06-060 KMS0772-2472 ENG
3/17/06
2-3. Outdoor Unit
AVOID:
G
heat sources, exhaust fans, etc. (Fig. 5a)
G
damp, humid or uneven locations.
DO:
G
choose a place as cool as possible.
G
choose a place that is well ventilated.
G
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5b)
G
provide a solid base (level concrete pad, concrete
block, 6" ¥ 1'4" (15 ¥ 40 cm) beams or equal), a mini-
mum of 6" (15 cm) above ground level to reduce
humidity and protect the unit against possible water
damage and decreased service life. (Figs. 5c and 5d)
CAUTION
G
Install cushion rubber under unit's feet to reduce
vibration and noise. (Fig. 5e)
G
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
G
Install in a location where no antenna of a television
or radio exists within 10' (3 m).
2-4. Baffle Plate for the Outdoor Unit
(CLM models only)
NOTE
It is recommended to use baffle plates for models
CLM1972, CLM2472 and CLM3172. The baffle plates
are not normally required for the other models.
When the outdoor unit is installed in a position exposed
to strong wind (like seasonal winds with low air tempera-
ture in winter), baffle plates must be installed in front of
the outdoor unit. (Fig. 5f)
This unit is designed so that the fan of the outdoor unit
runs at low speed when the air conditioner is operated at
low outdoor air temperatures. When the outdoor unit is
exposed to strong wind, the system pressure drops
because of the freeze protector.
Baffle
plate
Air discharge
2:50 PM
Page 10
A solid base must not cover
the hole of the bottom plate.
12" min
Baffle
plate
Fig. 5f
NO
Hot air
Outdoor unit
Air intake
Min. 8" (20 cm)
Min.
Air discharge
Min.
4" (10 cm)
1ʼ8" (50 cm)
Fig. 5b
Drain holes
Air intake
Concrete
or equal
10
Exhaust fan
Heat source
Fig. 5a
Obstacle above
Min.
Min.
7' (2 m)
7' (2 m)
Valve
side
Min. 10"
(25 cm)
Ground
Min. 8" (20 cm)
Air intake
Fig. 5c
Anchor bolts
(4 pcs.)
Min. 6" (15 cm)
Fig. 5d
Cushion rubber
Fig. 5e