Install Cisco NCS 1010 Modules
Figure 4: Rating Label for DC Power
DC power ratings:
• Input: 48-60Vdc, 30A.
• DC output: +12V, 87.5A Max. +12Vsb, 3A Max. Total output power must not exceed 1050W.
Procedure
Step 1
Verify that the correct fuse panel is installed in the top mounting space.
Step 2
Measure and cut the cables as required to reach Cisco NCS 1010 from the fuse panel.
Step 3
Connect the office battery and return cables according to the fuse panel engineering specifications.
Step 4
Attach the DC power cable to the cable connector in the DC power module.
Use the CAB-48DC-40A-8AWG or NCS1010-DC-CBL-ET= cable. We recommend using
NCS1010-DC-CBL-ET= with the ETSI 300-mm cabinet to remain compliant with the 300-mm footprint. See
Power Cable
Note
Specifications.
Ensure to ground the green colored cable.
Connect DC Power to Cisco NCS 1010
Install Cisco NCS 1010 Modules