SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS September 2016 No. OCH625 SERVICE MANUAL Indoor unit [Model Name] [Service Ref.] PLA-ZP35EA.UK PLA-ZP35EA Notes: • This manual describes ser- vice data of the indoor units PLA-ZP50EA.UK PLA-ZP50EA only. • RoHS compliant products have <G>...
SAFETY PRECAUTION 2-1. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuits must be disconnected. 2-2. CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilising refrigerant R410A Use a vacuum pump with a reverse flow check Use new refrigerant pipes. valve.
Unit Electonic weighing scale [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. Tool name Specifications Gauge manifold · Only for R410A · Use the existing fitting specifications . (UNF1/2) · Use high-tension side pressure of 5.3MPa·G or over. Charge hose ·...
Page 5
3-2. WIRELESS REMOTE CONTROLLER (Option) Transmission area Not available Remote controller display Battery replacement indicator Set Temperature buttons OFF/ON button Mode button (Changes operation mode) Fan Speed button (Changes fan speed) Airflow button (Changes up/down airflow direction) i-see button Timer ON button Menu button Timer OFF button SET/SEND button...
Page 6
3-3. Wired remote controller (Option) PAR-32MAA The functions which can be used are restricted according to each model. The main display can be displayed in 2 different modes: "Full" and "Basic." Display The initial setting is "Full." 1 Operation mode Indoor unit operation mode appears here.
Page 7
Menu structure Press the button. MENU Main menu Move the cursor to the desired item with the buttons, and press the button. SELECT Vane · Louver · Vent. (Lossnay) High power Timer ON/OFF timer Auto-OFF timer Weekly timer Restriction Temp. range Operation lock Energy saving Auto return...
Page 8
Setting and display items Setting details Vane · Louver · Vent. Use to set the vane angle. • Select a desired vane setting from 5 different settings. (Lossnay) Use to turn ON/OFF the louver. • Select a desired setting from "ON" and "OFF." Use to set the amount of ventilation.
SPECIFICATIONS Service Ref. PLA-ZP35EA.UK Mode Cooling Heating Power supply (phase, cycle, voltage) Single phase, 50Hz, 230 V Input 0.03 0.03 Running current 0.21 0.19 External finish (Grille) Munsell 1.0Y 9.2/0.2 Heat exchanger Plate fin coil Fan (drive) o No. Turbo fan (direct) o 1 Fan motor output 0.050...
Page 10
Service Ref. PLA-ZP71EA.UK Mode Cooling Heating Power supply (phase, cycle, voltage) Single phase, 50Hz, 230 V Input 0.05 0.05 Running current 0.34 0.32 External finish (Grille) Munsell 1.0Y 9.2/0.2 Heat exchanger Plate fin coil Fan (drive) o No. Turbo fan (direct) o 1 Fan motor output 0.120 Airflow (Low-Medium2-Medium1-High)
Page 11
Service Ref. PLA-ZP140EA.UK Mode Cooling Heating Power supply (phase, cycle, voltage) Single phase, 50Hz, 230 V Input 0.10 0.10 Running current 0.66 0.64 External finish (Grille) Munsell 1.0Y 9.2/0.2 Heat exchanger Plate fin coil Fan(drive) o No. Turbo fan (direct) o 1 Fan motor output 0.120 Airflow (Low-Medium2-Medium1-High)
NOISE CRITERION CURVES PLA-ZP35EA.UK PLA-ZP50EA.UK NOTCH SPL(dB) LINE NOTCH SPL(dB) LINE High High PLA-ZP60EA.UK Medium1 Medium1 Medium2 Medium2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20...
Page 13
PLA-ZP140EA.UK PLA-ZP125EA.UK NOTCH SPL(dB) LINE NOTCH SPL(dB) LINE High High Medium1 Medium1 Medium2 Medium2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20 CONTINUOUS CONTINUOUS NOISE NOISE 1000 2000 4000...
TROUBLESHOOTING 9-1. TROUBLESHOOTING <Check code displayed by self-diagnosis and actions to be taken for service (summary)> Present and past check codes are logged, and they can be displayed on the wired remote controller or controller board of out- door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa- rized in the table below.
Page 18
Refer to the following tables for details on the check codes. [Output pattern A] Beeper sounds Beep Beep Beep Beep Beep Beep Beep 1 st 2 nd 3 rd n th 1 st 2 nd OPERATION · · · Repeated INDICATOR lamp blinking pattern...
Page 19
• If the unit cannot be operated properly after the test run, refer to the following table to find out the cause. Symptom Cause Wired remote controller • For about 2 minutes after power-on,operation of the For about 2 minutes after power-on PLEASE WAIT remote controller is not possible due to system startup.
Page 20
Note: Errors to be detected in outdoor unit, such as codes starting with F, U or E (excluding E0 to E7), are not covered in this document. 9-3. SELF-DIAGNOSIS ACTION TABLE Please refer to the outdoor unit's service manual for the details. Abnormal point and detection method Countermeasure Check code...
Page 21
Abnormal point and detection method Countermeasure Check code Cause Drain pump lock protection operation 1 Malfunction of drain pump 1 Check if drain pump works. 2 Clogged drain pump 1 Error postponement, if drain pump stops 2 Check if drain pump works. 3 Contact failure of connector for 5 seconds continuously while drain 3 Check contact failure of connector CNP...
Page 22
Abnormal point and detection method Countermeasure Check code Cause Pipe temperature thermistor/ 1 Defective thermistor Condenser-Evaporator (TH5) characteristics 1–3 Check resistance value of thermistor. For characteristics, refer to (P1) above. 1 The unit is in 3-minute resume protec- 2 Contact failure of connector 2 Check contact failure of connector (CN44) tion mode if short/open of thermistor is (CN44) on the indoor controller...
Page 23
Abnormal point and detection method Countermeasure Check code Cause Indoor/outdoor unit communication error 1 Contact failure, short circuit or, Note: Check LED display on the outdoor control (Signal receiving error) miswiring (converse wiring) of circuit board. (Connect A-control service 1 Abnormal if indoor controller board tool, PAC-SK52ST.) indoor/outdoor unit connecting cannot receive any signal normally for 6...
Page 24
Abnormal point and detection method Countermeasure Check code Cause Fan motor trouble 1 Defective fan motor 12 Refer to "9-6-2. DC Fan Motor (Fan Motor/ 2 Defective indoor controller board Indoor Controller Board".) Abnormal refrigerant circuit 1 When this error occurs, be sure to replace 1 Abnormal operation of 4-way During Cooling, Dry, or Auto Cooling the 4-way valve.
Page 25
9-4. TROUBLESHOOTING OF PROBLEMS Note: Refer to the outdoor unit's service manual for the detail of remote controller. Phenomena Cause Countermeasure (1) LED2 on indoor controller board • When LED1 on indoor controller board is also off. is off. 1 Power supply of rated voltage is not supplied to out- 1 Check the voltage of outdoor power supply terminal block (L, N) or (L door unit.
Page 26
Note: Refer to the outdoor unit's service manual for the detail of remote controller. Phenomena Cause Countermeasure (2) LED2 on indoor controller board • When LED1 on indoor controller board is also blinking. Check indoor/outdoor unit connecting wire is blinking. Connection failure of indoor/outdoor unit connecting for connection failure.
Page 27
9-5. EMERGENCY OPERATION 9-5-1. When wireless remote controller fails or its battery is exhausted When the remote controller cannot be used When the batteries of the remote controller run out or the remote control- ler malfunctions, the emergency operation can be done using the emer- gency buttons on the grille.
Page 28
9-6. HOW TO CHECK THE PARTS PLA-ZP35EA.UK PLA-ZP50EA.UK PLA-ZP60EA.UK PLA-ZP71EA.UK PLA-ZP100EA.UK PLA-ZP125EA.UK PLA-ZP140EA.UK Parts name Check method and criterion Room temperature Measure the resistance with a tester. thermistor (TH1) (Parts temperature 10 to 30°C) Pipe temperature Abnormal Normal thermistor/liquid (TH2) Opened or short-circuited 4.3 to 9.6 k"...
Page 29
9-6-1. Thermistor < Thermistor for lower temperature > <Thermistor Characteristic Graph> Room temperature thermistor (TH1) Thermistor for Pipe temperature thermistor/liquid (TH2) lower temperature Condenser/evaporator temperature thermistor (TH5) Thermistor R =15k" ± 3% Fixed number of B=3480 ± 2% Rt=15exp { 3480( 273+t 15 k"...
Page 30
9-7. TEST POINT DIAGRAM Indoor controller board PLA-ZP35EA.UK PLA-ZP50EA.UK PLA-ZP60EA.UK PLA-ZP71EA.UK PLA-ZP100EA.UK PLA-ZP125EA.UK PLA-ZP140EA.UK CN5Y Vane motor (MV) i-see Sensor motor (MT) 12 V pulse output Connect to wired remote controller 12 V pulse output 10.4-14.6 V DC Model selection...
SPECIAL FUNCTION 10-1. OPERATION (AUTO DESCENDING PANEL: PLP-6EAJ/PLP-6EAJE) (1) Normal operation String 1b 1 UP/DOWN UP/DOWN UP/DOWN Air intake grille is raised/lowered by Machine 1 Machine 2 commands of UP and DOWN. Air intake grille does not move under the state of no-load detection or obstacle detection.
Page 33
10-2. ELECTRICAL CIRCUIT (Controller board and wiring diagram (Panel)) 10-2-1 DIP SW LED4 LED2 [ LEGEND ] SYMBOL NAME [EMERGENCY OPERATION] ELEVATION PANEL CONTROLLER BOARD 1. If the wireless remote controller for ELEVATION PANEL is faulty or lost, operation LED ORANGE LED2 will be possible using the emergency up/down switch at the wireless signal receiver (INTAKE GRILLE CONDITION (See table *1))
Page 34
10-3. TROUBLESHOOTING • Check the following points. Problem Possible Reason Corrective Action Intake grille does not function Air-conditioner is running. Stop running the air-conditioner and try again. After recovering from power failure, try again. Power failure. with operation of the remote Batteries are not inserted into the wireless remote Install or replace the battery.
Page 35
10-4. ROTATION FUNCTION (AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION) 10-4-1. Operation (1) Rotation function (and Back-up function) • Outline of functions · Main and sub unit operate alternately according to the interval of rotation setting. Note: Main and sub unit should be set by refrigerant address. (Outdoor DIP switch setting) Refrigerant address "00"...
Page 36
• System constraint · This function is available only in cooling mode. Ex.) Set temp. by R/C = 20: [2nd stage cut-in function]··· Request code number "322–324" Set point = 26: When request code number is “323”. Room temp. ] Set point Room temp.
Page 37
(2) Rotation and back up operation PAR-32MAA Press the button. Main Main menu Maintenance Initial setting Service Select "Service" with the [Cursor] buttons ( ) or the [Page] buttons ( ), and press the button. Main display: Cursor Page Enter the current maintenance password (4 numerical digits). Service menu •...
DISASSEMBLY PROCEDURE PLA-ZP35EA.UK PLA-ZP50EA.UK PLA-ZP60EA.UK PLA-ZP71EA.UK PLA-ZP100EA.UK PLA-ZP125EA.UK PLA-ZP140EA.UK Be careful when removing heavy parts. OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 1. Removing the filter Knob Air intake grille Figure 1 (1) Slide the knob of air intake grille toward the arrow to Grille open the air intake grille.
Page 39
OPERATING PROCEDURE PHOTOS 4. Removing the room temperature thermistor (TH1) Photo 3 (1) Remove the electrical box cover. (See Photo 1 and 2.) Room temperature thermistor (TH1) (2) Disconnect the connector CN20 (Red) from the indoor Electrical box controller board. Indoor controller (3) Remove the room temperature thermistor with its board...
Page 40
Be careful when removing heavy parts. OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 6. Removing the electrical box Bell mouth fixing screws Photo 5 (1) Remove the electrical box cover (See Photo 1 and 2.) and the connectors (Refer to 5.). (2) Remove the electrical box fixing screws (M5×10: 2 screw).
Page 41
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 9. Removing the panel Figure 4 (1) Remove the electrical box fixing cover. (See Photo 1.) Corner panel (2) Disconnect the connector for vane motor (CNV: White). Screw (Refer to 5.) (3) Loosen the 4 corner panel fixing screws (tapping screw ①...
Page 42
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 11. Removing the pipe temperature/liquid thermistor (TH2) Photo 13 and condenser/evaporator temperature thermistor (TH5) (1) Remove the drain pan (Refer to 10.) and loosen the 2 clamps of the coil plate. (See Photo 9.) (2) Remove the coil plate (tapping screw 4×10: 2 screws). (3) Disconnect the pipe temperature/liquid thermistor (TH2) and condenser/evaporator temperature thermistor (TH5) from the holder.
Page 43
OPERATING PROCEDURE PHOTOS Photo 15 Do not hold this floating part 13. Removing the float switch (FS) when lifting; Doing so will cause (1) Remove the drain pan. (Refer to 10.) malfunction. (2) Loosen the clamp of the drain pump. (See Photo 14.) (3) Remove the float switch (tapping screw 4×10: 1 screw/1 hook).
Page 44