This guide tells you briefly how to install the drive module into a 800 mm wide Rittal VX25 cabinet. For installation examples in different cabinets and more detailed instructions, engineering guide lines, technical data and complete safety instructions, see the hardware manual (www.abb.com/drives, Select Document Library and search for document number 3AXD50000420025 [English]). Obey the safety instructions See figures on page 9.
4 EN – Quick installation guide 5. Measure that the installation is de-energized. • Use a multimeter with an impedance of at least 1 Mohm. • Make sure that the voltage between the drive module input power terminals (L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V. •...
Page 5
EN – Quick installation guide 5 3AUA0000088632 • Unfasten the insertion ramp and attach the LCL filter module to bottom plate. • Attach the drive module pedestal guide plate to the cabinet bottom plate. • Attach the telescopic insertion ramp to the pedestal guide plate. •...
Page 6
6 EN – Quick installation guide Step Task (motor cables) Screw in and tighten the insulators to the drive module by hand. Install the T3/W2 connection terminal to the insulators. WARNING! Do not use longer screws or bigger tightening torque than given in the installation drawing.
Page 7
EN – Quick installation guide 7 Default I/O connections The default I/O connections of the Water default configuration are shown below. Wire sizes: 0.14…2.5 mm (26...16 AWG): All terminals. Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft). Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference : 0…10 V...
Page 9
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 9 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet (PE) PE (PE) Drive type Air flow Losses Type DIN 43653 ACQ580-34- = 400 V 246A-4 2100 5280 170M5408 293A-4...
Page 10
10 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet Rittal 8806.000 non-ABB part (see dimension drawings) Rittal 8617.140 80.5 (3.17) 280.5 (11.04) Tapping screw M6×12 Torx T30 8 N·m 360 °...
Page 11
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 11 Tapping screw M6×12 Torx T30 (Hex) 8 N·m Combi screw M8×30 Hex 20 N·m...
Page 12
12 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet +B051 Combi screw M4×8 Torx T20 2 N·m +B051 +B051 Combi screw M4×8 Torx T20 2 N·m Combi screw M4×8 Torx T20 2 N·m +B051...
Page 13
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 13 M6 Serpress 8 N·m M6 Serpress 8 N ·m Screw M10x30 and washer Combi screw M8 Combi screw M8 24 N·m 24 N·m...
Page 14
14 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet M10×30 Combi screw M4×8 Torx T20 2 N·m Combi screw M12×25 70 N·m Combi screw M4×8 Torx T20 2 N·m...
Page 15
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 15 T3/W2 T3/W2 T2/V2 T2/V2 T3/W2 T1/U2 T2/V2 T1/U2 T1/U2 Combi screw M12×25 Hex (Delta) 70 N·m T3/W2 T3/W2 T2/V2 T2/V2 T1/U2 T1/U2 8 N·m Combi screw M6×12 Torx...
Page 16
16 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet T3/W2 T3/W2 T3/W2 T2/V2 T2/V2 T2/V2 T1/U2 T1/U2 T1/U2 T3/W2 T3/W2 T2/V2 T2/V2 T1/U2 T1/U2...
Page 17
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 17 +B051 Combi screw M4×10 Torx T20 2 N·m Combi screw M6×20 Torx T25 2 N·m +B051 +B051 Combi screw M6×20 Torx T25 2 N·m +B051...
Page 18
18 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet UDC+ UDC+ UDC+ UDC- UDC- UDC- L1/U1 L1/U1 L3/W1 L2/V1 L1/U1 L3/W1 L2/V1 L2/V1 Hex screw M12×35 L3/W1 full thread 70 N·m +B051 Hex nut M12 70 N·m...
Page 19
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 19 +B051 +B051 UDC+ UDC- L3/W1 L2/V1 L1/U1 Combi screw M4×10 Torx T20 2 N·m +B051 Combi screw M4×10 Torx T20 2 N·m Combi screw M6×20 Torx T25 2 N·m...
Page 20
20 Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet Tapping screw M6×12 Torx T30 (Hex) 8 N·m Right air baffle, non-ABB part Rear air baffle, non-ABB part (see dimension drawings) (see dimension drawings) Rittal 8617.720...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
Page 22
Contact us www.abb.com/drives www.abb.com/drivespartners 3AXD50000424634 Rev C (MUL) 2019-09-12...