hit counter script
Siemens SIMATIC ET 200SP HA Equipment Manual
Hide thumbs Also See for SIMATIC ET 200SP HA:

Advertisement

Quick Links

SIMATIC
ET 200SP HA
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual
6DL1132-6HD50-0PK0
6DL1132-6HD50-0EK0
07/2022
A5E39389042-AF
Security information
Preface
2D Matrix code (QR code /
EAN code)
Product overview
Terminal
Parameters
Displays and interrupts
Technical specifications
Drivers, parameters,
diagnostics messages and
address space
1
2
3
4
5
6
7
8
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP HA

  • Page 1 Security information Preface 2D Matrix code (QR code / EAN code) SIMATIC Product overview ET 200SP HA RQ 4x120VDC-230VAC/5A CO HA Terminal Parameters Equipment Manual Displays and interrupts Technical specifications Drivers, parameters, diagnostics messages and address space 6DL1132-6HD50-0PK0 6DL1132-6HD50-0EK0 07/2022 A5E39389042-AF...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Security information..........................5 Preface ..............................7 2D Matrix code (QR code / EAN code) ....................9 Product overview ..........................11 I/O module......................... 11 Accessories ........................12 Output disable switch ......................13 Pulling the I/O module in runtime..................13 Terminal blocks........................
  • Page 4 Table of contents Parameter assignment and structure of the module/channel parameters......34 Diagnostics messages and maintenance events ..............36 Maintenance events......................37 Address space ........................37 Tables Table 8-1 Switching capacity and lifetime of the relay contacts .............. 32 Figures Figure A-1 Structure byte x to x+1 for the channels 0 to 3.................
  • Page 5: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
  • Page 6 Security information RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 7: Preface

    Preface Validity of the documentation This equipment manual describes the following I/O modules: System family I/O module Article No. SIMATIC Distributed I/O System ET 200SP RQ 4x120VDC-230VAC/5A CO 6DL1132-6HD50-0PK0 SIMATIC Distributed I/O System ET 200SP RQ 4x120VDC-230VAC/5A CO 6DL1132-6HD50-0EK0 It supplements the ET 200SP HA / ET 200SP HA Distributed I/O system system manual. Functions that generally relate to the system are described in this manual.
  • Page 8 Preface RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 9: Matrix Code (Qr Code / Ean Code)

    The 2D matrix code on the product is a coded representation of the product-specific article number. Access to product-related information For reading the 2D matrix code, SIEMENS offers an app for mobile use. Information about the app and the download can be found on the Internet: "Mobile use via app (https://support.industry.siemens.com/cs/ww/en/sc/2067)".
  • Page 10 2D Matrix code (QR code / EAN code) RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 11: Product Overview

    Product overview I/O module Definition The RQ 4x120VDC-230VAC/5A CO HA I/O module is a digital output module with 4 power outputs for process control. In addition to the technical specifications, this module has the following properties: NOTICE I/O modules with relay contacts •...
  • Page 12: Accessories

    Product overview 4.2 Accessories Description The I/O module consists of the following components: 4x 12 0V DC ..2 30 VA C/ 5A CO DI AG M T 1 .0 1P 1 L+ 24 VD C M 2P 1 L+ 24 1P 2 VD C M 2P 2...
  • Page 13: Output Disable Switch

    Product overview 4.4 Pulling the I/O module in runtime Description The following accessories are available: • Labeling strips • Color-coded labels • Reference identification label • Shield connector • Terminal blocks Output disable switch Definition The output disable switch switches the NO contact of the I/O module load-free. NOTICE Dangerous plant conditions possible (disconnect the load) If you want to pull the I/O module in runtime, you have to press the output disable switch for...
  • Page 14: Terminal Blocks

    Product overview 4.5 Terminal blocks The LED DIAG flashes red, the LED MT lights up yellow and the I/O module generates a diagnostics message. Status and error display (Page 23) Terminal blocks Definition The terminal blocks provide the process terminals (push-in terminals) for components to be connected such as devices.
  • Page 15: Terminal

    Terminal Terminal assignment Definition The pin assignment provides information about the arrangement and marking of the connections when wiring a connector. WARNING Risk of death or serious injury from electric shock! Prior to working on the system and module, always disconnect them from the power supply. NOTICE External fuse for relay outputs The outputs have to be protected with an external safety fuse with a maximum trip current of...
  • Page 16: Sample Connection Scheme

    Terminal 5.2 Sample connection scheme Description The pin assignment is structured as follows: Terminal Assignment Terminal Assignment Explanations : Common contact : NO : NC 1P1: Supply voltage L+ of the voltage bus 1P 2P1: Supply voltage L+ of the voltage bus 2P 1P2: Ground reference of the voltage bus 1P 2P2: Ground reference of the voltage bus 2P 1 .0...
  • Page 17: Schematic Circuit Diagram

    Terminal 5.3 Schematic circuit diagram Schematic circuit diagram Definition A block diagram contains the schematic representation of individual function blocks. Description The circuit diagram for the I/O module is structured as follows: RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 18 Terminal 5.3 Schematic circuit diagram RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 19: Parameters

    Parameters Parameter types Definition You define and thereby influence the functions supported by the module operation of the I/O module via the parameter types. Module/channel parameters Definition Module/channel parameters are specific parameters whose configuration can affect the entire module or channel. Description The following module/channel parameters are available: Parameters...
  • Page 20: Explanation Of The Module/Channel Parameters

    Parameters 6.3 Explanation of the module/channel parameters Explanation of the module/channel parameters 6.3.1 Diagnostics, Missing supply voltage L+ Definition Enabling of the diagnostics for missing or insufficient supply voltage L+. 6.3.2 Channel activated Definition Specifies whether a channel is activated or deactivated. 6.3.3 Reaction to CPU STOP Definition...
  • Page 21: Potential Group

    Parameters 6.3 Explanation of the module/channel parameters 6.3.5 Potential group Definition A potential group consists of a group of directly adjacent I/O modules within an ET 200SP HA station that are supplied via a common supply voltage. Description A potential group is built up from left to right by using terminal blocks. A new potential group starts on the left side with a light gray terminal block, via which the supply voltage for the potential group is fed in.
  • Page 22 Parameters 6.3 Explanation of the module/channel parameters RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 23: Displays And Interrupts

    Displays and interrupts Status and error display Definition The LED displays are status and error indicators. Diagnostics messages and maintenance events, as well as their possible causes or solutions are described in the diagnostics messages and maintenance events. AUTOHOTSPOT Description The following figure explains the LED displays of the I/O module.
  • Page 24: Leds

    Displays and interrupts 7.2 LEDs LEDs 7.2.1 DIAG LED Definition The DIAG LED provides you diagnostic information. Description The diagnostic display of the DIAG LED is as follows: DIAG LED Meaning The power supply of the ET 200SP HA is disrupted or switched off. Module is not configured.
  • Page 25: Channel Status Led

    Displays and interrupts 7.3 Interrupts 7.2.3 Channel status LED Definition The channel status LED gives you status information about the channels. Description The channel status and channel fault LEDs indicate the following: Channel status Meaning Process signal = 0 or channel disabled Process signal = 1 and channel enabled 7.2.4 PWR LED...
  • Page 26 Displays and interrupts 7.3 Interrupts Description The I/O module generates a diagnostics interrupt for the following events: • Channel/component temporarily unavailable • Parameter assignment error • Supply voltage missing • Retentive memory in carrier module defective • Retentive memory in the terminal block defective •...
  • Page 27: Technical Specifications

    Technical specifications Technical specifications of the RQ 4x120VDC-230VAC/5A CO HA Article number 6DL1132-6HD50-0PK0 General information Product type designation RQ 4x120 V UC ... 230 V AC/5 A CO HA Firmware version V1.0 • FW update possible Usable terminal block TB type K0 Color code for module-specific color identifica‐...
  • Page 28 Technical specifications Article number 6DL1132-6HD50-0PK0 yes; 6 A, see data in manual • external protection for relay outputs Switching capacity of contacts 2 A; 2 A (24 V DC), 0.5 A (60 V DC), 0.1 A (120 V DC) – with inductive load, max. –...
  • Page 29 Technical specifications Article number 6DL1132-6HD50-0PK0 3 000 m due to converter type used • Ambient air temperature-barometric pres‐ sure-altitude Dimensions Height 115 mm Depth 138 mm Weights Weight, approx. 162 g RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 30 Technical specifications Article number 6DL1132-6HD50-0EK0 General information Firmware version V1.0 • FW update possible Usable terminal block TB type K0 Color code for module-specific color identifica‐ CC40 tion plate Engineering with V8.0 • SPPA-T3000 can be configured/integrated from version Redundancy •...
  • Page 31 Technical specifications Article number 6DL1132-6HD50-0EK0 Interrupts/diagnostics/status information Diagnostics function Diagnoses • Monitoring the supply voltage – parameterizable Diagnostics indication LED Yes; Yellow LED • MAINT LED Yes; green PWR LED • Monitoring of the supply voltage (PWR-LED) Yes; green LED •...
  • Page 32: Switching Cycles

    Technical specifications 8.1 Switching cycles Switching cycles Switching capacity and lifetime of the contacts With an external protective circuit, the contacts will last longer than specified in the table. This table shows the switching capacity and lifetime of the relay contacts: Table 8-1 Switching capacity and lifetime of the relay contacts Resistive load...
  • Page 33: Drivers, Parameters, Diagnostics Messages And Address Space

    Drivers, parameters, diagnostics messages and address space Parameter assignment Parameter assignment in the user program You can reconfigure individual channels of the module in RUN without this having an effect on the other channels. Changing parameters in RUN The "WRREC" instruction is used to transfer the parameters to the module using data record 128. Output parameter STATUS If errors occur when transferring parameters with the "WRREC"...
  • Page 34: Parameter Assignment And Structure Of The Module/Channel Parameters

    Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Valid parameters Only the values specified in the following are permitted. Values that are not listed are rejected by the module. Every parameter data record is checked by the module. If an incorrect parameter is detected, the entire data record is rejected and the parameters of the module remain unchanged.
  • Page 35 Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the structure of the header information and module parameters. Channel parameters Each channel parameter block contains the cable parameters for the digital output (2 bytes). RQ 4x120VDC-230VAC/5A CO HA Equipment Manual, 07/2022, A5E39389042-AF...
  • Page 36: Diagnostics Messages And Maintenance Events

    Drivers, parameters, diagnostics messages and address space A.3 Diagnostics messages and maintenance events The following figure shows the configuration of the channel parameters for data record 128. x = 12 + (channel number * 2); with channel number 0…3 Any unused bits and bits or bytes marked with "reserved" must be set to zero. Activate a channel parameter by setting the corresponding bit to "1"...
  • Page 37: Maintenance Events

    Drivers, parameters, diagnostics messages and address space A.5 Address space Diagnostic Error code Assignment Meaning Solution alarm Retentive memo‐ Module An error in the RAM on the carrier Replace carrier module ry in carrier mod‐ module was detected during start-up ule defective Retentive memo‐...
  • Page 38 Drivers, parameters, diagnostics messages and address space A.5 Address space Address space The following figure shows the mapping of the address space of the RQ 4x120VDC-230VAC/5A CO HA. QB/IB QDQ3 QDQ2 QDQ1 QDQ0 Evaluating value status There is a bit value status for each digital output in the input address space. Irrespective of the diagnostics enables, each value status (each QI bit) provides information on the validity of the corresponding process value.