E2S BExCP3C-BG Instruction Manual

Break glass manual call point for use in flammable gas and dust atmospheres
Hide thumbs Also See for BExCP3C-BG:

Advertisement

Quick Links

BExCP3C-BG
Manual Call Point – Break Glass
With Resistor Modules
For use in Flammable Gas and
Combustible Dust Atmospheres.
1)
Introduction
The BExCP3C-BG is a break glass manual call
point which is certified to the European and
International Gas and Dust standards. The unit
meets the requirements of the ATEX directive
2014/34/EU and IECEx scheme.
The call point can be used in hazardous areas
where
potentially
flammable
gas
and
dust
atmospheres may be present.
All units have up to two of the following:
Monitoring resistors up to 1.5W per module
Monitoring diode
Monitoring Zener diode
The units are Group II, EPL (equipment protection
level) Gb. The equipment is certified 'Ex db eb mb
IIC T4 Gb' and as such may be used in Zones 1
and 2 with flammable gases and vapours with gas
groups IIA, IIB & IIC and temperature classes T1,
T2, T3 and T4.
These units are also Group III, EPL Db. The
equipment is certified 'Ex tb IIIC T75ºC Db' and as
such may be used in Zones 21 and 22 for
combustible dusts groups IIIA, IIIB & IIIC.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document D150-00-055-IS Issue 2 11-08-22
INSTRUCTION MANUAL
BExCP3C-BG Break Glass Manual Call Point
For use in Flammable Gas and Dust Atmospheres
2)
Ratings & Markings
All units have a rating label, which carries the
following important information: -
Unit Type No.:
BExCP3C-BG Manual Call Point
Input Voltages:
Important: See section 7.1 for current ratings
125VDC Max
0.5A Max. Resistive Load;
0.03A Max Inductive Load
75VDC Max
0.75A Max
48VDC Max
1.0A Max
24VDC Max
5.0A Max Resistive Load;
3.0A Max Inductive Load
12VDC Max
5.0A Max
6VDC Max
5.0A Max
Code:
BExCP3C-BG
Ex db eb mb IIC T4 Gb
Ex tb IIIC T75ºC Db
IP66
–40ºC <= Ta <= +65ºC
Certificate No.:
SIRA 09ATEX3286X
IECEx SIR 09.0121X
CSAE 21UKEX3556X
Epsilon x:
II 2GD
CE Marking
Notified
2813
Body No.
UKCA Marking
Notified Body No.
0518
Year/Serial No. i.e.20/1CP3CBG000001
WARNING - DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT
3)
Type Approval Standards
The call point has an EC Type examination
certificate issued by SIRA and have been approved
to the following standards: -
EN60079-0:2018 / IEC60079-0:2017
EN60079-1:2014 / IEC60079-1:2014
EN60079-7:2015 / IEC60079-7:2017
EN60079-18:2015 / IEC60079-18:2014
EN60079-31:2014 / IEC60079-31:2013
The equipment is certified for use in ambient
temperatures in the range
o
o
BExCP3C-BG -40
C to +65
C
and shall not be used outside this range.
4)
Installation Requirements
Installation of this equipment shall only be carried
out by suitably trained personnel in accordance
with the applicable code of practice e.g.
IEC 60079-14/EN 60079-14
Repair of this equipment shall only be carried out
by the manufacturer or in accordance with the
applicable code of practice e.g. IEC 60079-19/EN
60079-19.
Refer to certificates SIRA 09ATEX3286X, IECEx
SIR 09.0121X and CSAE 21UKEX3556X for
special conditions of safe use.
The certification of this equipment relies on the
following materials used in its construction:
Enclosure: Aluminium Pressure Die Cast Body
LM6
Through enclosure mechanism: Plastic Nylon
Zytel Injection Moulded
Sealing of enclosure and mechanism: O-ring
Acrylonitrile-Butadiene Rubber
Potting Compound of resistors where used:
Epoxy Resin
If the equipment is likely to come into contact with
aggressive
substances,
then
it
is
the
responsibility of the user to take suitable
precautions that prevent it from being adversely
affected, thus ensuring that the type of protection
is not compromised.
"Aggressive substances" - e.g. acidic liquids or
gases that may attack metals, or solvents that
may affect polymeric materials.
"Suitable precautions" - e.g. regular checks as
part of routine inspections or establishing from the
material's data sheet that it is resistant to specific
chemicals.
5)
Call Point Location and Mounting
The location of the call point should enable ease
of access for operation and testing. The unit
Sheet 1 of 3
should be mounted using the 4 off fixing holes
which will accept up to M4 sized fixings.
View of base unit showing fixing centers.
To gain access to the mounting holes in the base
the front cover must be removed. This is achieved
by removing the 4 off M4 cap head bolts holding on
the cover.
Once the screws are removed the cover will hang
down out of the way to gain access to the Ex e
terminal block, the internal earth terminal and
mounting hole recesses.
6)
Earthing
The unit has both internal and external earth
terminals.
It is recommended that a cable crimp lug is used
on the earth wires.
The internal earth wire is placed under a earth
clamp which will stop the cable twisting. This is
secured by an M4 screw and spring washer.
sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S BExCP3C-BG

  • Page 1 Through enclosure mechanism: Plastic Nylon Introduction IECEx SIR 09.0121X Zytel Injection Moulded The BExCP3C-BG is a break glass manual call CSAE 21UKEX3556X point which is certified to the European and Sealing of enclosure and mechanism: O-ring International Gas and Dust standards. The unit...
  • Page 2 Safety terminal key) this will than allow the glass to fit back into the E2S recommends a minimum resistor value enclosures, you are only permitted to connect one pocket it sits in, resting on the pivot point and test of 100 ohms for a Series device and 180...
  • Page 3 Proof Test Interval Up to 1 year European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 Document D150-00-055-IS Issue 2 11-08-22 Sheet 3 of 3 www.e2s.com Fax +44 (0)208 740 4200...
  • Page 4 Zener Diode ExxxZ SxxxZ DEVICE POLARITY DETAIL ADDED ; CODING UPDATED D.A.H - 21-12-2021 Contact E2S sales to discuss options. BExCP3B/C/D/E - PT L or C SINGLE SWITCH WITH EOL DEVICE SINGLE SWITCH WITH EOL DEVICE CONFIG. 1 SINGLE SWITCH WITH SERIES DEVICE CONFIG.
  • Page 5: Eu Declaration Of Conformity

    The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU. E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-007_Issue_N (BExCP3) - Page 1 of 2 - QAF_252_Issue_5...
  • Page 6 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC-007_Issue_N Quality Assurance Manager Date and Place of Issue: London, 23/12/2020 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-007_Issue_N (BExCP3) - Page 2 of 2 - QAF_252_Issue_5...
  • Page 7 The product and all the components contained within it are free from substances of very high concern. E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-093_Issue_A (BExCP3) - Page 1 of 2 - QAF_252_Issue_5...
  • Page 8 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC-093_Issue_A Quality Assurance Manager Date and Place of Issue: London, 24/02/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-093_Issue_A (BExCP3) - Page 2 of 2 - QAF_252_Issue_5...

This manual is also suitable for:

Bexcp3b-bgBexcp3d-bgBexcp3e-bg