4.1.2

Explanation of the parameters

Dual assignment of the socket
Defines whether dual assignment of the socket is enabled for the respective channel group.
The channel groups are defined by the digital inputs of the relevant sockets:
• Channels 0 and 1 form the channel group at socket X10
• Channels 2 and 3 form the channel group at socket X12
• Channels 4 and 5 form the channel group at socket X14
• Channels 6 and 7 form the channel group at socket X16
You can find more information in section Pin assignment (Page 16).
Diagnostics: Undervoltage 1L+
Enabling of diagnostics for insufficient supply voltage 1L+.
Undervoltage at 1L+ triggers the "Undervoltage" maintenance event. You can find more
information in section Maintenance events (Page 31).
Diagnostics: Short-circuit
Enabling of diagnostics for short-circuit to ground at transducer supply
Diagnostics: Wire break detection and alarm
Activation of wire break detection and enabling of diagnostics. In the event of an interruption
of the line between the encoder and I/O device, a diagnostics alarm is generated.
Note
Effect on the value status
When the parameter is deactivated, wire break detection is switched off. A wire break does
not have an effect on the value status.
I/O device digital inputs DI 8x24VDC M12-L 8xM12 (6ES7141-6BG00-0BB0)
Equipment Manual, 02/2022, A5E46570417-AC
PROFINET IO
4.1 Parameters/address space
21