Siemens SITRANS LR260 Operating Instructions Manual

Siemens SITRANS LR260 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

Quick Links

SITRANS L
Radar transmitters
SITRANS LR260 with mA/HART
Operating Instructions
7ML5427
11/2019
A5E32337683-AD
Introduction
Safety notes
Description
Installing/mounting
Connecting
Commissioning
Operating
Parameter reference
Service and maintenance
Diagnosing and
troubleshooting
Technical data
Dimension drawings
Application examples
Appendix A: Technical
reference
Appendix B: HART
Communications
Product documentation and
support
List of abbreviations
LCD menu structure
1
2
3
4
5
6
7
8
9
10
11
12
13
A
B
C
D
14

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LR260

  • Page 1 Introduction Safety notes Description SITRANS L Installing/mounting Connecting Radar transmitters SITRANS LR260 with mA/HART Commissioning Operating Parameter reference Operating Instructions Service and maintenance Diagnosing and troubleshooting Technical data Dimension drawings Application examples Appendix A: Technical reference Appendix B: HART Communications...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Radio Equipment Directive (RED) compliance (Europe) ............17 Laws and directives........................17 2.2.1 Conformity with European directives..................18 Requirements for special applications ...................18 Use in hazardous areas ......................19 Description..............................21 Overview SITRANS LR260 ....................21 Features ..........................21 Applications..........................21 System configuration......................22 HART communication ......................22 Installing/mounting............................23 Basic safety notes ........................23 4.1.1...
  • Page 4 High Calibration Point (HIGH CALIB. PT.) (1.6.)..............54 6.2.3.9 Apply (1.7.)..........................54 6.2.3.10 Requesting an Echo Profile....................54 6.2.3.11 Device address ........................55 6.2.3.12 Auto false echo suppression ....................55 Application examples ......................56 6.3.1 Application examples ......................56 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 5 Low Calibration Point (LOW CALIB. PT.) (1.5.) ..............76 8.4.6 High Calibration Point (HIGH CALIB. PT.) (1.6.)..............77 8.4.7 Apply (1.7.)..........................77 Setup (2.) ..........................77 8.5.1 Device (2.1.)...........................77 8.5.2 Firmware Revision (FIRMWARE REV.) (2.1.1.)..............77 8.5.3 Loader Revision (LOADER REV.) (2.1.2.) ................78 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 6 20 mA Setpoint (2.3.1.4.) .......................93 8.5.43 Minimum mA limit (MIN. mA LIMIT) (2.3.1.5.)................93 8.5.44 Maximum mA limit (MAX. mA LIMIT) (2.3.1.6.)..............93 8.5.45 4 mA Output Trim (2.3.1.7.) ....................94 8.5.46 20 mA Output Trim (2.3.1.8.) ....................94 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 7 Acknowledge Status (ACK. STATUS) (4.16.8.) ..............107 8.7.17 Acknowledge (ACK.) (4.16.9.)....................107 8.7.18 Calibration Interval (CALIB. INTERVAL) (4.17.) ..............108 8.7.19 Time Last Calibrated (TIME LAST CAL.) (4.17.1.)...............108 8.7.20 Remaining Lifetime (REMAIN LIFETIME) (4.17.2.) .............108 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 8 Device status icons ......................120 10.3 General fault codes ......................121 10.4 Operation troubleshooting....................123 Technical data ............................125 11.1 Power ...........................125 11.2 Performance.........................125 11.3 Interface ..........................126 11.4 Mechanical ...........................127 11.5 Environmental ........................127 11.6 Process ..........................128 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 9 Fail-safe Timer ........................158 A.9.3 Fail-safe Material Level ......................158 A.9.4 Fail-safe Level........................158 A.10 Process Pressure/Temperature derating curves..............159 A.11 Versions with 3 bar pressure rating..................160 A.12 Loop power ..........................160 A.12.1 Typical Connection Drawing ....................160 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 10 Table of contents A.12.2 Allowable operating area of SITRANS LR260 ..............162 A.12.3 Startup Behavior ........................162 Appendix B: HART Communications......................165 HART communications ......................165 SIMATIC PDM........................165 HART Electronic Device Description (EDD).................165 HART communication protocol ....................165 HART Communicator 375 Menu Structure ................166 Supported HART Commands ....................168 Universal and Common Practice Commands ..............168...
  • Page 11: Introduction

    Introduction Note This manual applies to the SITRANS LR260 mA/HART version only. HART is a registered ® trademark of the HART Communication Foundation. Purpose of this documentation These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning.
  • Page 12: Industrial Use Note

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 13: Transportation And Storage

    The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
  • Page 14 Introduction 1.8 Notes on warranty SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 15: Safety Notes

    Dispose of in an environmentally safe manner, and according to local regulations. 2.1.2 Laws and directives Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 16: Fcc Conformity

    Industry Canada The SITRANS LR260 complies with Industry Canada standard RSS211 (March 2015). 1. The installation of the SITRANS LR260 shall be done by trained installers, in strict compliance with the manufacturer's instructions. 2. The use of this device is on a “no-interference, no-protection” basis. That is, the user shall accept operations of high-powered radar in the same frequency band which may interfere with or damage this device.
  • Page 17: Radio Equipment Directive (Red) Compliance (Europe)

    2.1.5 Radio Equipment Directive (RED) compliance (Europe) Hereby, Siemens declares that the SITRANS LR260 is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. The LR260 complies with EN 302 372 for use in closed storage vessels, when installed according to the installation requirements of EN 302 372, and may be used in all EU countries.
  • Page 18: Conformity With European Directives

    If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note Operation under special ambient conditions...
  • Page 19: Use In Hazardous Areas

    ● Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit. ● Observe the specifications for the electrical data on the certificate and/or in Technical data (Page 125). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 20 Safety notes 2.4 Use in hazardous areas SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 21: Description

    Signals are processed using Process Intelligence which has been field-proven in over 1,000,000 applications worldwide (ultrasonic and radar). Applications Inventory level measurement or process control SITRANS LR260 is designed to measure levels of solids and liquids in a variety of applications: ● Cement powder ● Plastic pellets ● Grain ●...
  • Page 22: System Configuration

    Loop resistance (total of cable resistance plus 250 Ohm [resistor]) must be less than 550 Ohm for the device to function properly. HART communication This device supports HART communication protocol. For more information, see HART Communication (https://fieldcommgroup.org/). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 23: Installing/Mounting

    Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 24: External Stresses And Loads

    ● Make sure that the maximum permissible ambient temperature is not exceeded. Refer to the information in Technical data (Page 125). 4.1.2.1 Strong vibrations NOTICE Strong vibrations Damage to device. ● In installations with strong vibrations, mount the transmitter in a low vibration environment. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 25: Proper Mounting

    ● Secure the remaining connections so that no damage can result if the process is started unintentionally. Note Do not disassemble and reassemble the horn from the polymeric flange version more than five times. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 26: Proper Mounting

    ● Avoid central locations on tall, narrow vessels. ● Align the antenna so that the radar cone is perpendicular to the surface of the monitored material, if possible. See Easy Aimer (Page 28) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 27: Orientation In A Vessel With Obstructions

    Auto false echo suppression (Page 55) 4.3.3 Orientation in a vessel with obstructions Note For best results on a vessel with obstructions, orient the front or back of the device toward the obstructions. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 28: Stainless Steel Easy Aimer

    Polarization axis ② Polarization reference point ③ Display 4.3.4 Stainless steel Easy Aimer Note When the Easy Aimer ball is loosened, the device is free to tilt to a maximum of 30°. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 29 1. Holding the electronics enclosure firmly, loosen the Easy Aimer ball locking bolts and gently reposition the enclosure. 2. Direct SITRANS LR260 so the horn antenna is pointed at an angle perpendicular to the material surface, if possible. (As a guide, aim the beam at a point approximately 2/3 of the way across the tank diameter.)
  • Page 30 Installing/mounting 4.3 Proper mounting SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 31: Aluminum Aimer Flanges

    The system provides an 1/8" inlet (female thread) on the flange where cooling air or cleaning fluid passes through the flange and exits the inside of the horn to clean it. The customer will supply the purging medium by a manual or automatic valve system. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 32 • Some dust particles are highly abrasive and can be drawn into the inside of the horn during purge cleaning, damaging the internal PTFE emitter of the antenna. A replacement kit is available from your local Siemens representative. • It is the customer’s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained, considering the hole that passes through the process connection and SITRANS LR260 antenna system.
  • Page 33: Universal Slotted Flange

    See Dimension drawings (Page 131) for more details. 4.3.8 PTFE dust cap for stainless horn versions Note The dust cap must be removed before using the Air Purge feature. See Air Purging System (Page 31). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 34 4. Use a screwdriver or nut driver to tighten the clamp screw until the clamp provides an air- tight seal. Note It is critical to ensure no moisture can be trapped inside. ① Groove ② Plastic emitter ③ Ridge ④ Dust cap ⑤ Clamp screw SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 35: Aluminum Horn With Polypropylene Lens (Dust Cover) Antenna Version

    6. Install one of the two o-rings provide using the kit on the groove at the top of the lens ⑤ ⑥ 7. Seat the second o-ring (provided in the kit) in the groove inside the aimer adaptor SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 36 10.Use an appropriate screwdriver or nut driver to tighten the clamp screw until the clamp is an air-tight seal. Note It is critical to ensure no moisture can be trapped inside. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 37: Connecting

    ● Close unused cable inlets for the electrical connections. ● When replacing cable glands, only use cable glands of the same type. ● After installation, check that the cables are seated firmly. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 38: Connecting Device In Energized State In Hazardous Areas

    Connecting 5.2 Connecting SITRANS LR260 5.1.2 Connecting device in energized state in hazardous areas WARNING Connecting device in energized state Risk of explosion in hazardous areas. ● Connect devices in hazardous areas only in a de-energized state. Exceptions: ● Devices having the type of protection "Intrinsic safety Ex i" may also be connected in energized state in hazardous areas.
  • Page 39 Connecting 5.2 Connecting SITRANS LR260 WARNING Loss of protection Loss of approvals can result from improper connection. ● Check the nameplate on your device, to verify the approval rating. ● Use appropriate cable entry seals to maintain IP or NEMA rating.
  • Page 40: Hazardous Area Installation

    ● Connect the device in accordance with the specified power supply and signal circuits. The relevant specifications can be found in the certificates, in Technical data (Page 125) or on the nameplate. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 41: Instructions Specific To Hazardous Area Installation

    07.0090X. Device nameplate (FM/CSA) FM/CSA Intrinsically Safe connection drawing number A5E03745229 can be downloaded from the product page of our website at: www.siemens.com/LR260. Go to Technical info > Images, graphics and drawings For power demands see Startup Behavior (Page 162).
  • Page 42: Special Conditions For Safe Use (Denoted By X After The Certificate Number)

    ● Aluminium, magnesium, titanium or zirconium may be used at the accessible surface of the equipment. In the event of rare incidents, ignition sources due to impact and friction sparks could occur. This shall be considered when the Sitrans LR260 is being installed in locations that specifically require Equipment Protection Level Ga or Da.
  • Page 43: Reference European Atex Directive 2014/34/Eu)

    8. The equipment contains no user-replaceable parts and is not intended to be repaired by the user. Repair of the equipment is to be carried out by the manufacturer, or their approved agents, in accordance with the applicable code of practice. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 44 – Aggressive substances: for example, acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials. – Suitable precautions: for example, establishing from the material’s data sheet that it is resistant to specific chemicals. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 45: Commissioning

    Loss of explosion protection WARNING Loss of explosion protection Risk of explosion in hazardous areas if the device is open or not properly closed. ● Close the device as described in Installing/mounting (Page 23). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 46: Local Commissioning

    6.2.1.1 Activating the radar device Power up the device. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed. The first time the device is configured, you will be prompted to select a language (English, German, French, or Spanish).
  • Page 47: Remote Quick Start Options

    6.2.2.3 Quick Start via local operation SITRANS LR260 carries out its level measurement tasks according to settings made via parameters. The settings can be modified locally via the Local User Interface (LUI) which consists of an LCD display and a handheld programmer.
  • Page 48: The Lcd Display

    In response to a key press request. For details, see Handheld Programmer (Page 50) for key func‐ tions in Measurement mode. Fault present ① Device status indicator, see Device status icons (Page 120) ② Text area displays status messages SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 49 ● A deeper band indicates fewer items. Parameter view Edit view OPERATION 2.2.1.5 OPERATION 2.2.1.5 NO SERVICE DISTANCE LEVEL PREVIOUS SPACE BACK EDIT DISTANCE NEXT ① Parameter name ② Parameter number ③ Parameter value/selection SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 50: Handheld Programmer (Part No. 7Ml1930-1Bk)

    Then top level menu will be displayed. RIGHT arrow opens PROGRAM mode Opens the top level menu. UP or DOWN arrow toggles between linear LCD displays measured value in either linear units and percent units or percent. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 51: Programming

    ● The Quick Start Wizard settings are inter-related and changes apply only after you click on Yes in Apply? at the end of the Quick Start steps. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 52: Application Type (1.1.)

    Point (process empty level). Options SPACE Distance to material surface ref‐ erenced from High Calibration Point (process full level). DISTANCE Distance to material surface ref‐ erenced from Sensor Reference Point. Default: DISTANCE SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 53: Low Calibration Point (Low Calib. Pt.) (1.5.)

    Low Calibration Point (LOW CALIB. PT.) (1.5.) Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operation (Page 52) types for an illustration.) Range: 0.0000 to 30.000 m Values Default: horn type dependent SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 54: High Calibration Point (High Calib. Pt.) (1.6.)

    In order to save the Quick Start settings, it is necessary to select Yes and apply changes. YES, NO, DONE Options Display shows DONE when Quick Start is suc‐ cessfully completed. ● Press Mode to return to Measurement mode. 6.2.3.10 Requesting an Echo Profile SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 55: Device Address

    6.2.3.12 Auto false echo suppression If SITRANS LR260 displays a false high level, or the reading is fluctuating between the correct level and a false high level, you can use the Auto False Echo Suppression parameters to prevent false echo detection. See TVT (Auto False Echo Suppression) setup (TVT SETUP) (Page 86) for instructions.
  • Page 56: Application Examples

    The application is a steel silo containing flour that takes an average of 3 hours to fill and 3 weeks to empty. Using the Easy Aimer, orient the SITRANS LR260 so that the emission cone is approximately perpendicular to the material surface.
  • Page 57 OPERATION (Page 75) LEVEL Material level referenced from Low Calibration Point. LOW CALIBRATION POINT Process empty level. (Page 76) HIGH CALIBRATION POINT Process full level. (Page 77) APPLY? (Page 77) Save new settings. (CHANGES) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 58 Commissioning 6.3 Application examples SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 59: Operating

    Check the support page of our website to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF): SIMATIC PDM Version (https://support.automation.siemens.com) Browse to Product Support > Automation Technology > Process control systems > SIMATIC PCS 7 > System components > Plant Device Management >...
  • Page 60: Initial Setup

    7.1 Operating via SIMATIC PDM 7.1.1.3 Initial setup Initial setup It is required to obtain the SITRANS LR260 EDD from the product support website and install into PDM using the device integration manager utility. 7.1.1.4 Updating the Electronic Device Description (EDD) You can locate the EDD in Device Catalog, under Sensors/Level/Echo/SiemensMilltronics/ SITRANS LR260.
  • Page 61: Quick Start Note

    ● For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM (Page 87). 7.1.2.3 Quick start menu and instruction Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 4. ① Quick start SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 62: Quick Start Steps With Images

    3. Click on NEXT to accept the default values. (Description, Message, and Installation Date fields can be left blank.) Step 2 – Application Select the application type (level or volume) and the material, then click on NEXT. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 63 Check parameter settings, and click on BACK to return and revise values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and transfer them to the device. The message Quick Start was successful will appear. Click on OK. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 64: Changing Parameter Settings Using Simatic Pdm

    3. Open the Device menu, click on Download to device, then use File - Save to save settings offline. The status fields are cleared. 7.1.4 SIMATIC PDM pull-down menu image You have access to a number of functions via pull-down menus from the menu bar. under Device or View. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 65: Parameters Accessed Via Pull-Down Menus

    Click on Device or View to open the associated pull-down menus. ① pull-down menus 7.1.5.2 Display To compare outputs in real time, open the menu View – Display. 7.1.5.3 Echo profile Open the menu View - Echo Profile. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 66: Trend

    There should be a minimum distance of two meters from the radar instrument to the material. ● Set Auto False Echo Suppression and Auto Suppression Range during installation, if possible. ● Before adjusting these parameters, rotate the instrument for best signal (minimum false- echo amplitude). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 67: Tvt Shaper

    Operating 7.1 Operating via SIMATIC PDM SITRANS LR260 first learns the echo profile. Then the learned profile, or part of it, is used to screen out false echoes. (See Auto False Echo Suppression (Page 87)for a more detailed explanation.) 1. Determine Auto Suppression Range (the distance within which the learned TVT will replace the default TVT).
  • Page 68: Device Status

    Reports the number of hours the device has been operating, and the number of times it has been powered up. Open the menu View – Wear to view: ● Powered Days ● Power-on Resets Note Powered days are whole days only. Fractional days are truncated. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 69: Maintenance

    2. Modify desired values, and click on Write. 3. Click on Read, to see the effects of your modification. 4. If desired, activate alerts. 5. Click on Service Performed to reset the schedule. 7.1.5.10 Device Reset Factory Defaults SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 70: Configuration Flag Reset

    4. Select AnalogOut window displays the new setting: click OK. 7.1.5.14 Simulate AO (Analog Output) Allows you to input a simulated value in order to test the functioning of the mA connections during commissioning or maintenance of the device. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 71: Hart Communication

    We recommend you do not change the default value (5). 7.1.5.16 How to set the device address The default address for the device is 0. To reset the address via the handheld programmer see Device Address. (Page 111) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 72 Operating 7.1 Operating via SIMATIC PDM SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 73: Parameter Reference

    Trend (Page 66) Upload to PC/PG Echo Profile (Page 65) Update Diagnostic Status Show Echo Profile (Page 95) Device Status (Page 69) Clear Faults Wear (Page 68) Peak Values Set Address Toolbar Status bar SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 74: Quick Start Wizard

    Options FAST 10.0m/minute Default: FAST Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy; faster settings allow for more level fluctuation. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 75: Units (1.3.)

    Point (process empty level). Options SPACE Distance to material surface ref‐ erenced from High Calibration Point (process full level). DISTANCE Distance to material surface ref‐ erenced from Sensor Reference Point. Default: DISTANCE SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 76: Low Calibration Point (Low Calib. Pt.) (1.5.)

    Low Calibration Point (LOW CALIB. PT.) (1.5.) Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operation (Page 75) types for an illustration.) Range: 0.0000 to 30.000 m Values Default: horn type dependent SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 77: High Calibration Point (High Calib. Pt.) (1.6.)

    ● Values shown in the following tables can be entered via the handheld programmer 8.5.1 Device (2.1.) 8.5.2 Firmware Revision (FIRMWARE REV.) (2.1.1.) Corresponds to the software or firmware that is embedded in the SITRANS LR260. Read only. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 78: Loader Revision (Loader Rev.) (2.1.2.)

    Parameter reference 8.5 Setup (2.) 8.5.3 Loader Revision (LOADER REV.) (2.1.2.) Corresponds to the software used to update the SITRANS LR260. Read only. 8.5.4 Hardware Revision (HARDWARE REV.) (2.1.3.) Corresponds to the electronics hardware of the SITRANS LR260. Read only.
  • Page 79: Operation (2.2.1.5.)

    Parameter reference 8.5 Setup (2.) 8.5.9 Operation (2.2.1.5.) SITRANS LR260 stops updating measurements and SERVICE associated loop current. Last valid measurement value is displayed. LEVEL Distance to material surface referenced from Low Cali‐ bration Point (process empty level). Options SPACE Distance to material surface referenced from High Cali‐...
  • Page 80: Low Calibration Pt. (Low Calib. Pt.) (2.2.1.6.)

    Distance from Sensor Reference to High Calibration Point (corresponding to High Level Point). Units are defined in Sensor Units. (See Operation types (Page 75)for an illustration.) Values Range: 0 to 30 m. Default 0 m Related parameters 2.2.1.12. Near Range (Page 81) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 81: Limit Sensor Value (2.2.1.8.)

    Max. for 4" horn = 31 m (103.35 ft) Default: Value for Low Calibration Pt. + 1 m (3.28 ft) Use this feature if the measured surface can drop below the Low Cal. Point in normal operation. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 82: Sensor Offset (2.2.1.25.)

    Defines where on the echo the distance measurement is determined. (See Echo Position Detection (Page 153)) Rising Edge Center of Mass (COM) Options Hybrid (Center and CLEF) CLEF (Constrained Leading Edge Fit) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 83: Sampling (2.2.4.2.)

    Range: 5 to 95% Default: 70% Related Parameters 2.2.4.1.2. Echo Position (Page 82) When SITRANS LR260 is using Rising Edge, higher values will cause lower level readings and lower values will cause higher level readings. 8.5.16.2 Sampling (2.2.4.2.) Provides a method of checking the reliability of a new echo before accepting it as the valid reading, based on numbers of samples above or below the currently selected echo.
  • Page 84: Up Sampling (2.2.4.2.4.)

    ● For faster Measurement Response values, the window becomes progressively wider. Note The echo lock window is stored as standard sample, but displayed in sensor units. Any value entered for the echo lock window will be rounded to the nearest sample. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 85: Filtering (2.2.4.3.)

    = wider  Range: 0 to 50 mS  Recommended: 5 to 20 mS; higher is not recommended. Related parameters 2.2.4.1.1. Algorithm  (Page 82) 2.2.4.3.6. Narrow Echo Filter (Page 85) 2.2.4.1.5. Echo Marker (Page 83) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 86: Noise (2.2.4.5.)

    When SITRANS LR260 is located in the center of the vessel, the TVT hover level may be lowered to increase the confidence level of the largest echo. (For an illustration of the TVT curve see Before Auto False Echo Suppression (Page 87).)
  • Page 87: Auto False Echo Suppression (2.2.5.2.)

    Default: 1.00 m 1. Press RIGHT ARROW to open Edit mode.  2. Enter the new value and press RIGHT ARROW to accept it. 3. Set 2.2.5.2. Auto False Echo Suppression (Page 87). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 88: Shaper Mode (2.2.5.4.)

    Shaper Mode (Page 88). 8.5.24 Shaper 1-9 (2.2.6.1.) Values Range: –50 to 50 dB Default: 0 dB 8.5.25 Shaper 10-18 (2.2.6.2.) Values Range: –50 to 50 dB Default: 0 dB SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 89: Shaper 19-27 (2.2.6.3.)

    1 m/min 1 m/min 10 s max verifica‐ Options tions fast 10 m/min 10 m/min max. verifica‐ tions Use a setting just faster than the maximum filling or emptying rate (whichever is faster). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 90: Fill Rate (Fill Rate/Min.) (2.2.7.2.)

    Fill Rate (FILL RATE/MIN.) (2.2.7.2.) Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you to adjust the SITRANS LR260 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered.
  • Page 91: Space Measurement (Space Meas.) (2.2.8.3.)

    Range: 3.6 mA to 22.6 mA 8.5.40 mA Output Function (mA OUTPUT FUNC.) (2.3.1.2.) Alters the mA output/measurement function and allows the output to be set independently. Manual Level Options Space Distance SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 92: Ma Setpoint (2.3.1.3.)

    4 mA 0% 0% 4 mA ⑮ Level Range: 0 to 30 m Values Default: 0 m (set to value corresponding to 0% as defined by mA Output Function) Related Parameters mA Output Function SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 93: Ma Setpoint (2.3.1.4.)

    Prevents the mA output from rising above this maximum level for a measurement value. This does not restrict the Fail-safe or manual settings. Values Range: 3.8 to 20.5 (mA) Default: 20.5 (mA) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 94: Ma Output Trim (2.3.1.7.)

    6. Confirm that the mA output is as expected. 8.5.47 Fail-safe (2.4.) 8.5.48 Fail-safe Timer (2.4.1.) Sets the time to elapse in minutes since the last valid reading, before Fail-safe State activates. Values Range: 0 to 720 min. Default: 1 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 95: Fail-Safe Material Level (Failsafe Mat. Le) (2.4.2.)

    To request a profile via SIMATIC PDM: 1. Open the menu View – Echo Profile. 2. If desired, press Save. 3. To view the saved profile, open the menu View – Show Echo Profile. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 96: Measured Values (Meas. Values) (3.14.)

    Minimum Internal Temperature (MIN. INTERN. TEMP.) (3.14.3.) Read Only. Displays (in degrees C) the minimum temperature recorded by the internal electronics. The high and low values are maintained over a power cycle. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 97: Remaining Device Lifetime (Remain. Dev. Life.) (3.15.)

    ● Click on Snooze to add a year to the Total Expected Device Life. 8.6.7 Total Device Operating Time (TOTAL OP. TIME) (3.15.1.) Read only. The amount of time the device has been operating in selected units. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 98: Remaining Device Lifetime (Remain. Lifetime) (3.15.2.)

    Allows you to enable a maintenance limit. Warning Limit 1 (Maintenance Required Limit) Warning Limit 2 (Maintenance Demanded Limit) Options Warning Limits 1 and 2 (Maintenance Required and Main‐ tenance Demanded Limits) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 99: Total Expected Device Life (Total Exp. Life) (3.15.6.)

    Acknowledges the current limit status To acknowledge an alert via PDM: 1. Open the menu View – Device Status and click on the tab Maintenance. 2. In the Device Lifetime section, click on Acknowledge Warnings. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 100: Remaining Sensor Lifetime (Remain Sens. Life.) (3.16.)

    ● Click on Snooze to add a year to the Total Expected Sensor Life. ● Click on Sensor Replaced to restart the timer and clear any fault messages. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 101: Total Sensor Operating Time (Sens Op. Time) (3.16.1.)

    To modify the value via PDM, open the menu Device – Maintenance and click on Remaining Sensor Lifetime. Modify limit values as required. Enable 3.16.5. Maintenance Alert Activation (ALERT ACTIVATION) (Page 102). Click on Write to accept the changes. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 102: Maintenance Alert Activation (Alert Activation) (3.16.5.)

    Read only. Acknowledges the status of the Maintenance limits. Via SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab and check the Sensor Lifetime Status window. 8.6.25 Acknowledge (ACK.) (3.16.9.) Acknowledges the current limit status. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 103: Service (4.)

    To perform a reset to factory defaults via SIMATIC PDM, open the menu Device – Device Reset and click on Factory Defaults. 8.7.2 Manufacture Date (MANUF. DATE) (4.2.) The date of manufacture of the SITRANS LR260 (yy mm dd). 8.7.3 LCD Fast Mode (4.3.) Note Affects Measurement mode only: has no effect on Navigation mode.
  • Page 104: Lcd Contrast (4.4.)

    Via SIMATIC PDM, open the menu View – Wear. Time powered is displayed in user selectable units via PDM. 8.7.6 Power-on Resets (4.8.) Read only. The number of power cycles that have occurred since manufacture. Via SIMATIC PDM, open the menu View – Wear. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 105: Memory Test (Mem. Test) (4.11.)

    Parameter reference 8.7 Service (4.) 8.7.7 Memory Test (MEM. TEST) (4.11.) Allows verification of the RAM, EEPROM, and Flash memory of the SITRANS LR260. IDLE No test in progress. BUSY Test in progress. PASS Memory test successful. FAIL Test failed.
  • Page 106: Time Last Serviced (Time Last Serv.) (4.16.1.)

    2. Set Maintenance Alert Activation to the desired option. 8.7.13 Maintenance Alert Activation (4.16.5.) Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 107: Total Service Interval (4.16.6.)

    Read only. Acknowledges the current limit status. Open the menu View – Display Status, click on the Maintenance tab and check the Service Schedule Status window. 8.7.17 Acknowledge (ACK.) (4.16.9.) Acknowledges the current limit status. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 108: Calibration Interval (Calib. Interval) (4.17.)

    Calibration Performed to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time Last Calibrated to zero. 8.7.20 Remaining Lifetime (REMAIN LIFETIME) (4.17.2.) Read only. Total Calibration Interval less Time Last Calibrated. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 109: Maintenance Required Limit (Maint. Req. Limit) (4.17.3.)

    On - limit 1 Values On - limits 1 and 2 On - limit 2 1. First set the limit values in Maintenance Required Limit/Maintenance Demanded Limit. 2. Select the desired Alert Activation option. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 110: Total Calibration Interval (Total Calib. Intrv.) (4.17.6.)

    2. In the Calibration Schedule Status section, click on Acknowledge Warnings. To acknowledge an alert via the handheld programmer: 1. Press RIGHT arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow to acknowledge the alert. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 111: Communication (5.)

    ● Press RIGHT arrow to open Edit mode. Key in a new value and press RIGHT arrow to accept it. 8.8.2 Communication Control (5.2.) Note SITRANS LR260 can only reset this parameter via the handheld programmer. Enables /disables the read/write access to parameters via remote communications. Read Only No changes are permitted via remote commu‐ nications.
  • Page 112: Security (6.)

    ● After a new value is stored in Unlock Value (6.2), that value will be recalled after a reset to Factory Defaults. ● Consult your Siemens representative if you have forgotten the unlock value. Stores the value to be entered in 6.1. Lock to unlock programming. If Lock is on, Unlock Value will not display the unlocked value.
  • Page 113: Language (7.)

    Parameter reference 8.10 Language (7.) 8.10 Language (7.) Selects the language to be used on the LCD. English German Options French Spanish SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 114 Parameter reference 8.10 Language (7.) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 115: Service And Maintenance

    ● Reliability of power supply, lightning protection, and grounds 9.1.2 Impermissible repair of the device WARNING Impermissible repair of the device ● Repair must be carried out by Siemens authorized personnel only. 9.1.3 Penetration of moisture into the device NOTICE Penetration of moisture into the device Device damage ●...
  • Page 116: Cleaning

    ● Note the antenna material and the process medium, and select a cleaning solution that will not react adversely with either. ● Remove the device from service and wipe the antenna clean using a cloth and suitable cleaning solution. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 117: Maintenance And Repair Work

    9.3.1 Impermissible repair of the device WARNING Impermissible repair of the device ● Repair must be carried out by Siemens authorized personnel only. 9.3.2 Maintenance The device is maintenance-free. However, a periodic inspection according to pertinent directives and regulations must be carried out.
  • Page 118: Disposal

    Service and maintenance 9.5 Disposal Required forms ● Delivery note ● Return goods note (http://www.siemens.com/processinstrumentation/returngoodsnote) with the following information: – Product (item description) – Number of returned devices/replacement parts – Reason for returning the item(s) ● Declaration of decontamination (http://www.siemens.com/sc/ declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully...
  • Page 119: Diagnosing And Troubleshooting

    SITRANS LR260. Any device with infrared capabilities (laptops, cell phones, PDAs) can cause interference ● PROGRAM mode displayed instead of which simulates a command to the SITRANS LR260, Measurement mode potentially causing it to switch modes or to change a ●...
  • Page 120: Device Status Icons

    ● Communication is good; device is in simulation mode or works with substitute values. ● Out of operation ● Communication is good; device is out of action. ● Data exchanged ● No data exchange ● Write access enabled ● Write access disabled SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 121: General Fault Codes

    ● Adjust process conditions to minimize foam or other tions, invalid configuration range. adverse conditions. ● Correct configuration range. ● If fault persists, contact your local Siemens representative. S: 2 Unable to collect profile because of a power Repair required: contact your local Siemens representative.
  • Page 122 Repair required: contact your local Siemens representative sensor has been lost. S: 34 Factory calibration for the device has been lost. Repair required: contact your local Siemens representative S: 35 Factory calibration for the device has been lost. Repair required: contact your local Siemens representative S: 36 Unable to start microwave module.
  • Page 123: Operation Troubleshooting

    ● correct calibration range. conditions, invalid calibration range. If fault persists, or for 1 and 2, contact your local Siemens representative. S: 53 Configuration lost: one or more parameter set‐ Restore user parameters using SIMATIC PDM.
  • Page 124 ● temperature too high ● relocate ● physical damage Reading does not SITRANS LR260 processing ● re-locate SITRANS LR260 change, but the level wrong echo. For example, vessel ● ensure nozzle protrudes 10 mm min. does wall or structural member ●...
  • Page 125: Technical Data

    Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power General Purpose Intrinsically Safe Nominal 24 V DC at 550 Ohm Non-Sparking Non-incendive (FM/CSA US/Canada only) ●...
  • Page 126: Interface

    Max. line length multi-wire: ≤ 1 500 m (4 921 ft) Protocol HART, Version 5.1 Configuration Remote Siemens SIMATIC PDM or AMS Device Manager (PC) Local Siemens infrared handheld programmer, or HART handheld communicator Display (local) graphic LCD, with bar graph representing level Display quality will be degraded in temperatures below –25 °C (–13 °F) and above +65 °C (+149 °F).
  • Page 127: Mechanical

    Note ● For the specific configuration you are about to use or install, check transmitter nameplate and see Approvals (Page 129). ● Use appropriate conduit seals to maintain IP or Type rating. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 128: Process

    2) Pressure rated version for maximum process temperature of 80 °C (176 °F) ① Ambient temperature ② Device nameplate ③ Device tag ④ Process temperature (at process connection) ⑤ Process connection tag (contains process connection related information) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 129: Approvals Data

    -40 °C ≤ Ta ≤ +80 °C IP67/IP68 11.8 Programmer data - 7ML1930-1BK Siemens Infrared IS (Intrinsically Safe) Handheld Programmer for hazardous and all other locations (battery is non-replaceable). Approvals FM/CSA Class I, II, III, Div. 1, Gr. A to G T6 ATEX 1 GD Ex ia op is IIC T4 Ga Ex ia op is IIIC T135°C Da...
  • Page 130 Technical data 11.8 Programmer data - 7ML1930-1BK SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 131: Dimension Drawings

    Stainless steel aimer version Note ● Process temperature and pressure capabilities are dependent upon information on the process device tag. ● Signal amplitude increases with horn diameter, so use the largest practical size. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 132 Process device tag point ② ⑦ Sensor reference point Universal slotted flange ③ ⑧ ½" NPT or M20 cable entry Optional horn extension ④ ⑨ Threaded cover Horn antenna ⑤ ⑩ Enclosure/electronics Antenna O.D. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 133: Stainless Steel Threaded Version

    ● Process temperature and pressure capabilities are dependent upon information on the process connection tag. ● Signal amplitude increases with horn diameter, so use the largest practical size. ● Optional extensions can be installed below the threads. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 134 ⑦ ½" NPT or M20 cable entry Sensor reference point ③ ⑧ Threaded cover Optional 100 mm (4.0 ") horn extension ④ ⑨ Enclosure/ electronics Horn ⑤ ⑩ Retaining collar Horn O.D. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 135 213 mm (8.39") 30m (98.4 ft) (2.94") 4 inch horn 94.8 mm 254 mm (10") 268 mm (10.55") 30m (98.4 ft) (3.73") Height from bottom of horn to sensor reference point as shown. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 136: Aluminum Horn Antenna

    Dimension drawings 12.3 Aluminum horn antenna 12.3 Aluminum horn antenna ① ½" NPT or M20 cable entry ② threaded cover ③ process connection tag ④ Aluminum horn antenna Dimensions in mm (inch) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 137: Aluminum Horn With Polypropylene Lens Antenna And Polymeric Flange

    Aluminum horn with polypropylene lens antenna and polymeric flange ① ½" NPT or M20 cable entry ② threaded cover ③ process connection tag ④ aluminum horn with polypropylene lens antenna Dimensions in mm (inch) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 138: Aluminum Horn Antenna With Aluminum Aiming Flange

    Aluminum horn antenna with aluminum aiming flange Aluminum horn antenna with 3" (80 mm) universal aiming flange ① ④ ½" NPT or M20 cable entry Horn ② Threaded cover ③ Process connection tag Dimensions in mm (inch) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 139 Aluminum horn antenna with 4" (100 mm) universal aiming flange ① ④ ½" NPT or M20 cable entry Horn ② ⑤ Threaded cover Universal aimer ③ Process connection tag Dimensions in mm (inch) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 140 12.5 Aluminum horn antenna with aluminum aiming flange Aluminum horn antenna with 6" (150 mm) universal aiming flange ① ④ ½" NPT or M20 cable entry Horn ② Threaded cover ③ Process connection tag Dimensions in mm (inch) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 141: Universal Stainless Steel Slotted Flange

    6 (150) 11.22 0.38 (9.65) 9.53 (242) 9.45 (240) 0.45 (11.5) (285) Dimensions are in inch (mm) Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 142: Universal Polymeric Flange

    5.91 (150) 0.37 (9.5) 4 (100) 9.00 (229) 0.7 (17.5) 7.52 (191) 6.89 (175) 0.37 (9.5) 6 (150) 11.22 (285) 0.7 (17.5) 9.53 (242) 9.45 (140) 0.45 (11.5) Dimensions are in inch (mm) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 143: Universal Aluminum Aimer Flange

    "A" "A" ① ⑤ bolt hole circle max. diameter flange O.D. ② ⑥ number of slotted bolt holes thickness ③ ⑦ bolt hole radius bolt hole circle min. diameter ④ section A-A SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 144 5.91 (150) 0.37 (9.5) 4 (100) 9.00 (229) 0.88 (22.3) 7.52 (191) 6.89 (175) 0.37 (9.5) 6 (150) 11.22 (285) 0.88 (22.3) 9.53 (242) 9.45 (240) 0.45 (11.5) Dimensions are in inch (mm) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 145: Mounting Bracket

    (4) M5 x 0.8 x 14 screws, washers, lock washers ② Mounting bracket ③ (2) M5 x 0.8 x 16 screws, washers, lock washers ④ (2) M5 x 0.8 x 16 screws, washers, lock washers, nylon insert lock nuts SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 146 12.9 Mounting bracket Dimensions in mm (inch) Note Torque the bracket screws to 5 Nm (3.7ft/lbs) to hold the aiming adjustment of the antenna. Wall and ceiling mount for free space applications SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 147: Application Examples

    YES in step 7 to apply changes.) In each example, after performing a Quick Start, navigate to the other required parameters (either via the handheld programmer, or via SIMATIC PDM) and enter the appropriate values. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 148 ● High Calibration Pt.= 0.5 m from sensor reference point. ● Maximum fill/empty rate = 0.1 m/ min. ● In the event of a loss of echo, SITRANS LR260 is to go into Fail-safe High after two minutes. SITRANS LR260 with mA/HART...
  • Page 149 Transfers Quick Start (1.7.) (Page 77) settings to device. Fail-safe Timer (2.4.1.) 2 minutes (Page 94) Independent parame‐ ters Fail-safe Material Level Failsafe level set to High (FAILSAFE MAT. LE) (2.4.2.) (Page 95) SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 150 Application examples 13.1 Application Example SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 151: Appendix A: Technical Reference

    Principles of operation SITRANS LR260 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries. (The microwave output level is significantly less than that emitted from cellular phones.) Radar level measurement uses the time of flight principle to determine distance to a material surface.
  • Page 152: Time Varying Threshold (Tvt) Curves

    TVT, amongst other characteristics. The true echo is selected based on the setting for the Echo selection algorithm (Algorithm 2.2.4.1.1 (Page 82)). SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 153: Echo Lock

    If the echo selected by Algorithm is within the Echo Lock window, the window is centered about the echo, which is used to derive the measurement. ● Lock Off: SITRANS LR260 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected.
  • Page 154 Example after Auto False Echo Suppression Auto False Echo Suppression Range set to 2 m ① ④ Learned TVT Default TVT ② ⑤ False echo Material echo ③ ⑥ Auto False Echo Suppression Range Echo marker SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 155: Measurement Range

    A.4.1 Near Range Near Range programs (2.2.1.12) (Page 81) SITRANS LR260 to ignore the zone in front of the antenna. The default blanking distance is 50 mm (1.97 inch) from end of horn antenna. Near Range allows you to increase the blanking value from its factory default. Auto False Echo Suppression (2.2.5.2) (Page 87) is generally recommended in preference to extending the...
  • Page 156: Ma Output

    ⑧ Distance When SITRANS LR260 is put into PROGRAM mode it stops responding to the process. It stores the most recent measurement, and holds the associated readings and mA signal output. The instrument reverts to the parameter last addressed during the previous program session.
  • Page 157: Loss Of Echo (Loe)

    If two faults are present at the same time, the fault code, error text, and error icon for each fault are displayed alternately. For example, Loss of Echo and Temperature Sensor Failure. S: 0 LOE S: 11 Temp. Sensor Failure SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 158: Fail-Safe Mode

    A.9.4 Fail-safe Level When Fail-safe Material level is set to Value, the Fail-safe Level defines a user-defined level to report when the Fail-safe timer expires. Fail-safe Level Values 3.6 to 22.6 mA SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 159: Process Pressure/Temperature Derating Curves

    Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 160: Versions With 3 Bar Pressure Rating

    Appendix A: Technical reference A.12 Loop power Siemens Level Transmitters with flanged, threaded, or sanitary clamp type process mounts have no pressure-bearing housing of their own and, therefore, do not come under the Pressure Equipment Directive as pressure or safety accessories (see EU Commission Guideline A-08 and A-20).
  • Page 161 Appendix A: Technical reference A.12 Loop power ① Loop voltage ② Power supply ③ Loop resistance RL ④ Loop current IL SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 162: Allowable Operating Area Of Sitrans Lr260

    Startup Behavior Note ● SITRANS LR260 is designed to start reliably with a power supply capable of delivering at least 25 mA. ● When connected to a power supply with a current limit of < 25 mA, the LR260 may not start reliably.
  • Page 163 Typical Startup Current ① Current (mA) ② Loop Power Supply without Current Limit ③ Loop Power Supply with 25 mA Current Limit ④ Time (seconds) ⑤ Current-limited power ⑥ No current limit SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 164 Appendix A: Technical reference A.12 Loop power SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 165: Appendix B: Hart Communications

    The radar device can be configured over the HART network using either the HART Communicator 375 by Fisher-Rosemount, or a software package. The recommended software package is the SIMATIC Process Device Manager (PDM) by Siemens. SIMATIC PDM This software package is designed to permit easy configuration, monitoring, and troubleshooting of HART devices.
  • Page 166: Hart Communicator 375 Menu Structure

    B.5 HART Communicator 375 Menu Structure HART Communicator 375 Menu Structure Note HART Communicator 375 is supported by SITRANS LR260 HART. The menu structure is aligned with the menu structure of SIMATIC PDM. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 167 Appendix B: HART Communications B.5 HART Communicator 375 Menu Structure SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 168: Supported Hart Commands

    B.7 Universal and Common Practice Commands Supported HART Commands SITRANS LR260 conforms to HART rev. 5 and supports the following: Universal Commands 0, 1, 2, 3, 6, 7, 8, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22...
  • Page 169: Product Documentation And Support

    – "Download as html5, only PC": Open or save the manual in the HTML5 view on your PC You can also find manuals with the Mobile app at Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/sc/2067). Download the app to your mobile device and scan the device QR code. Product documentation by serial number Using the PIA Life Cycle Portal, you can access the serial number-specific product information including technical specifications, spare parts, calibration data, or factory certificates.
  • Page 170: Technical Support

    In addition to our technical support, Siemens offers comprehensive online services at Service & Support (http://www.siemens.com/automation/service&support). Contact If you have further questions about the device, contact your local Siemens representative at Personal Contact. To find the contact for your product, go to "all products and branches" and select "Products &...
  • Page 171: List Of Abbreviations

    μs microsecond Nominal Pipe Size Pressure Equipment Directive safety approval pico Farads parts per million Primary Variable measured value Secondary Variable equivalent value Time Varying Threshold sensitivity threshold Input voltage Output voltage SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 172 List of abbreviations D.1 List of abbreviations SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 173: Lcd Menu Structure

    14.1 LCD menu structure Note ● In Navigation mode, ARROW keys ( ) navigate the menu in the direction of the arrow. See Parameter Reference (Page 73) for detailed information and instructions. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 174 LCD menu structure 14.1 LCD menu structure SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 175 LCD menu structure 14.1 LCD menu structure SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 176 LCD menu structure 14.1 LCD menu structure SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 177: Glossary

    (-3 dB) of the microwave beam. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 178 Echoes are frequently measured in decibels relative to the directly transmitted signal. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 179 1 Gigahertz (GHz) is equal to 109 Hz. horn antenna a conical, horn-shaped antenna which focuses microwave signals. The larger the horn diameter, the more focused the radar beam. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 180 Distance is determined by the return transit time. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 181 299, 792, 458 meters per second. stilling-well see stillpipe. stillpipe a pipe that is mounted inside a vessel parallel to the vessel wall, and is open to the vessel at the bottom. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 182 Can be loop powered, analog, intrinsically safe 4 to 20 mA, or a digital (BUS) transmitter. waveguide antenna a hollow, metallic tube that transmits a microwave signal to the product target. SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 183: Index

    48 Disposal, 118 Document history, 11 Downloads, 169 mA output select analog output, 70 maintenance, echo processing calibration schedules, 69 Process Intelligence, 151 repairs, 116 service schedules, 69 updating, 60 Manuals, 169 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...
  • Page 184 Warranty, 13 Wear reading erratic powered hours, 68 troubleshooting, 124 poweron resets, 68 reading incorrect view via PDM, 68 troubleshooting, 124 repair cautions, 117 Return procedure, 117 Scope of delivery, 12 Service, 170 SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD...