approvals.
  • Page 41: Advanced Displays

    Advanced Displays As shown in Figure 8, the Advanced Display provides three formats. Figure 8 lists and describes the fields in each of the three Advanced Display formats. Essentially, all three formats provide the same information, but with the following differences: •...
  • Page 42: Table 11: Advanced Displays With Pv Format Display Indications

    Table 11: Advanced Displays with PV Format Display Indications Display Indicator What It Means Diagnostic / Diagnostic condition present Maintenance This indicator is displayed any time a diagnostic is present in the Remote Indicator, either Critical or Non-Critical. If a Critical Diagnostic is present, the message “Critical Diag”...
  • Page 43: Button Operation During Monitoring

    PV Function Block The Function Block Mode is only displayed for Foundation Fieldbus Remote Mode Indicators. The eight possible Modes are shown below. OOS Out Of Service RCas Remote Cascade Auto Automatic Rout Remote Output Man Manual IMan Initialization Manual Cascade Local Override Process Variable Tag...
  • Page 44: Rma803 Ff Remote Indicator Configuration

    5. RMA803 FF Remote Indicator Configuration ATTENTION Additional Function blocks are available post liscensing. Importing the RMA803 FF Device Description (DD) files Importing the DD to Experion PKS ATTENTION Experion release compatibility Experion Release DD Compatibility 410.4 400.4 + CP3 311.3 The steps in the following procedure are specific to Experion R410 only.
  • Page 45 Step Action The following dialog box appears, Click OK Type the Device Type Name, and then click Save As (only applicable if the same DD version is available and being imported). The following dialog box appears, Click OK. The following dialog box appears, Click OK.
  • Page 46 The device is created in the Library-Containment window under the folder named Honeywell. From the Library-Containment window, drag and drop the device into the corresponding FF link on the Project-Assignment window. You are prompted to name the new function block. If you want to change the name in the destination column, type the new name or if you want to use the default name, click Finish.
  • Page 47 On the Monitoring-Assignment window, you can notice that device on the Project-Assignment window has been loaded to the corresponding FF link. Right-click the device, and then click Activate >> Selected Item(s) and Content(s). The device is commissioned. ATTENTION Note that after importing the DD, you have to create control strategies. Control strategy A control strategy is an organized approach to define a specific process using detailed information •...
  • Page 48: Configuring The Function Block Application Process

    Configuring the function block application process About the Function Block Application Process (FBAP) The RMA803 Remote Indicator has one resource block, two transducer blocks, and seven function blocks respectively. The DD-View feature supports all the 9 permanent blocks. The FBAP provides the block related information in a much more organized way.
  • Page 49 Block_ERR Block Alarms Description Output Failure Output Failure detected by this block/back calculation input has a status of Bad or Device Failure. NOTE: It is not applicable to the Remote Indicator. Memory Failure A diagnostic algorithm has found a failure in memory (includes all types) and the device is still able to communicate that condition.
  • Page 50: Process Alarms

    Process Alarms A set of alarms that indicates a process value has exceeded a certain threshold. Process Alarm detection is based on the OUT value. The alarm limits can be configured for the following standard alarms: • High (HI_LIM) • High High (HI_HI_LIM) •...
  • Page 51: Resource Block

    Resource block The Resource block is used to describe characteristics of the Fieldbus device such as the device name, manufacturer, and serial number. The block does not contain any input or output parameters. The block contains data that is specific to the hardware associated with the resource. The resource block monitors and controls the general operation of the device hardware.
  • Page 52: Execution

    Execution CYCLE TYPE The parameter CYCLE_TYPE is a bit string that defines the types of cycles that are available for the resource and supports scheduled and block execution. CYCLE_SEL allows the person doing the configuration to indicate that one or more of these execution types can be used by the device. MIN_CYCLE_T is the minimum time to execute a cycle;...
  • Page 53: Soft W Lock And Hard W Lock

    SOFT W LOCK and HARD W LOCK There are two types of write locks: Hardware write lock and Software write lock. The software write lock is used to lock the device. The software write lock does not need a jumper. A hardware write lock is provided with a jumper in the device to perform the write lock operation.
  • Page 54: Field Diagnostics

    Field Diagnostics The Resource block acts as a coordinator for alarms. There are four alarm parameters: Fail alarm, Offspec alarm, Maintenance alarm, and Check alarm. It contains information of device errors that are detected by the Remote Indicator. Based on the error detected, the device provides the recommended actions;...
  • Page 55 MAINT_ALARMS A maintenance alarm indicates either the device or some part of the device needs maintenance. If the condition is ignored, the device eventually fails. • MAINT_MAPPED parameter contains a list of conditions indicating either the device or some part of the device needs maintenance soon. If the condition is ignored, the device eventually fails.
  • Page 56 OFFSPEC_ALARMS Indicates if the device is operating outside its specified range or internal diagnostics indicates deviations from measured or set values due to internal problems in the device or process characteristics. • OFFSPEC_MAPPED parameter contains a list of informative conditions that do not have a direct impact on the device's primary functions.
  • Page 57: Parameter List

    MAINTENANCE_MODE It indicates if the device is available for maintenance. When the resource block is in AUTO mode, MAINTENANCE_MODE parameter displays the text as 'Chk with Oper' i.e., the device is in process and is not available for maintenance. When the resource block is in OOS mode, MAINTENANCE_MODE parameter displays the text as ‘Avail for Maint' i.e., the device is out of process and is available for maintenance.
  • Page 58 Parameter Description CYCLE_TYPE Identifies the block execution methods available for this resource. The supported cycle types are: SCHEDULED, and COMPLETION_OF_BLOCK_EXECUTION. CYCLE_SEL Used to select the block execution method for this resource. MIN_CYCLE_T Time duration of the shortest cycle interval of which the resource is capable. MEMORY_SIZE Available configuration memory in the empty resource.
  • Page 59 Parameter Description WRITE_ALM This alert is generated if the write lock parameter is cleared. ITK_VER Major revision number of the interoperability test case used in certifying this device as interoperable. The format and range are controlled by the Fieldbus Foundation. The current ITK version is 6.0.1. FD_VER A parameter equal to the value of the major version of the Field Diagnostics specification that the device is designed for.
  • Page 60 Parameter Description FD_CHECK_MAP Mapped CHECK_ALM alarm conditions. Corresponds bit for bit to the CHECK_ACTIVE. A bit on means that the corresponding alarm condition is Mapped and is detected. A bit off means the corresponding alarm condition is disabled and is not detected. FD_CHECK_MASK Mask of CHECK_ALM.
  • Page 61: Diagnostic Transducer Block

    Diagnostic Transducer block The Diagnostics Transducer block supports the Remote Indicator electronic diagnostics. ATTENTION The electronics temperature can be tracked in 8 ways: • Current Temperature • Units • Maximum Temperature • Minimum Temperature • Maximum Temperature Accumulated Minutes • Minimum Temperature Accumulated Minutes •...
  • Page 62: Parameter List

    STRESS_MONITOR into an algorithm to calculate an estimated percent of time that the Remote Indicator has spent in stressful conditions. HON_RES_1 Reserved for Honeywell use only. HON_RES_2 Reserved for Honeywell use only. Page 46 Foundation Fieldbus RMA803 Remote Indicator User's Guide...
  • Page 63 Attributes Supported Modes The block supports the following modes: • AUTO (Automatic) • OOS (Out of Service). Alarm Types The block supports standard block alarms (see section 5.2). Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 47...
  • Page 64: Lcd Transducer Block

    LCD Transducer block The LCD Transducer block supports Advanced Display. The block is used to configure the advanced display connected to the RMA803 Remote Indicator. The block stores the LCD configurations, and sends these values to the Display while the Remote Indicator is powered up or restarted. Figure 9: LCD Transducer block ATTENTION The initial configuration of LCD transducer is configured to show eight screens.
  • Page 65: Table 17: Lcd Parameters

    Table 17: LCD parameters Block FF Parameter PID BLOCK (PID) CAS_IN BKCAL_IN BKCAL_OUT RCAS_IN ROUT_IN RCAS_OUT ROUT_OUT FF_VAL TRK_VAL ARITHMETIC FUNCTION BLOCK IN_LO IN_1 IN_2 IN_3 INTEGRATOR BLOCK IN_1 IN_2 SIGNAL CHARACTERIZER BLOCK OUT_1 OUT_2 IN_1 IN_2 INPUT SELECTOR BLOCK IN_1 IN_2 IN_3...
  • Page 66 Block FF Parameter IN_6 IN_7 IN_8 MULTIPLE ANALOG OUTPUT BLOCK IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 AI BLOCK FIELD_VAL DIAGTB BLOCK EL_TEMP VALUE Page 50 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 67: Parameters List

    Parameters List Table 18: LCD Transducer block parameters Parameter Description The revision level of the static data associated with the function ST_REV block. The user description of the application of the block. TAG_DESC Used to identify grouping of blocks. STRATEGY ALERT_KEY The identification number of the plant unit.
  • Page 68 Parameter Description UNIT_TYPES Unit selection for screen process value. Appropriate units need to be selected based on the configured parameter. If desired units are not present, 'custom' may be selected. The UNIT_TYPES is present in all the eight screens: UNIT_TYPES_1, UNIT_TYPES_2, UNIT_TYPES_3, UNIT_TYPES_4, UNIT_TYPES_5, UNIT_TYPES_6, UNIT_TYPES_7 and UNIT_TYPES_8 CUSTOM_UNIT...
  • Page 69 Attributes Supported Modes The block supports the following modes: • AUTO (Automatic) • OOS (Out of Service). Alarm Types The block supports standard block alarms (see section 5.2). Note: Additional Function blocks (PID block, Signal Characterizer block, Arithmetic block, Input Selector block and Integrator block) are available only for a licensed version.
  • Page 70: Proportional Integral Derivative (Pid) Block With Auto Tune

    Proportional Integral Derivative (PID) block with auto tune The PID block is the key to many control schemes, and it is commonly used. The PID function integrates the errors. If there is difference in process time constants of a primary process and secondary process measurement, then the block can be cascaded if required.
  • Page 71: Execution

    Execution The Process Value to be controlled is connected to the IN input. The value is passed through a filter, and its time constant is PV_FTIME. The value is then shown as the PV, which is used in conjunction with the SP in the PID algorithm. A PID does not integrate if the limit status of IN input is constant, or if further control action based on the PID error proceeds IN input further towards its active status limit.
  • Page 72 PID Control block is an algorithm that produces an output signal in response to the measured variable and the setpoint. The PID block allows you to choose either a standard PID control equation (Ideal) or a robust PID equation defined by Honeywell. This selection is defined in the PID_FORM parameter.
  • Page 73: Table 19: Pid Tuning Parameters

    Ideal PID Fixed for Ideal PID form - not configurable. Robust PID 2 • T 7500 Zero permitted which implies no output lag. BAL_TIME Not used in Honeywell Implementation. Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 57...
  • Page 74: Auto Tuning

    Auto tuning Cycle tuning The PID block supports the Cycle tuning algorithm. In Cycle tuning, the tuning parameter values are derived from the process response to the resultant action of causing the PV to oscillate about a SP value. The tuning method uses the measured ultimate gain and period to produce tuning parameter values, by using the relationship developed by Ziegles Nichols equations.
  • Page 75: Parameter List

    Parameter list Table 20: PID block parameters Parameter Description ST_REV The revision level of the static data associated with the function block. The revision value is incremented each time a static parameter value in the block is changed. TAG_DESC The user description of the application of the block. STRATEGY Used to identify grouping of blocks.
  • Page 76 Parameter Description BYPASS Used to override the calculation of the block. When enabled, the SP is sent directly to the output. CAS_IN The remote setpoint value from another block. SP_RATE_DN Ramp rate for downward SP changes. When the ramp rate is set to zero, the SP is used immediately.
  • Page 77 Parameter Description TRK_VAL The value (after scaling from TRK_SCALE to OUT_SCALE) APPLIED to OUT in LO mode. FF_VAL The feedforward control input value and status. FF_SCALE The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with the feedforward value (FF_VAL).
  • Page 78 Working setpoint. This is the setpoint value after absolute and rate limits have been applied. Deviation alarms are computed on this value. It is a read only parameter. BLOCK_TEST An internal Honeywell test parameter. Page 62 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 79: Attributes

    Parameter Description AT_TYPE Auto Tune Selection supports two types: Disable, Cycle Tune. TUNING_CRITERIA Tuning Criteria supports two types: Normal, Fast. TUNE_REQ Tuning Request performs auto tuning process. Auto Tune Indicator indicates Auto tune ON/OFF. AT_MODE Auto Tune Mode supports two options: AT Ready, Inactive •...
  • Page 80: Input Selector Block

    Input Selector block The Input Selector block performs maximum, minimum, middle, average and ‘first good’ input selection. The Input Selector block provides selection of up to eight inputs and generates an output based on the selected type of input. The block functions as a rotary position switch, or a validated priority selection based on the use of the first good parameter and the disable_n parameter.
  • Page 81: Figure 13 : Input Selector Schematic Diagram

    Selection Processing • If OP_SELECT is non-zero, the OP_SELECT value determines the selected input, irrespective of the SELECT_TYPE selection. The value of SELECTED is the number of the input used. • If SELECT_TYPE is ‘First Good’, it transfers the value of the first remaining input to the output of the block.
  • Page 82: Parameters List

    Parameters List Table 21: Input Selector block parameters Parameter Description ST_REV The revision level of the static data associated with the function block. The revision value increments each time a static parameter value in the block is changed. TAG_DESC The user description of the application of the block. STRATEGY Used to identify grouping of blocks.
  • Page 83 Parameter Description DISABLE_5 Parameter to switch off the input from being used. 0-Use, 1 -Disable. DISABLE_6 Parameter to switch off the input from being used. 0-Use, 1 -Disable. DISABLE_7 Parameter to switch off the input from being used. 0-Use, 1 -Disable. DISABLE_8 Parameter to switch off the input from being used.
  • Page 84: Attributes

    Attributes Supported The block supports the following modes: Modes • AUTO (Automatic) • MAN (Manual) • OOS (Out of Service). Alarm Types The block supports standard block alarms, (see section 5.2). Status During normal operations, the value and status of the selected input Handling is shown by OUT.
  • Page 85: Integrator Block

    Integrator block The Integrator block integrates a variable as a function of time, and also accumulates the counts from a Pulse Input block. The block is used as a totalizer that counts up until reset or as a batch totalizer that has a setpoint, and the integrated or accumulated value is compared to pre-trip and trip settings.
  • Page 86: Figure 15: Two Rate Inputs

    The usage is as follows: Rate It is used when the variable connected to the input is a rate, that is Kg/s, w, Gal/hour, and so on. This input can come from the rate output OUT of an Analog Input block. Accum It is used when the input comes from the OUT_ACCUM output of a Pulse Input block, which represents a continuous accumulation of pulse counts from a transducer, or from the output of...
  • Page 87 If the input option is Accum The Integrator block determines the number of additional counts from the counter input readings from the last execution. The difference in count is determined as follows: • If the difference between the reading in one cycle and the reading in the preceding cycle is less than 500,000 or greater than (- 500,000), the difference must be taken as the variation.
  • Page 88 Integration of Inputs There are three internal registers used for the totalization: • Total = The net increment is added every cycle, irrespective of the status. • Atotal = The absolute value of the net increment is added every cycle, irrespective of status. •...
  • Page 89 Resetting the totals The block uses a discrete input RESET_IN to reset the internal integration registers. The operator can send a command to reset the same registers by making OP_CMD_INT = RESET. This is a momentary switch that turns-off when the block is evaluated. The option “Confirm Reset” in INTEG_OPTS, if set, prevents another reset from occurring until the value 1 has been written to RESET_CONFIRM.
  • Page 90 When this option is selected, only reverse flows is considered for integration. If there is no reverse flow inputs (whose value is negative), and if one inputs is forward (whose value is positive) the integration continues. Note: If both the inputs are forward, then the integration stops. INTEG_OPTS: 0 (Use uncertain) When this option is selected, the input (IN_1/IN_2) whose status is Uncertain is considered for integration.
  • Page 91: Parameters List

    Parameters List Table 22: Integrator block parameters Parameter Description ST_REV The revision level of the static data associated with the function block. TAG_DESC The user description of the application of the block. STRATEGY Used to identify grouping of blocks. This data is not checked of processed by the block.
  • Page 92 Parameter Description RESET_IN Resets the totalizers STOTAL Indicates the snapshot of OUT just before a reset RTOTAL Indicates the totalization of “Bad” or “Bad” and “Uncertain” inputs, according to INTEG_OPTIONS. SRTOTAL The snapshot of RTOTAL just before a reset The snapshot of TOTAL_SP. INTEG_TYPE Defines the type of counting (up or down) and the type of resetting (demand or periodic)
  • Page 93: Attributes

    Attributes Supported The block supports the following modes: Modes • AUTO (Automatic) • MAN (Manual) • OOS (Out of Service). Alarm Types The block supports standard block alarms, (see section 5.2). Status If an input has status as Uncertain or Bad, then the limit status of Handling the inputs is ignored, as is the sub status.
  • Page 94: Arithmetic Block

    Arithmetic block The Arithmetic block is designed for using popular measurement math functions easily. The math algorithm is selected by name and the type of function to be performed. The block is used for calculating measurements from a combination of signals from the sensors. The block must not be used in a control path.
  • Page 95: Figure 17: Arithmetic Schematic Diagram

    Figure 17: Arithmetic schematic diagram The remaining three inputs (IN_1, IN_2, and IN_3) are combined with the PV in a selection of four term math functions. To ensure that the PV enters the equation with the right units, the inputs used to form the PV must come from devices with the desired engineering units.
  • Page 96 2. Flow compensation, square root. Usually, IN_1 is pressure, IN_2 temperature, and IN_3 is the ���������������� = ����×�������� compressibility factor Z. (����_1) (����_2) � ���� = × [���� ���� ���� ���� ���� ��������] (����_3) 3. Flow compensation, approximate. Both IN_2 and IN_3 would be connected to the same ����������������...
  • Page 97: Parameter List

    Parameter List Table 23: Arithmetic block parameters Parameter Description ST_REV The revision level of the static data associated with the function block. The revision value increments each time a static parameter value in the block is changed. TAG_DESC The user description of the application of the block. STRATEGY Used to identify grouping of blocks.
  • Page 98: Attributes

    Parameter Description BIAS_IN_1 The bias value for IN_1. GAIN_IN_1 The proportional gain (multiplier) value for IN_1. BIAS_IN_2 The bias value for IN_2. GAIN_IN_2 The proportional gain (multiplier) value for IN_2. BIAS_IN_3 The bias value for IN_3. GAIN_IN_3 The proportional gain (multiplier) value for IN_3. COMP_HI_LIM Determines the high limit of the compensation input.
  • Page 99: 5.10 Signal Characterizer Block

    5.10 Signal Characterizer block The Signal Characterizer block describes the input/output relationship for any type of function. The block has two paths, each with an output that is a non-linear function of the corresponding input. The non-linear function is configured based on a single look-up table with 21 arbitrary x-y pairs. To use the block in a control or process signal path, the status of an input is provided to the corresponding output.
  • Page 100: Figure 19: Signal Characterizer Curve

    To derive the output value that corresponds to the input, use the following formula, y = mx + c Where, • m is the slope of the line. • c is the y-intercept of the line Figure 19: Signal characterizer curve The values of x must increase sequentially for interpolation to be applicable.
  • Page 101: Parameter List

    Parameter list Table 24: Signal Characterizer block parameters Parameter Description ST_REV The revision level of the static data associated with the function block. The revision value is incremented each time a static parameter value in the block is changed. TAG_DESC The use description of the intended application of the block.
  • Page 102: Attributes

    Attributes Supported The block supports the following modes: Modes • AUTO (Automatic) • MAN (Manual) • OOS (Out of Service). Alarm Types The block supports standard block alarms, (see section 5.2). Status OUT_1 shows the status of IN_1 and OUT_2 shows the status of Handling IN_2.
  • Page 103: 5.11 Mao Block

    5.11 MAO Block Execution The MAO block provides its eight input parameters to the I/O subsystem. The output function block acts upon the inputs from another function block and passes its output to the LCD Transducer block. However, if an input has a fault state status, the previous value or a user set value (FSTATE_VAL1 - FSTATE_VAL8) is passed depending on the options (MS_OPTS) that have been enabled.
  • Page 104: Parameter List

    Use fault state value on Used when the input 4 is in the fault state at restart 4 restart Use fault state value on Used when the input 5 is in the fault state at restart 5 restart Use fault state value on Used when the input 6 is in the fault state at restart 6 restart...
  • Page 105: Attributes

    FSTATE_TIME The delay time(in seconds) the MAO function block takes to set the fault state status if an input becomes Bad and stays in that state fault state. FSTATE_VAL1 A value transferred as input 1 to LCD Transducer Block during fault state condition.
  • Page 106: Rma803 Ff Remote Indicator Operation

    6. RMA803 FF Remote Indicator Operation Operational considerations There are a number of considerations that must be noted when configuring a Remote Indicator to operate in a fieldbus network. LAS Capability The Remote Indicator is capable of operating as the Link Active Scheduler (LAS). The LAS is a fieldbus feature which controls traffic on the network, such as controlling token-rotation and coordinating data publishing.
  • Page 107: Performing Block Instantiation

    Figure 21: Connecting the Remote Indicator to the handheld Performing block instantiation About block instantiation A block instance is a copy of an available block in the device. There are totally 10 permanent blocks, and ten instances of 4 functional blocks can be created. Only 4 blocks support instantiation in a device.
  • Page 108: Rma803 Ff Remote Indicator Maintenance

    7. RMA803 FF Remote Indicator Maintenance 7.1 Overview This section provides information about preventive maintenance and replacing damaged parts. The topics covered in this section are: • Replacement of damaged parts such as the Remote Indicator Printed Wiring Assembly (PWA). 7.2 Preventive Maintenance Practices and Schedules The RMA803 Remote Indicator does not require any specific maintenance at regularly scheduled intervals.
  • Page 109 Turn OFF Remote Indicator power (Power removal is only required in accordance with area safety approvals. Power removal is only required in Class 1 Div 1 Explosionproof and Class 1 Div 2 environments). • When removing the Communications Module with power applied, the loop will go to 0V.
  • Page 110: Downloading The Firmware

    12. Loosen the End Cap locking screw and unscrew the End Cap from the Field Wiring side of the Remote Indicator housing. 13. Select the proper Communication/External Configuration upgrade kit label from the label strip provided and adhere to the inside of the Field Wiring compartment End Cap. 14.
  • Page 111: Downloading The File

    This reduces the traffic on the link and therefore reduces the time required for the download to complete. Parallel Firmware downloads from single CB Firmware downloads to a single FIM should be done from single CB instance. This reduces the chance of initiating multiple downloads to the same H1 link from different users.
  • Page 112: Licensing For Function Blocks

    Licensing for Function Blocks Enabling the ‘Additional Function blocks’ option in device requires user to activate the license. Therefore, the following steps need to be followed in order to activate that option: If the license is required after the device was originally shipped: •...
  • Page 113: Rma803 Ff Remote Indicator Troubleshooting

    8. RMA803 FF Remote Indicator Troubleshooting Troubleshooting overview This section contains information to help you identify the faults in devices and the recommended actions to correct them. Troubleshooting is performed to determine the cause of the fault by analyzing the device indications (such as device not visible on network or not able to write values to parameters.) Device status and faults The Remote Indicator constantly runs internal background diagnostics to monitor the functions and...
  • Page 114: Troubleshooting The Remote Indicator

    Troubleshooting the Remote Indicator Device not visible on the network If a device cannot be seen on the fieldbus network, the device may not be powered up or possibly the supervisory or control program is not able to find (or polling) the node address of that device. See the following table for possible causes and recommended actions.
  • Page 115: Incorrect Or Non-Compatible Tools

    See the following table for the possible causes and recommended actions. Symptoms Device and/or block objects not identified (Unknown). Parameters are not visible or identified by name. Honeywell-defined parameters are not visible. Possible cause Things to check Recommended action Incorrect Standard...
  • Page 116: Troubleshooting Blocks

    Troubleshooting blocks Non-functioning blocks Device block objects may not be running (executing their function block schedules) or the blocks may be in Out of Service (OOS) mode due to block configuration error. For example, if the PID function block is in OOS mode, the block does not provide updated output values, although the PID block may be running.
  • Page 117: Troubleshooting The Diagnostics Transducer Block

    Troubleshooting the Diagnostics Transducer block Table 27: Diagnostics Transducer block Problem cause Things to check Recommended action Diagnostic Read Add AUTO mode to MODE_BLOCK.PERMITTED MODE_BLOCK.PERMITTED. Transducer block mode is in OOS and does not change to Read MODE_BLOCK. If necessary, Set AUTO mode.
  • Page 118: Troubleshooting The Lcd Transducer Block

    If display is available, remove and reconnect the local display, and check if display powers up. If display is not powering up contact Honeywell TAC. NOTE If a user goes to menus/sub menus in the display, the parameter change will fail. He must navigate out of the menus.
  • Page 119: Troubleshooting The Proportional Integral Derivative (Pid) Block

    Troubleshooting the Proportional Integral Derivative (PID) block Table 29: PID block Problem Cause Things to check Recommended action PID block mode is in Read Add AUTO, CAS, RCAS and ROUT OOS mode, and does MODE_BLOCK.PERMITTED. modes to MODE_BLOCK.PERMITTED. not change to AUTO, CAS, RCAS and Read MODE_BLOCK.
  • Page 120: Troubleshooting The Input Selector Block

    Problem Cause Things to check Recommended action Value of output does Check Cascade Initialization Assure that the output can move an not make sense actuator. Block alarms are not Read FEATURE_SEL Reports are not selected in reported FEATURE_SEL. If features do not include Reports then the host must poll for alarms.
  • Page 121 Problem Cause Things to check Recommended Action Read FEATURE_SEL. Block alarms are not Reports are not selected in reported. FEATURE_SEL. If features do not include Reports then the host must poll for alarms. Read LIM_NOTIFY. Set LIM_NOTIFY to a value higher than zero, but not higher than MAX_NOTIFY.
  • Page 122: Troubleshooting The Integrator Block

    Troubleshooting the Integrator block Table 31: Integrator block Problem Cause Things to check Recommended Action Integrator block mode Read Add AUTO mode to is in OOS and does MODE_BLOCK.PERMITTED. MODE_BLOCK.PERMITTED. not change to AUTO Read If necessary, set mode. MODE_BLOCK.ACTUAL of MODE_BLOCK.TARGET to Resource block.
  • Page 123: Troubleshooting The Arithmetic Block

    Troubleshooting the Arithmetic block Table 32: Arithmetic block Problem Cause Things to check Recommended Action Arithmetic block mode Read Add AUTO mode to MODE_BLOCK.PERMITTED MODE_BLOCK.PERMITTED. is in OOS and does not change to AUTO Read MODE_BLOCK. If necessary, set mode. ACTUAL of Resource block.
  • Page 124: Troubleshooting The Signal Characterizer Block

    Troubleshooting the Signal Characterizer block Table 33: Signal Characterizer block Problem cause Things to check Recommended action Signal characterizer Read Add AUTO mode to block mode is in OOS MODE_BLOCK.PERMITTED. MODE_BLOCK.PERMITTED. and does not change Read MODE_BLOCK. If necessary, Set to AUTO mode.
  • Page 125: Resolving The Block Configuration Errors

    Resolving the block configuration errors Table 34 lists the parameters of all the blocks that can cause the status bit of Block Configuration Error to be set in their respective BLOCK_ERR parameters. The following table provides the initial values and the valid range for the parameters. ATTENTION Block configuration errors can only be cleared if the function block is being executed (running).
  • Page 126: Device Diagnostics

    Device Diagnostics RMA803 FF Remote Indicator memory The Remote Indicator contains a number of areas of memory. An EEPROM provides a non-volatile memory area for static and non-volatile parameter values. The Remote Indicator also contains areas of RAM and ROM. Performing diagnostics in the background Block objects (Resource, Transducer and Function blocks), the communications stack and other device objects, each of them have an allotted area of memory for their corresponding database.
  • Page 127: Restoring The Remote Indicator To Default Settings

    Restoring the Remote Indicator to default settings Remote Indicator Diagnostics Remote Indicator faults are grouped into one of these two diagnostic categories and could cause the following results: Critical and Non-Critical Fault  Remote Indicator continues to read PVs from other Remote Indicators connected to the RMA803.
  • Page 128: Understanding Simulation Mode

    Understanding simulation mode About simulation mode jumper If the process is not running, a simulation mode is available in the Remote Indicator which aids in system debug. When simulation mode is enabled, user can simulate Field Diagnostic Alarm from Resource Blocks. Setting simulation jumper A hardware jumper on the Communication Module assembly is set to enable or disable the SIMULATE parameter.
  • Page 129: Enabling Simulation Mode

    Table 36: Setting the Simulation Jumper Set the Jumper to: Disable the SIMULATE parameter. “OFF” position on the Transducer board. (Set Remote Indicator for normal operation.) Enable the SIMULATE parameter. “ON” position on the Transducer board. (For testing or debugging purposes.) Enabling simulation mode The SIMULATE parameter is enabled by setting the hardware simulation jumper to the “ON”...
  • Page 130: Understanding Write Protection

    Understanding write protection The software write lock feature can be enabled, only if the hardware write lock feature is disabled. If the software write lock feature is enabled without disabling the hardware write lock feature, then the software write lock feature gets disabled automatically. If the hardware write lock feature is selected with the hardware jumper being enabled, the selection is rejected.
  • Page 131: Parts List

    9. Parts List 9.1 Overview Individually saleable parts for the various Remote IndicatorRemote Indicator models are listed in this section. Some parts are illustrated for identification. Parts are identified and listed in the corresponding tables as follows: • Individually saleable parts are indicated in each figure by key number callout. Table 40 is a summarized list of recommended spare parts.
  • Page 132: Figure 26: Electronic Housing, Display End

    Quantity Key No. Part Number Description Per Unit 50090524-501 Carbon Steel Pipe Bracket Mounting kit for all models 50090524-503 316 Stainless Steel Pipe Bracket Mounting kit for all models 50092363-501 Carbon Steel Wall Bracket Mounting kit for all models 50092363-503 316 Stainless Steel Wall Bracket Mounting kit for all models Figure 26: Electronic Housing, Display End Page 116...
  • Page 133: Table 42: Remote Indicator Major Assemblies

    Table 42: Remote Indicator Major Assemblies (Refer to Figure 27) Quantity Key No. Part Number Description Per Unit 50049832-501 End Cap, Display (Aluminum) 50049832-521 End Cap, Display (Stainless Steel) See Fig. 26 50075472-533 Terminal Assy FF/PB without Lightning protection 50075472-534 Terminal Assy FF/PB with Lightning protection 50049846-501 Advanced Display...
  • Page 134: Appendix A. Product Certifications

    Appendix A. Product Certifications A1. European Directive Information (CE Mark) RMA800 SmartLine Remote Indicator Series EU Declaration of conformity (Document #32302406), can be downloaded here: EU Declaration Page 118 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 135 Hazardous Locations Certifications AGENCY TYPE OF PROTECTION Electrical Ambient CODE Parameters Temperature Explosion proof: Class I, Division 1, Groups A, B, C, D; T6..T4 Dust Ignition Proof: T6: -50ºC to +65ºC Note 1 Class II, III, Division 1, Groups E, F, G; T4 T4, T5: -50 ºC to 85ºC Class 1, Zone 1, AEx d IIC T4 Gb Class 2, Zone 21, AEx tb IIIC T 95...
  • Page 136 Flame-proof: II 2 G Ex d IIC T4 Gb Note 1 C to 70 º º II 2 D Ex tb IIIC T 95 C Db Intrinsically Safe: II 2 G Ex ia IIC T4 Ga C to 70 Note 2 FISCO Field Device Ex ia IIC T4 ATEX...
  • Page 137 Marking ATEX Directive a. General The following information is provided as part of the labeling of the Remote Indicator: Name and Address of the manufacturer The serial number of the Remote Indicator is located on the Meter Body data-plate. The first two digits of the serial number identify the year (02) and the second two digits identify the week of the year (23);...
  • Page 138 Conditions of Use “for Ex Equipment”, Hazardous Location Equipment or “Schedule of Limitations” a. Consult the manufacturer for dimensional information on the flameproof joints for repair. b. Painted surface of the RMA 800 series may store electrostatic charge and become a source of ignition in applications with a low relative humidity less than approximately30% relative humidity where the painted surface is relatively free of surface contamination such as dirt, dust or oil.
  • Page 139 Control Drawing: 50089981 Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 123...
  • Page 140 Page 124 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4...
  • Page 141 Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 125...
  • Page 142: 10. Index

    10. INDEX Advanced Display Menus ........... 18 LCD Transducer block ..........48 Diagnostics Menu ..........18 Licensing for Function Blocks ........96 Display Setup Menus ..........19 Information Menus ..........22 Arithmetic block ............78 Maintenance ............. 92 Preventive Maintenance Practices and Schedules 92 Replacing the Communication Module ....
  • Page 143 Verifying communication ..........8 Wiring a Remote Indicator ........13 Verifying the installation ..........7 Write protection ............. 114 Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 127...
  • Page 144 Phone: +(822) 799 6114 Fax: +(822) 792 9015 For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd...

This manual is also suitable for:

Smartline rma803Smartline rma801Smartline rma3000-eu

Table of Contents