hit counter script

Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aoyg09Kbtb - Fujitsu AUXG09KVLA Design & Technical Manual

Cassette type
Hide thumbs Also See for AUXG09KVLA:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOYG09KBTB

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
HEATING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
6-1. Model: AOYG09KBTB
Height difference H
1
*
H
Outdoor unit
15
10
1
7.5
5
0.992
0
1.000
-5
1.000
-7.5
2
-10
-15
15
10
1
7.5
5
1.000
0
1.000
-5
0.995
-7.5
2
-10
-15
- 65 -
Indoor unit is lower than outdoor unit
Outdoor unit
Connection pipe
Pipe length (m)
5
7.5
10
0.964
0.988
0.968
0.992
0.972
1.000
0.980
1.000
0.980
1.000
0.980
0.980
Pipe length (m)
5
7.5
10
1.010
1.000
1.010
1.000
1.010
1.000
1.010
0.995
1.005
0.993
1.002
0.999

6. Capacity compensation rate for pipe length and height difference

2
*
H
Indoor unit
15
20
0.903
0.894
0.918
0.909
0.922
0.912
0.925
0.916
0.933
0.923
0.933
0.923
0.933
0.923
0.933
0.923
0.933
0.923
15
20
0.943
0.916
0.943
0.916
0.943
0.916
0.943
0.916
0.943
0.916
0.939
0.912
0.936
0.909
0.934
0.907
0.925
0.898

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents