SCREENS
Setpoints
Dehumidification Setpoints
•
Dehumidification Enable:
this value, Unit will go into Dehumidification Mode.
Default: 50%; Range: 40-60%
•
Dehumidification Lockout:
this value, the Dehumidification Mode will be locked
out. Default: 55°F; Range: 35-75°F
•
Supply Air Reheat Setpoint:
mode, the controller will try to maintain this setpoint.
Default: 70°F; Range: 55-120°F
Dehumidification Setpoints
50%
Dehum Enable
55ºF
Dehum Lockout
Setpoints
Setpoints
Figure 4-8: Setpoints - Dehumidification
Economizer Setpoints
•
Economizer Cooling Enable:
Temperature is below this value, the Economizer can be
used for "Free" Cooling. Default: 45°F; Range: 45-60°F
•
Economizer Heating Enable:
Temperature is Above this value, the Economizer can be
used for "Free" Heating. Default: 85°F; Range: 75-90°F
•
Water Econ Cooling Failure Time and
Water Econ Heating Failure Time
If the Waterside Economizer is enabled for cooling
or heating, the failure time is the time period before
it switches to Compressor Cool or Heat. Setting the
value to 255 will disable the timer so the Waterside
Economizer will run indefinitely in that mode and never
timeout. Default: 10 minutes; Range: 10-255 minutes
4-4
If Space RH is above
If the Space Temp is below
In the Modulating Reheat
70ºF
Supply Air Reheat
MAIN MENU
MAIN MENU
If the Entering Water
If the Entering Water
Pioneer Gold 3.00 Controller Technical Guide
Economizer Setpoints
45ºF
Econ Cool Enable
Setpoints
Setpoints
Figure 4-9: Setpoints - Economizer
Compressor Setpoints
•
Compressor must run for this amount
Minimum On Time:
of time before it can turn off. Default: 180 seconds;
Range: 120-255 seconds
•
Minimum Off Time:
this amount of time before it can turn on.
Default: 120 seconds; Range: 60-255 seconds
•
Interstage On Delay:
controller must wait for this amount of time before
turning on Stage 2. Default: 60 seconds;
Range: 30-255 seconds
•
Interstage Off Delay:
controller must wait for this amount of time before
turning off Stage 2. Default: 60 seconds;
Range: 30-255 seconds
Compressor Setpoints
120 s
Min Off Time
180 s
Min On time
Setpoints
Setpoints
Figure 4-10: Setpoints - Compressor
Econ Heat Enable
MAIN MENU
MAIN MENU
Compressor must remain for
If Stage 1 is energized, the
If Stage 2 is energized, the
Interstage On Delay
Interstage Off Delay
MAIN MENU
MAIN MENU
85ºF
60 s
60 s