Functions
2.1 General
2.1.6.3 Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
1102
FullScaleCurr.
1107
I MOTOR START
2.1.6.4 Information List
No.
Information
126
ProtON/OFF
356
>Manual Close
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
4602
>52-b
16019
>52 Wear start
16020
52 WearSet.fail
16027
52WL.blk I PErr
16028
52WL.blk n PErr
46
C
Setting Options
10 .. 50000 A
1A
0.40 .. 10.00 A
5A
2.00 .. 50.00 A
Type of In-
formation
IntSP
Protection ON/OFF (via system port)
SP
>Manual close signal
OUT
Relay PICKUP
OUT
Relay GENERAL TRIP command
VI
Primary fault current Ia
VI
Primary fault current Ib
VI
Primary fault current Ic
OUT
Manual close signal detected
SP
>Enable 50/67-(N)-2 (override 79 blk)
SP
>52-a contact (OPEN, if bkr is open)
SP
>52-b contact (OPEN, if bkr is closed)
SP
>52 Breaker Wear Start Criteria
OUT
52 Wear blocked by Time Setting Failure
OUT
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
OUT
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
Default Setting
100 A
Measurem:FullScaleCur-
rent(Equipm.rating)
2.50 A
Motor Start Current (Block
49, Start 48)
12.50 A
Comments
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008