Installation and Operating Manual – FSX™ Fire and Flame Detectors Model FS24X™ FS24X QuadBand Triple IR™ Multi-Spectrum Infrared Electro-Optical Multi-Spectral Digital WideBand IR Sensor Radiant Energy Fire and Flame Detector...
• Selecting a unique digital address (128 choices). • Factory Use 3. The ten (10) position Rotary switch Figure 1-3 allows selection of the analog and FS24X and FS24X-9 Detector Puck, ( rear view digital communication protocol. Honeywell...
Heater circuit turns ON only when temperature drops below zero (0) degrees Farenheit (-17° C) The supply connection wiring shall be rated at least 10°C above the rated service temperature (120°C for T4 applications and 85°C for T5 applications) Honeywell...
Flame Performance Certification (See Sections 4.7.3 and 4.7.4 on page 28 and 29) Agency Standard Certificate Notes LPCB EN 54-10:2002 +A1:2005 1175a/02 Sensitivity settings: Very High, High EN 54-10 Class 1 EN 54-10:2002 +A1:2005 0832-CPR-F0516 FM/cFM FM3260 Sensitivity: Very High Honeywell...
• FSC Windows® based PC Interface User can perform remote FSX Detector diagnostics, real-time status, Real-Time Graphing (RTG), SnapShot data recording, and downloading FirePic’s with Honeywell Analytics’ exclusive FSIM-2 USB ® Interface Unit and easy to use Windows based PC Software.
Detector may cause the fire to be undetected. 5. The Model SM4 is a 316 Stainless Steel Swivel Mount designed for the Honeywell Analytics Detector housing. The adapter plate, with the two (2) screw holes (facing away), is attached to the base of the Detector (see Figure 2-1).
Page 9
3. There are no serviceable parts inside the Detector puck. If the puck is opened up or tampered with, all warranties are voided. CAUTION: Follow static protection procedures while handling the connectors and the wiring of the Module puck to the Detector. Use a wrist strap connected to earth ground. Honeywell...
It is necessary to remove the Detector Module puck from the enclosure to access the field connections. CAUTION: Disconnect power before unscrewing the Housing Lid. 1. Loosen the set screw on the enclosure lid (see Figure 2-6). Figure 2-6 2. Turn counterclockwise (CCW) to unscrew the enclosure lid (see Figure 2-7). Figure 2-7 Honeywell...
Page 11
Installation and Operating Manual Opening the Detector (continued) 3. Loosen the three captive screws on the Detector Module puck (see Figure 2-8). Figure 2-8 4. Slide the Detector Module puck out of the enclosure base (see Figure 2-9). Figure 2-9 Honeywell...
Alarm COM 4-20mA Sink Figure 2-10 Fault NO Detector Puck, ( rear view Fault COM +24 VDC DC Return Contacts shown with no power applied Note: Do not attempt to open the Detector Module puck as this voids all warranties. Honeywell...
Page 14
2. Avoid wire splices whenever possible. If wire splices are required, solder and properly insulate them. Good wiring practices simplify installation, improve reliability, and facilitate maintenance. 3. For applications requiring analog/digital communications, please refer to Section 3.2 of this Instruction Manual. Honeywell...
6. To ensure optimum performance, shield the detector face from intense bright light sources when first energized. The Detector is now ready for Power-Up. on Power-Up, the Fault Relay will change status if the Factory Default Setting is used (Section 3.2). Honeywell...
The TL-1055 and the TL-2055 are the only Test Lamps that will activate the FSX Detectors.. Additionally, do not use these Test Lamps to activate other Honeywell Analytics Detectors (nor any other conventional fire and flame detectors). Do not use other Honeywell Analytics Test Lamps or non-Honeywell Analytics Test Lamps to test the FSX Detectors.
Page 17
Remember to disable the outputs, as a full functional test includes activating the ALARM outputs. A Honeywell Analytics Test Lamp must be used for this test (Section 4.4). Point the Test Lamp directly at the front of the Detector (on axis as much as possible, within a distance of about 1 to 25 feet). Activate the Test Lamp by pressing and holding its pushbutton.
WideBand IR regions from approximately 1.1 to 3.0 microns and 3.0 to 5.0 microns. This allows the FS24X Detectors to sense over 85% of the total radiant “Blackbody Energy” emitted by a fire. Honeywell Analytics’ Detectors sense and measure the radiant energy generated by a fire at the speed of light.
Page 19
Figure 3-3 to configure SW3. Factory Use Only Factory Use Only Figure 3-3 SW3 10-Position Factory Use Only Rotary Switch Factory Use Only Note: The Medium and Low Sensitivity ranges are not approved as compliant with the requirements of EN 54-10:2002. Honeywell...
• 4-20 mA (source 20 mA) Output • RS-485 FireBus Alarm Notification • RS-485 Modbus Alarm Notification Figure 3-5 Red LED Location 1 This output is a Verified Alarm Output 2 Only one active Alarm output from this group Honeywell...
Additionally, semi-annual or quarterly testing should be performed, using the correct Honeywell Analytics Test Lamp, to ensure the integrity of the entire fire protection system. In order to ensure the Detector is operating properly at all times, it may be necessary to establish a periodic cleaning schedule.
Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of three years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
2 = Relays / HART Communication Application 1 = General Applications Manufacturer’s Code 2 = Standard Honeywell Analytics Detector - 110° Field of View (-1 has been replaced by -2) 9 = Standard Honeywell Analytics Detector - 90° Field of View EXAMPLES: FS24X-911-21-1 QuadBand Triple IR Detector, 90°...
Some manufacturers claim that their detectors do not need remote testing with an external Test Lamp because it tests itself. Even though Honeywell Analytics Detectors also perform “through the lens” self-testing and tests themselves, Honeywell Analytics, in compliance with NFPA 72 codes, has developed portable test lamps for periodical “end-to-end”...
< 8 seconds Pine Needles 12 in X 12 in (0.3m X 0.3m) 50 feet (15 meters) < 8 seconds Wood 12 in X 12 in (0.3m X 0.3m) 90 feet (27 meters) 50 < 6 seconds feet (15 meters) Honeywell...
1. Cable shield must be grounded at one end only, at the Control Panel. Coil and tape cable shield at the Detector end. 2. Set SW3 (rotary switch) to position one (1) for Source current wiring. 3. Set SW3 (rotary switch) to position zero (0) for Sink current wiring. Honeywell...
Page 29
3. Fault relay contacts shown with no power applied. During normal operation and with no Fault, this relay will De-Energize and the N.O. (normally open) contacts will close. 4. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Honeywell...
Page 30
FS24X-2 FS24X-2 FS24X-2 FS24X-2 FS24X-2 FS24X-2 FS24X-2 -60ºC to -60ºC to -60ºC to Label, 0.020” 316 QuadBand 1175a/02 +110ºC +75ºC +60ºC FS24X-9, ss, Stainless Triple IRTM Matte Black FS24X-9 0832-CPR- with Steel F0516 6095- FM/Canada/U S ATEX, IECEX approval Honeywell...
Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.