SPLIT TYPE AIR CONDITIONER DUCT TYPE (50Hz) Indoor unit Outdoor unit ARYG36LMLA AOYG36LATT ARYG45LMLA AOYG45LATT CONTENTS SPECIFICATIONS....DIMENSIONS..... .
SPECIFICATIONS ELECTRICAL DATA NOISE LEVEL High Cooling & Heating 40 dB 42 dB TYPE Medium 36 dB 38 dB INDOOR UNIT ARYG36LMLA ARYG45LMLA INDOOR UNIT OUTDOOR UNIT AOYG36LATT AOYG45LATT 31 dB 32 dB COOLING CAPACITY Quiet 10.0 kW 12.5 kW...
Page 11
OUTDOOR UNIT MAIN PCB REACTOR CN102 AOYG36LATT : K07AK-1200HUE-C1 2-1747052-3 R101 P I N 101 P I N 102 BLUE ZPR0RCH400 D101 340V AOYG45LATT : K07AK-1101HUE-C1 PFC5000-0702F x 2 CN101 LL25XB60 L101 B3P5-VH-B RCV1904-050PF07 WHITE L151 D151 C104 AC I N BL02Rn1 DAN217U 0.01...
Page 12
OUTDOOR UNIT TRANSISTOR PCB K11CA-1200HUE-TR1 TM802 YELLOW P I N D908 US1J TM803 BLUE R900 R901 R902 N I N P I N801 <2.8W> <7W> <7W> L960 RGDU7M RGGS7 RGGS7 BL02Rn1 R940 - R949 DC + P I N800 0.1 <1W> 1% x 10 L900 BL02Rn1 K880...
Page 13
OUTDOOR UNIT ACTIVE FILTER PCB - 1 K-11BZ-1100HUE-AF0 REACTOR L1 - L3 12A 18mH From Filter PCB TM504 TM300 TM500 DC+ OUT L1 I N W300 TM301 TM501 L2 I N W301 TM302 TM502 L3 I N W302 TM505 N OUT CT301, CT300 D351 FC-1-X x 2...
Page 14
OUTDOOR UNIT ACTIVE FILTER PCB - 2 K11BZ-1100HUE-AF0 Jump To Page1 Jump To Page1 R530, R536 47k 1% x 2 D530 I C510-3 D470 R590 R539 C530 RB751V BA2901F DAN217U D533 R533 RB751V <F> R470 - R474 R503 8.2k 1% C591 220k <1/3W>...
Page 15
OUTDOOR UNIT FILTER PCB K07AQ-0700HUE-FL0 3 Phase 380 - 415V 50Hz VA202 L200 L201 H-0017-2 x 2 820V RC3V3812-009PF05 RC3V3812-009PF05 FH200 FH201 L1 I N <TNR> 12A 0.9mH 12A 0.9mH TM203 L1 OUT TM200 VA200 P200 <NSHV4> 820V <TNR> H-0017-2 x 2 L2 I N FH202 FH203...
Page 16
OUTDOOR UNIT CAPACITOR PCB K07AP-0700HUE-P0 W700 W702 P I N P OUT YELLOW ORANGE R700 R702 C700 C702 660/ 660/ 450V <RS-5W> <RS-5W> 450V R701 R703 C701 C703 660/ 660/ <RS-5W> <RS-5W> 450V 450V W701 W703 N OUT N I N BLUE PURPLE 2012.02.29...
ER R OR D E TEC TION Receiver unit Receiver unit Wired Wired OPERATION TIMER ECONOMY remote Description OPERATION TIMER ECONOMY remote Description INDOOR UNIT lamp lamp lamp lamp lamp lamp control control (green) (orange) (green) (green) (orange) (green) and WIRED REMOTE CONTROL Discharge temp.
Page 18
OUTDOOR UNIT TEST RUN CAUTION Always turn on the power 6 hours prior to the start of the operation in order to protect the compressor. 1. Check items before performing the test run 2.1. Operating procedures for the test run Make sure to perform the test run.
Page 19
OUTDOOR UNIT ERROR CODE DISPLAY Display when an error occurs TEST PUMP POWER LOW NOISE PEAK CUT DOWN ERROR MODE (L1) (L2) (L3) (L4) (L5) (L6) (L7) Blinks (Hi-speed) Check that the ERROR LED blinks, and then short-press the [ENTER] switch once. Display mode : ON The number of blinks of the LED indicates the type of error.
Page 20
2. Pump down procedure OUTDOOR UNIT PUMP DOWN (Refrigerant collecting operation) (1) Check the 3-way valves (both at the liquid side and gas side) are opened. (2) Turn the power on. Perform the following procedures to collect the refrigerant when moving the indoor unit or outdoor unit TEST PUMP POWER...
PARTS INDOOR UNIT Ref. Description Part number Intake Cover Sub Assy 9374512010 Main Panel Sub Assy 9374511013 Drain Pan Sub Assy 9374513017 Evaporator Total Assy 9374517251 Seal Panel Sub Assy 9374515011 Outlet Panel Sub Assy 9374510016 Intake Frame Assy 9374216017 Cabinet L Sub Assy 9374509010 Cabinet R Sub Assy...
Page 22
INDOOR UNIT Ref. Description Part number Base Sub Assy 9374504015 Casing A 9374233014 Casing B 9374234011 Sirocco Fan Assy 9356531046 Fan Motor 9603213015 Panel (Control Box) 9374210015 2012.04.11...
Page 23
INDOOR UNIT Ref. Description Part number Control unit Main PCB (36) 9709245330 Main PCB (45) 9709245347 Power Supply PCB 9707398359 Terminal 3P 9703345012 Terminal 3P 9306489045 Reactor Assy 9707457018 Remote Control 9318593013 Room Thermistor 9703299025 Pipe Thermistor 9703297021 2013.03.07...
PARTS OUTDOOR UNIT Ref. Description Parts number Ref. Description Parts number Top Panel Sub Assy 9374417032 Reactor Assy 9900641016 Front Panel Sub Assy 9374414130 Motor, DC Brushless 9602843046 Sevice Panel Sub Assy 9374415076 Propeller Fan Assy 9366378020 Emblem Rear 9351355005 Condenser A Sub Assy 9374420261 Pipe Cover Front...
A C C ESS OR IES INDOOR UNIT Name and Shape Q'ty Application Part number Hanger For suspending the 9356563009 indoor unit from ceiling Special nut A 313005446653 (large flange) Special nut B 313005446759 (small flange) Coupler heat For indoor side pipe joint insulation (large) (gas pipe) 9378173569...
Page 28
OPTIONAL PARTS Parts name Model No. Application Wired remote control UTY-RNNYM For air conditioner operation Simple remote control UTY-RSNYM For air conditioner operation Remote sensor unit UTY-XSZX Room temperature sensor UTD-ECS5A For control input/output port External connect kit Square flange UTD-SF045T Round flange UTD-RF204...