Parameters - Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Parameters/address space

5.1 Parameters

5.1
Parameters
Introduction
The parameters of the F-DI 16×24VDC HA are described below.
The parameters of the I/O module are displayed in the "Properties" dialog of the module in HW
Config on the following tabs:
• "Parameters" tab
• "Redundancy" tab
This tab is displayed for redundant I/O modules.
• "Time stamp" tab
This tab is used to configure the time stamp for the I/O module.
For more information on time stamping, refer to the function manual "SIMATIC; Process
Control System PCS 7; High-precision Time Stamping with ET 200SP HA
support.industry.siemens.com/cs/ww/en/view/109772337)".
Parameters in the "Parameters" tab
You have the following setting options:
Parameter
F-parameters
F_source_address
F_destination_address
F_monitoring time (ms)
Cross-channel
Channel activated
Diagnostics: Wire break
Input delay (ms)
20
Value range
1 (display only) *a)
1 to 65534
10 ms to 65535 ms
Enabled
Disabled
Enabled
Disabled
0.4 ms
0.8 ms
1.6 ms
3.2 ms
6.4 ms
10.0 ms
12.8 ms
20 ms
The value of the input delay depends
on the time for the short-circuit test
of the sensor and the discrepancy
time.
Default value
Parameter
reassign‐
ment in RUN
1
No
Preset
No
automatically *b)
2500
No
Enabled
No
Disabled
No
3.2 ms
No
Equipment Manual, 08/2021, A5E45647528-AD
(https://
Scope
Module
Module
Module
All channels
All channels
All channels
F-DI 16x24VDC HA