In order to keep the manual lean and show you how topics are interrelated, cross-references are used. Field of use The Climatix HMI-DM products can only be used in the field of heating, ventilation, air conditioning and refrigeration. Proper use Prerequisites for flawless and safe operation of the Climatix HMI-DM products are proper transport, installation and commissioning, as well as correct operation.
SCOPE commissioning and service tool Human machine interface Brief introduction The Climatix HMI-DM is designed for display, system configuration, set-up and operation. It is a product of the Climatix range, supporting all Climatix range of controllers. The Climatix HMI-DM cannot be used to operate any 3 -party devices.
- Firmware upgrades over SCOPE tool or SD card Reference documents The following documents contain further information on the products described in this document. Document Document No. Data sheet “Climatix HMI-DM” CB1Q3941en Mounting instructions “Climatix HMI-DM” CB1M3940en Climatix controllers POL6xx and I/O modules POL9xx – CB1P3903en...
Refer to CB1P3903en, section 10 “Climatix process bus” for more information about network’s characteristics and limit. Connection via process The connection via process bus is shown as follows: 7/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Connections 2015-07-02...
The HMI-DM is equipped with a USB interface. Users can connect the HMI-DM to a PC via USB interface to upgrade the firmware. PC connection The connection with PC is illustrated as follows: 8/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Connections 2015-07-02...
HMI-DM overview This section introduces the overview of Climatix HMI-DM. Function keys The function keys of HMI-DM are illustrated as follows: Key Name Operation Description To increase the input value Turn the knob Turning the knob clockwise rapidly and continually will enable...
Character size For Latin (English) characters, font size 6*12 pixels (width*height) is supported; For Eastern Asian characters such as Chinese, font size 12*12 pixels (width*height) is supported. Here are the examples: 10/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies HMI-DM overview 2015-07-02...
Page 11
INFO and the current user level has the area privilege to access to this target page, it will redirect to this page. Regarding how to program a title line, please refer to Climatix SCOPE online help. 11/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies HMI-DM overview 2015-07-02...
Page 12
In the case that 12*12 Eastern Asian characters such as Chinese are used, maximum 8 lines can be displayed in one screen. Maximum 15 characters can be displayed in each line including the submenu indicator “►”. 12/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies HMI-DM overview 2015-07-02...
ID “[00:FD:10:80:00:6D]” in the process bus. Users can change the screen settings on this page, such as backlight color, backlight turn off time, contrast, and brightness. 13/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 14
(0…300 seconds, configurable). Follow the steps to change the backlight turn off time. 1. Select Backlight Turn Off Time. 2. Press key ROLL, and then turn the knob to change the value. 14/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 15
Refer to Backlight color for value editing. The brightness of HMI-DM screen can be configured from 0 to 100. Brightness Refer to Backlight color for value editing. 15/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Turn the knob of key ROLL to select one controller and press key ROLL to confirm the selection. Then the communication between the HMI-DM and the selected controller will be set up. 16/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 17
After the objects have been downloaded, it will redirect to the following page as follows: If the version of controller BSP is below 7.32, it will redirect to the home page without downloading the objects. 17/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
For example 1. Press and hold key ROLL at any page (except the error report pages) with OEM factory user level to go to the log in/off page as follows: 18/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 19
If yes, it will redirect to the target page. Otherwise, it will redirect to the home page. The corresponding user level will be displayed on the upper-left corner as follows. 19/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 20
If the password is entered incorrectly, it will display the following information: 20/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 21
For detail information about how to configure the password, refer to Climatix SCOPE online help. To change the password of user level, select Change User Password and press key ROLL, and the following page will be displayed. 21/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
After logging in with one certain user level, it will automatically log off if there is no operation within a certain period (defined in the controller by application engineer). 22/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
A dedicated page is used to edit integer or float type of value. On the value-editing integer and float page, turn the knob of key ROLL to change the value. 23/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 24
ROLL to choose the multiple options. At the very bottom of the options, a fixed item Done is available for users to confirm the selection and exit. Press key ESC to exit and all the modifications will be cancelled. 24/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Press key ALARM, and the alarm related pages will be displayed by the following order: Alarm list detail →Alarm list →Alarm history list →Alarm list/history settings. Alarm list detail page Alarm list page 25/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 26
To change the sorting methods, select SortOrder1 or SortOrder2 on the Alarmlist/-historysettings page, and the following page will be displayed. Select one sorting method on this page and press key ROLL to confirm the selection. 26/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Activate two trend lines two trend lines. The maximum and minimum value of Y-axis is calculated automatically based on the actual values of data point, and will be adjusted to be reasonable. 27/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
BSP 10.xx or above. Other HMI types have only text time scheduler (e.g. HMI-IB, HMI4Web). 1. Define the name for time scheduler (e.g. “Enumeration Scheduler” or “Set point Scheduler”) in SCOPE as follows. 28/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 29
To adjust the date and time Turn the knob To change enumeration value or set ROLL point Press To confirm the selection INFO Long press (3 seconds) To delete a scheduler entry 29/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 30
4. Turn the knob of key ROLL to adjust the value on the vertical axis. The value is displayed on the top line. Press key ROLL. 5. Repeat step 3 through 4 until all scheduler points are set. 30/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
Page 31
4. Turn the knob of key ROLL to adjust the value on the vertical axis. The value is displayed on the top line. Press key ROLL. 5. Repeat step 3 through 4 until all scheduler points are set. 31/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 32
3. Turn the knob of key ROLL to select the scheduler entry. 4. Long press key INFO 3 seconds to delete it. It is possible to set maximum 6 scheduler entries. Afterwards an error message appears. 32/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
3. Press and hold key ESC to enter Setting and Local connection page. 4. Select HMI Setting and press key ROLL. Following page is displayed. 5. Select Firmware Update and press key ROLL, and turn the knob and select Yes. 33/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Functions and operations 2015-07-02...
Page 34
When the firmware of HMI-DM has been upgraded successfully, INFO LED is green. If there is no operation within 15 seconds, HMI-DM restarts and enter the home page. 34/36 Siemens Climatix HMI-DM CB1P3916en02 Building technologies Functions and operations 2015-07-02...
24 √ Alarm management on page 25 √ Online trend on page 27 √ Graphical time scheduler on page 28 √ Firmware Update on page 33 35/36 Siemens Climatix HMI-DM CB1P3916en02 Building Technologies Function list 2015-07-02...