hit counter script

In Case Of Compressor Malfunction - Sanyo SAP–KR184GJ Technical & Service Manual

Split system air conditioner
Table of Contents

Advertisement

10-5. In case of compressor malfunction

CAUTION
10-5-1.Procedure for replacing compressor
(1) Recovering refrigerant
• Any remaining refrigerant inside the unit should not be
released to the atmosphere, but recovered using the
refrigerant recovery unit for R410A.
• Do not reuse the recovered refrigerant, since will con-
tain impurities.
(2) Replacing compressor
• Soon after removing seals of both discharge and
suction tubes of the new compressor, replace it
quickly.
(3) Checking for sealing
• Use nitrogen gas for the pressurized gas, and never
use a refrigerant other than R410A. Also do not use
oxygen or any flammable gas.
(4) Evacuation
• Use a solenoid valve-installed vacuum pump so
that even if power is cut off in the middle of evacuation
of air due to a power interruption, the valve will pre-
vent the pump oil from flowing back.
• The equipment may be damaged if moisture remains
in the tubing, thus carry out the evacuation thoroughly.
• When using a vacuum pump with exhaust air volume
more than 25L/min. and ultimate vacuum pressure
rate of 0.05Torr:
Standard time of evacuation
Length of tubing
Time
Should the compressor malfunction, be sure to replace compressor
as quickly as possible.
Use only the tools indicated exclusively for R410A.
specifically for R410A".
Less than 10 meters
More than 10 minutes
(1) Recover refrigerant
(2) Replac compressor
(3) Check for sealing
(4) Evacuation
(5) Recharge
More than 10 meters
More than 15 minutes
44
See "10-3. Tools
OK
OK
OK
OK

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap–cr184gSap–kr224gjSap–cr224g

Table of Contents