Explanation of symbols and safety instructions If you are in any doubt contact the Robert Bosch Explanation of symbols and safety instructions technical hotline on: 1300 30 70 37 AU or 0800 54 33 52 NZ Explanation of symbols Warnings...
The designation of the wall mounted condensing boiler comprises the following: ▶ In the case of open flue operation:Ensure that the • Bosch: manufacturer installation location meets the ventilation • Condens 5000W ZBR-3: product name requirements. • 70 or 100: type name ▶ Only use original spares. Data plate...
If the wall mounted gas condensing boiler can be converted for another gas type, corresponding information will be provided in the gas data ( chapter 2.14, page 10). Condens 5000W – 6720813952 (2019/02)
Condensate pipe, Ø external diameter 24 mm Connection set for gas connection, R 1" female thread Connection set for flow, G 1½ '' male thread with flat gasket Heating flow, G 1½ '' screw fitting with female thread Condens 5000W – 6720813952 (2019/02)
[29] Pump connection set, external pump 230 V AC, max. 250 W [12] Flow temperature sensor [13] Safety temperature sensor [14] Flame sense electrode [15] Earth [16] Turquoise - no function [17] Grey - no function [18] Blue - outside temperature sensor Condens 5000W – 6720813952 (2019/02)
Heating return pipe, male thread with flat gasket inch G1½ Gas line inch Electrical power consumption WILO Stratos PARA 25/1-8, min./max. 8 / 140 Table 2 Specifications The information in brackets corresponds to the information on the data plate. Condens 5000W – 6720813952 (2019/02)
Type B2, B3 and B5 boilers with a rated heat valve input no greater than 1000 kW Resistance of wall mounted gas condensing boiler Table 5 Regulations, standards and guidelines [l/h] Flow rate [mbar] Residual head Condens 5000W – 6720813952 (2019/02)
V ▶ Flush and clean the heating system if necessary. ▶ Only use untreated mains water. ▶ Do not use any chemical additives (e.g. inhibitors or pH-increasing or reducing agents) other than those approved by Bosch Thermotechnik. Product Concentration...
• Using the connection set (accessory) ( chapter 5.8) using an approved sealant [1]. • Without using the connection set ( chapter 5.9). ▶ Mount the gas isolator G 1" in the gas line [2]. Condens 5000W – 6720813952 (2019/02)
Damage to appliance due to excessive operating pressure. ▶ Mount a pressure relief valve between the wall mounted gas 0010009994-001 condensing boiler and shut-off valve. Fig. 16 Connection of the heating water pipework Flow pipe Pressure Relief Valve Condens 5000W – 6720813952 (2019/02)
5.11 Installing the siphon ▶ Removing the transport protection. 0010009999-001 0010009997-001 Fig. 20 Mounting the flexible hose Fig. 18 Remove the transport protection T piece ▶ Fill the condensate trap with water. Flexible hose tube Condens 5000W – 6720813952 (2019/02)
Western Australia refer to SECWA rules and regulations. ▶ All measurements are the minimum clearances required. ▶ Terminals must be positioned to avoid combustion products entering the building. The fixing method must be sufficient to hold the weight of the boiler. Condens 5000W – 6720813952 (2019/02)
NOTICE: 0010010003-001 Short circuit. Fig. 25 Principle of weather-compensated control ▶ Only use original cables if they must be replaced. Wall mounted gas condensing boiler Room temperature-dependent controller Thermostatically controlled radiator valve Condens 5000W – 6720813952 (2019/02)
0010010005-001 Fig. 27 Removing the cover ▶ Connect the components to the relevant plug. 0010010006-001 Fig. 28 Terminal strips 24 V AC terminal strip 230 V AC terminal strip 0010010008-001 Fig. 30 Tightening the screw Condens 5000W – 6720813952 (2019/02)
“d3” appears in the display of the wall mounted gas condensing boiler. All standard, potential-free switching contacts can be connected for use as external switching contact. ▶ Remove the jumper of the red plug [1]. Condens 5000W – 6720813952 (2019/02)
(240 V AC) (fuse, circuit breaker) and secure against “Info” unintentional reconnection. The status of the wall mounted gas condensing boiler can be read out via key. Display Condens 5000W – 6720813952 (2019/02)
“OFF” appears in the display when heating Setup menu mode is switched off. The text “menu” is displayed for 1 second. No information about DHW mode is shown here. Heating mode is switched on. Setting: On, Off. Condens 5000W – 6720813952 (2019/02)
Fig. 41 Display - Lock ▶ Hold down to switch off the flue gas inspector mode. Disable ▶ Press the keys again simultaneously for 5 seconds to remove the key block; the word “Lock” disappears. Condens 5000W – 6720813952 (2019/02)
The output of the wall mounted gas condensing boiler can be adapted to 0010010025-001 the heat energy demand via the setup menu. Proceed as follows: Fig. 42 Open the burner pressure nipple at the type 70 Condens 5000W – 6720813952 (2019/02)
▶ Check that the measured value is not less than the permissible value ▶ Connect pressure gauge. ( tab. 3, page 3). ▶ Set pressure gauge to “0”. Hold the pressure gauge at the same height when the measurement is in progress. Condens 5000W – 6720813952 (2019/02)
▶ Measure the CO content. ▶ Push on the plug of the ionisation cable. ▶ Establish and eliminate the cause of a possible high CO content. ▶ Bring wall mounted gas condensing boiler into operation. Condens 5000W – 6720813952 (2019/02)
▶ Take the wall mounted gas condensing boiler out of operation via the ON/OFF switch. ▶ Close gas isolation valve. ▶ Drain the entire heating system. ▶ If installed, drain the entire potable water system. Condens 5000W – 6720813952 (2019/02)
▶ Use only original spare parts. ▶ When carrying out the work, check all removed gaskets for damage, deformation or ageing and replace if necessary. 0010010041-001 Fig. 53 Detaching the air intake pipe (Detail: Type 70) Condens 5000W – 6720813952 (2019/02)
Fig. 58 Cleaning the heat exchanger 11.5 Checking the ignition system NOTICE: Damage to the hot surface igniter. The glow ignitor unit is made of breakable material. ▶ Handle with care. 0010010046-001 Fig. 56 Removing the burner gasket Condens 5000W – 6720813952 (2019/02)
▶ Undo the nozzle pressure test nipple [1] by turning it through 2 revolutions. 0010010057-001 6 720 807 034-67.1DDC Fig. 64 Opening the snap fasteners of the condensation catch pan Fig. 66 Opening the burner pressure test nipple at Type 70 Condens 5000W – 6720813952 (2019/02)
▶ Close the inspection aperture of the flue gas pressure-relief valve. 0010010059-001 Fig. 68 Setting the gas/air ratio at the Type 70 Differential pressure incorrect Differential pressure correct 0010010061-001 Fig. 70 Checking the flue gas pressure-relief valve Inspection aperture Flue gas pressure-relief valve Condens 5000W – 6720813952 (2019/02)
▶ Consult the instruction manual for the control valve. 13. Final inspection check, take measurements and document measurement and test results. Confirm correct inspection Company stamp/signature/date Table 13 Inspection and maintenance reports Condens 5000W – 6720813952 (2019/02)
Component test phase. 2 7 0 The wall mounted gas condensing boiler ramps up. 2 8 3 The wall mounted gas condensing boiler is preparing for a burner start. The fan and pump are activated. Condens 5000W – 6720813952 (2019/02)
Page 33
▶ Check the function of the wall mounted gas condensing boiler by replacing the boiler return temperature sensor. 2 3 2 The external switching contact has opened. ▶ Check the jumper at the connection of the external switching contact. ▶ Check external switching contact. Condens 5000W – 6720813952 (2019/02)
Page 34
▶ Check whether it is possible to achieve a sufficient flow via the heating system. ▶ Check cabling and function of pump and flow temperature sensor. Replace the component if necessary. Condens 5000W – 6720813952 (2019/02)
Page 35
▶ Check plug and wiring of the burner control unit. ▶ Check the operating characteristics of the wall mounted gas condensing boiler by replacing the burner control unit. Condens 5000W – 6720813952 (2019/02)
Page 36
DHW ▶ Refill the heating system. mode. H r E The wall mounted gas condensing boiler is reset. The wall mounted gas condensing boiler is reset. Table 14 Operating and fault codes Condens 5000W – 6720813952 (2019/02)
Page 40
Robert Bosch (Australia) Pty Ltd Thermotechnology Division 1555 Centre Road Clayton Victoria 3168 Australia Phone: 1300 30 70 37 Fax: 1300 30 70 38 www.bosch-climate.com.au New Zealand Phone: 0800 54 33 52 Fax: 0800 54 33 55 www.bosch-climate.co.nz...