hit counter script

Outdoor Unit - Fujitsu AUXG18KVLA Service Manual

Simultaneous multi
Hide thumbs Also See for AUXG18KVLA:
Table of Contents

Advertisement

5-2. Outdoor unit

¢ Heatsink thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
5-2. Outdoor unit
Resistance (kΩ)
94.26
67.95
49.62
36.68
27.42
20.73
15.83
12.21
9.50
7.46
5.90
4.71
3.78
3.06
2.50
2.05
1.69
1.40
1.17
0.98
0.83
0.70
0.60
0.51
0.44
0.38
0.33
- (03-68) -
Voltage (V)
0.08
0.11
0.15
0.20
0.26
0.34
0.43
0.55
0.68
0.84
1.01
1.21
1.42
1.64
1.88
2.11
2.35
2.58
2.81
3.02
3.22
3.41
3.58
3.73
3.87
3.99
4.10
5. Thermistor resistance values

Advertisement

Table of Contents
loading

Table of Contents