6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe
6-1. Model: AOYG09KBTB
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
HEATING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
6-1. Model: AOYG09KBTB
Height difference H
1
*
H
Outdoor unit
15
10
1
7.5
5
0.992
0
1.000
-5
1.000
-7.5
2
-10
-15
15
10
1
7.5
5
1.000
0
1.000
-5
0.995
-7.5
2
-10
-15
- 65 -
Indoor unit is lower than outdoor unit
Outdoor unit
Connection pipe
Pipe length (m)
5
7.5
10
—
—
—
—
—
0.964
—
0.988
0.968
0.992
0.972
1.000
0.980
1.000
0.980
—
1.000
0.980
—
—
0.980
—
—
—
Pipe length (m)
5
7.5
10
—
—
—
—
—
1.010
—
1.000
1.010
1.000
1.010
1.000
1.010
0.995
1.005
—
0.993
1.002
—
—
0.999
—
—
—
6. Capacity compensation rate for pipe length and height difference
2
*
H
Indoor unit
15
20
0.903
0.894
0.918
0.909
0.922
0.912
0.925
0.916
0.933
0.923
0.933
0.923
0.933
0.923
0.933
0.923
0.933
0.923
15
20
0.943
0.916
0.943
0.916
0.943
0.916
0.943
0.916
0.943
0.916
0.939
0.912
0.936
0.909
0.934
0.907
0.925
0.898