6) Once the blower assembly is clear of the
blower panel, turn the blower assembly,
90 degrees, counter clockwise.
Caution: At any time, DO NOT rest
blower assembly on bottom access
panel, as damage may occur to the unit
7) Pull the blower assembly out of the unit.
Discharge Modification
The AAON WSHP discharge direction can
be selected in ECat and is also designed so
that the discharge direction can be field
modified if needed.
Note: DO NOT perform this action while
unit is hanging. It MUST be done on a solid
working surface. Otherwise, serious unit
damage may occur.
5
For WH-006
�
16
1) Use a
" socket to remove the four
(4) screws holding the blower panel
in place.
2) Firmly grip the blower panel and lift it
approximately ½" or until the bottom of the
blower panel clears the WSHP unit.
3) Pull the bottom of the blower panel out
about 10 degrees then down and away from
the unit.
4) Remove the side access panel.
5) Swap and install the two panels keeping
note of which side is up.
Note: Installing blower panel upside down
will result in damage to the unit.
19