12.Specifications

GPS2436

Galaxy Power System 2436 Specifications
Input Distribution
NE100AC24ATEZ
Minimum Wire
SizeNE100AC24ATEZ
Output Current
Output Current
Nominal Cabinet
Dimensions (H x W x D)
Rectifiers
Controller
Battery Disconnect Modules
DC Distribution
1. With Galaxy Millennium Controller
Page 73
© Copyright 2023 ABB. All rights reserved.
• 125A circuit breaker per 2-shelf cabinet
• 150A circuit breaker per 3-shelf cabinet
• 25A circuit breaker per rectifier for individual feeds
• 110 / 125A circuit breaker per 1-shelf cabinet
• 2 x 110 / 125A circuit breaker per 2-shelf cabinet
• 2 x 150A circuit breaker per 3-shelf cabinet
• 50A circuit breaker per rectifier for individual feeds
• 2 gauge/35 mm
2
- 1 and 2-shelf cabinet
• 1/0 gauge/50 mm
2
- 3-shelf cabinet
• 10 gauge/6 mm
2
- per rectifier for individual feeds
• 2 gauge/35 mm
2
- 1-shelf cabinet
• 2 x 2 gauge/35 mm
2
- 2-shelf cabinet
• 2 x 1/0 gauge/50 mm
2
• 8 gauge/10 mm
2
- per rectifier for individual feeds
Cabinet Output +24V
System Output +24V
2 x Full Height
100 - 2000A
Full Height
2100 H x 600 W x 600 D mm
(82.6 H x 23.6 W x 23.6 D in.)
Units Per Initial Cabinet
Full Height
1-36
1
0-1
Maximum discharge is 1600 amps per cabinet. No distribution panels can be installed in a
rectifier only cabinet, as many distribution panels as will fit can be installed in other
cabinets.
Electrical
AC Input
- 3-shelf cabinet
100 - 2000A
Mechanical
Cabinet
GPS2436_MAN
Maximum System
2000A
Rev. 1.3