6.1.3

Explanation of the parameters

Dual assignment of the socket
Defines whether dual assignment of the socket is enabled for the respective channel group.
The channel groups are defined by the digital inputs of the relevant sockets:
• Channels 0 and 1 form the channel group at socket X10
• Channels 2 and 3 form the channel group at socket X12
• Channels 4 and 5 form the channel group at socket X14
• Channels 6 and 7 form the channel group at socket X16
You can find more information in section AUTOHOTSPOT.
Diagnostics: Undervoltage 1L+
Enabling of the diagnostics for insufficient supply voltage 1L+.
Diagnostics: Short-circuit
Enabling of diagnostics for short-circuit to ground at transducer supply
Diagnostics: Wire break detection and alarm
Activates wire break detection and enabling of diagnostics for the digital input in case of an
interruption of the cable between the encoder and I/O device.
Note
Effect on the value status
When the parameter is deactivated, wire break detection is switched off. A wire break does
not have an effect on the value status.
Input delay
This parameter can be used to suppress signal interference. Changes to the signal are only
detected if they are present consistently for longer than the set input delay time.
For input channels with longer input delays, the read-in time is moved accordingly. This
means individual channels can be assigned input delays, if necessary, without having a
negative impact on the possible update time.
Hardware interrupt on rising edge
Specifies whether a hardware interrupt is generated via the data status on a rising edge on
the channel. The hardware interrupt information can be read and confirmed via the event
interface.
I/O device digital inputs DI 8x24VDC M12-L 8xM12 (6ES7141-6BG00-0BB0)
Equipment Manual, 02/2022, A5E46570417-AC
6.1 Functions/parameters/address space