ABB Zenith ZBTS T Series Installation And Operating Instruction

ABB Zenith ZBTS T Series Installation And Operating Instruction

Bypass/isolation automatic transfer switches
Hide thumbs Also See for Zenith ZBTS T Series:
Table of Contents

Advertisement

Quick Links

I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N
Bypass/Isolation Automatic
Transfer Switches
Zenith ZBTS T-series, 100–600 A

Advertisement

Table of Contents
loading

Summary of Contents for ABB Zenith ZBTS T Series

  • Page 1 I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass/Isolation Automatic Transfer Switches Zenith ZBTS T-series, 100–600 A...
  • Page 2 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 3 équipement. with the transportation company, and no- tify your local ABB sales office. HAZARD OF EQUIPMENT Do not remove the shipping package until OVERTURNING ready to install the Bypass/Isolation Auto- When moving with a fork lift, do not re- matic Transfer Switch.
  • Page 4 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — Read these safety instructions carefully before using this product! Danger...
  • Page 5 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 1 — Installation and Operating Instruction OPER ATING INSTRUCTIONS, Bypass/Isolation ZENITH ZBTS T-SERIES...
  • Page 6 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 7: Table Of Contents

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 1 — Operating Instruction Bypass/Isolation Automatic Transfer Switches, Zenith ZBTS T-series 100–600 A...
  • Page 8 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3 HMI, menu tree 3.3.1 Start Menu 3.4 Description of Basic Functionality 3.4.1 Quick start guide of bypassing ATS...
  • Page 9 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 1 Technical Data 6.1 Technical Data of Bypass/Isolation Transfer Switches 6.1.1 I/O Contacts, Default Settings: Bypass/Isolation Automatic...
  • Page 10 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 11: Introduction

    The safe operation of your Bypass/Isola- It is used to notify of practices not related to personal injury. Failure to comply with these tion Automatic Transfer Switch is ABB’s instructions may result in product damage. focus. Proper storage, installation, opera-...
  • Page 12: Warranty

    ABB representative for Non-US war- hardware and software systems. ranty terms and conditions. ABB Zenith assumes no obligation of no- For support in the United States, contact tice to holders of this document with re- service team at: +1 800 637 1738 or spect to changes subsequently made.
  • Page 13: Product Specification

    Strict procedures ensure first class product quality. Product Rating / Applicable Standards For UL 1008 ‘withstand’ and ‘close on short circuit’ ratings, refer to ABB publica- tion number 1SCC303020C0201. Product Serial Number Please have the serial number available when communicating about the Bypass/ Isolation Automatic Transfer Switch.
  • Page 14: Definitions

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 1.4 Definitions Automatic Transfer Switches Source 1, relate to a Normal Power Source...
  • Page 15: Product Overview

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 2. Product Overview Bypass/Isolation Automatic Transfer Switches, Zenith ZBTS T-series, from 100 A up to 600 A, are used to provide a continuous source of power for critical loads by automatically transferring from Source 1 power to Source 2...
  • Page 16 The up- Warning Due to hazardous voltage and current, ABB per switch module, Bypass switch, is recommends that ABB certified technician or available in either a fixed or draw-out ver- qualified electrician perform the installation and maintenance.
  • Page 17: General Overview

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 2.1 General Overview Upper door for Bypass compartment Ground Terminal Bypass switch I/O connections...
  • Page 18 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Operation instruction Place for racking in/out mechanism, in case the Bypass switch is also a draw-out version...
  • Page 19: Main And Control Connections

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 2.2 Main and Control Connections 2.2.1 Main Connections The cable lugs for Load, Source 1 and Source 2 are situated on the left side of...
  • Page 20: Interlocks

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N The upper switch is the Bypass switch. It can be fixed or draw-out version.
  • Page 21: Hmi

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 2.3 HMI HMIs are the control interfaces (Human touch screen for both switches Bypass Machine Interface), available as level 4 for and ATS.
  • Page 22: Bypass And Ats Switches, Features

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 2.4 Bypass and ATS Switches, Features Features Level 4 controls (TOUCH)
  • Page 23 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Features Level 4 controls (TOUCH) LOAD AUTO Override momentary...
  • Page 24 For applications Mains - Mains Mains - Generator Contact ABB for applications with smaller than 20 kVA gensets Includes support for redundant module — Table 2.1 ATS feature comparison, main features - but not limited to - in the table above...
  • Page 25: Operating

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 3. Operating — 3.1 LED Functionality in HMIs LED functionality in HMIs is similar for both Bypass and ATS switches.
  • Page 26 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass Lamp Auto load...
  • Page 27: Using The Control Interface Hmi

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 3.2 Using the Control Interface HMI 3.2.1 Keypad Keypad functionality in HMIs is similar for both Bypass and ATS switches...
  • Page 28: Hmi, Menu Tree

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 3.3 HMI, menu tree Password The small icons in Switch Overview -pages...
  • Page 29 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Alarm List To Define the Home Page Alarm List 11:06 Switch Overview...
  • Page 30: Start Menu

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1 Start Menu Overviews Analog Meters Switch Overview...
  • Page 31 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 3.3.1.2 Bypass System Overview 10:55 Bypass System Overview LOAD AUTO...
  • Page 32 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.3 Main Menu Overviews Analog Meters Overviews...
  • Page 33 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Operation *Default Alarm Reset Reset any active switch control alarms (open I failure, close I failure, open II failure, close II failure) Bypass Time Delay Bypass any currently running time delay...
  • Page 34 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.4 Analog Meters Overviews Analog Meters Switch Overview...
  • Page 35: Description Of Basic Functionality

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 3.4 Description of Basic Functionality The system provides the ability to with- Both ATS and Bypass switches have a draw the ATS for test and / or mainte-...
  • Page 36: Quick Start Guide Of Bypassing Ats

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.1 Quick start guide of bypassing ATS STEP 1: Match Bypass power source with ATS Bypass/HMI ATS/HMI...
  • Page 37 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 ATS/HMI LOAD CHECK! STEP 4: Racking out to ISOLATED location ATS/HMI 05:17 Bypass System Overview...
  • Page 38: How To Draw-Out The Switch To Test And Isolated Locations - Bypassing The Ats Switch

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.2 How to draw-out the switch to If the power supply of ATS is Source 2 (the TEST and ISOLATED locations –...
  • Page 39 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 3.4.2.3 Step 3: Operate ATS to TEST Location with the Racking in/out Tool Warning ATS and Bypass switch "OFF"...
  • Page 40: Mechanism To Rack Out The Switch

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.3 How to use the Racking out mechanism to rack out the Switch This guide applies to switches with a Racking out mechanism.
  • Page 41 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 • If the Bypass switch is in the CON- 05:10 NECTED location but in the OFF posi- Bypass System Overview...
  • Page 42 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N When the TEST location is reached and When the ATS is racked out to the ISO- the "Racking in/out mechanism"...
  • Page 43 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 In CONNECTED location In CONNECTED location, Push button pushed, Push button returns, TEST location reached, Racking in/out tool inserted, ready to start rotation Push button pushed again, Racking in/out tool...
  • Page 44 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N HMI of Bypass: HMI of ATS: Page “Bypass System Overview”...
  • Page 45: To Reconnect Ats Switch

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 3.4.4 To Reconnect ATS Switch Push the ATS unit back to the bottom Reconnecting the ATS switch after main- and connect HMI cable back to the...
  • Page 46 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N cation. You can operate the ATS to OFF 00:14 position by pushing the button of the ATS Bypass System Overview...
  • Page 47 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Operate Bypass switch to OFF position.
  • Page 48 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 49: Electronic Accessories

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 4. Electronic Accessories NOTE! It is still possible to add two pieces of Ekip modules to the fixed Bypass switch Warning Hazardous voltage may be present within the...
  • Page 50: Auxiliary Power Supply Module Oxea1

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.1 Auxiliary Power Supply Module OXEA1 The auxiliary power supply module, type ferrule;...
  • Page 51: Ekip Supply Module

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 4.2 Ekip Supply Module 4.2.2 Signallings The Ekip Supply is a power supply acces- sory module.
  • Page 52: Ekip Signalling 2K -Module

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.3 Ekip Signalling 2K -module 4.3.1 Electrical characteristics of The Ekip Signalling 2K-3 is a signalling ac-...
  • Page 53 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Settings (*Default) Description Modules (Optional modules) Ekip Signalling 2K -3 I 11/12, I 21/22, I 31/32...
  • Page 54 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Settings (*Default) Description Modules (Optional modules) (continued) O 11/12, O 21/22,...
  • Page 55 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Test Modules (Optional modules) Ekip Signalling 2K-1 / -2 / Auto Test —...
  • Page 56: Signals And Inputs/Outputs Of Ekip Signalling 2K -Module

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 4.3.3 Signals and inputs/outputs of Green LED for signalling the physical Ekip Signalling 2K -module...
  • Page 57: Troubleshooting

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 5. Troubleshooting Warning Danger Any troubleshooting should be conducted by Hazardous voltage may be present.
  • Page 58 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Alarms, continued from previous page Message Fault Action...
  • Page 59 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Alarms, continued from previous page Message Fault Action...
  • Page 60: Warnings

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 5.2 Warnings Message Reason...
  • Page 61: Information

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 5.3 Information Message Description Invalid Date Date not set Test on Load...
  • Page 62 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 63 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 6. Technical Data 6.1 Technical Data of Bypass/Isolation Transfer Switches Bypass/Isolation Transfer Switch, Power Circuit Value Rated operational voltage U, three phase...
  • Page 64 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Automatic Transfer Switch, I/O Contacts Cabling Rating / Remark Generator start/stop...
  • Page 65 Table 6.4 Specified technical data of operating times Type peak 500 V [kA] ZS_010...060_ Iq 100 kA rms. OFA_1000 A gG 67.7 5235 OFA_1000 A aM 77.1 7155 Iq 50 kA rms. ABB T6L1000_ 57.2 16800 — Table 6.5 Rated conditional short-circuit values...
  • Page 66 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 6.1.1 I/O Contacts, Default Settings: Bypass/Isolation Automatic Transfer Switch These settings are for internal use only, these settings cannot be changed.
  • Page 67 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 6.2 Circuit Diagrams The following pages contain simplified circuit diagrams for Bypass/Isolation Au- tomatic Transfer Switch products.
  • Page 68 Pidätämme itsellemme kaikki oikeudet tähän asiakirjaan ja siihen liittyvään informaatioon. Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB.
  • Page 69 MATERIAL NORM NET WEIGHT VOLUME AREA CREATED MODIFIED APPROVED ECN DATE ECN NUMBER CONCERNING DRAWING FILE ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI maatioon. REV. TITLE (EN) DOC. NO.
  • Page 70 Pidätämme itsellemme kaikki oikeudet tähän asiakirjaan ja siihen liittyvään informaatioon. Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB.
  • Page 71 2021-06-08 Jonna Ojala 2021-06-08 Jonna Ojala 2021-06-08 Timo Jokiniemi ECN DATE ECN NUMBER CONCERNING DRAWING FILE TruBypass ZSDD040-120-1-Z31 ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI ormaatioon. REV. TITLE (EN) DOC.
  • Page 72 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 73 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — Installation Instruction Bypass/Isolation Automatic Transfer Switches Zenith ZBTS T-series 100–600 A Installation...
  • Page 74: Installation

    Make sure that all covers and barriers are installed and properly fastened. Warning Each ABB Zenith Bypass/Isolation Auto- Do not use a blower since debris may become lodged in electrical and mechanical compo- matic Transfer Switch is factory wired and nents and may cause damage and malfunction tested.
  • Page 75: Mounting / Lifting

    Not following ABB lifting guidelines may re- sult in severe injury or death. Avertissement Ne pas suivre les directives de levage d' ABB – peut entraîner de graves blessures ou la mort. Fig. 7.1 Proper lifting equipment must be used to mount...
  • Page 76: Lifting The Draw-Out Switch

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.1.2 Lifting the Draw-out Switch 4-pole draw-out switch is 70 kg / 154 lb).
  • Page 77 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 NOTE! Before carrying out any work, first NOTE! When the switch is attached back make sure that the HMI cable is removed to the track mechanism, the fixing screws...
  • Page 78: Wiring

    7.2.1 Power Connections with Screw starting work, make sure that the switch is Type Terminals (as standard) de-energized. ABB Zenith Bypass/Isolation Automatic Danger Une tension dangereuse peut être présente. Transfer Switches are supplied with UL Seul un électricien autorisé peut effectuer listed solderless screw-type terminals as l'installation électrique et l'entretien des Com-...
  • Page 79 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 OZXA-25 OZXA-412L OZXA-800E — Fig. 7.5 Screw-type terminals for the Load, Source 1 and Source 2 power connections, see Table 7.1.
  • Page 80: Power Connections With Compression Lugs (Option)

    7.2.2 Power Connections with 7.2.3 Ground Connections with Screw Compression Lugs (option) Type Terminals ABB Zenith Bypass/Isolation Automatic ABB Zenith Bypass/Isolation Automatic Transfer Switches are supplied as an op- Transfer Switches are supplied with UL tion for cable lug connections. Find the...
  • Page 81: Neutral Connections With Screw Type Terminals

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 7.2.4 Neutral Connections with Screw Type Terminals ABB Zenith Bypass/Isolation Automatic Transfer Switches are supplied with UL listed solderless screw-type neutral termi- nal as optional choice.
  • Page 82: Customer Connections, I/O Signals

    Stripping length: 12 mm, 0,47 in out switch (ATS always) Tightening torque: 0.8...1 Nm, 7.1...8.9 lb-in 7.2.7 Customer Connections, I/O Signals In ABB Zenith Bypass/Isolation Automatic 1 COMMON 1 +24V 3 CLOSES TO START 2 GND Transfer Switches there are some I/O con-...
  • Page 83: Mounting Of Accessories

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 8. Mounting of Accessories More information, see animation: Installation of accessories - TruONE™...
  • Page 84: Mounting Of The Ekip -Modules To The Fixed Bypass Switch

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 8.1.1 Mounting of the Ekip -modules to the fixed Bypass switch —...
  • Page 85: Mounting Of The Ekip -Modules To The Draw-Out Switch

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 8.1.2 Mounting of the Ekip -modules to the draw-out switch —...
  • Page 86: Wiring Routes Of I/O-Connections / Ekip -Modules Inside The Cabinet

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 8.2 Wiring routes of I/O-connections / Ekip -modules inside the cabinet Once all the afterwards added or factory...
  • Page 87 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — Maintenance Bypass/Isolation Automatic Transfer Switches Zenith ZBTS T-series 100–600 A 9.
  • Page 88: Maintenance

    HMI, and solenoid Warning mechanism, as well as accessories are Due to hazardous voltage and current, ABB recommends that ABB certified technician or readily replaceable. qualified electrician must perform the instal- lation and maintenance.
  • Page 89: Useful Tips For Service Situations

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 9.2 Useful Tips for Service Situations These operations are recommended for If the door needs to be opened for service maintenance use only.
  • Page 90: Release The Locking Solenoid

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.2.2 Release the Locking Solenoid This is not a recommended measure, but The locking solenoids are located behind if such a situation occurs during commis-...
  • Page 91: Release The Racking In/Out Push Button

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 switch via the HMI or manually by the switches own handle e.g.
  • Page 92: Ekip Signalling 10K

    There is no possibility to use multiple Further information on Ekip Signalling Ekip Signalling 10K modules (10K-2, 10K-3). 10K is available from the web site http:// www.abb.com/abblibrary/ DownloadCenter/, in particular in the manual 1SDH001318R0002. — Fig. 9.5 Ekip Signalling 10K module...
  • Page 93: Wiring

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Connections The module must be mounted on a DIN rail and connected by wiring the connec- X14: 5 (+24V DC) tors on the module.
  • Page 94 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description KS01, Pins of the output contact O S01.
  • Page 95 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 Position Description Power LED, green. The possible states are: •...
  • Page 96 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description I S01 Signalling LED of the input I S01 physical status, green.
  • Page 97: Communication Connectors

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 9.3.3 Communication Connectors The communication connectors are posi- tioned on the upper side of the module.
  • Page 98: Dip Switch Configuration When

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.3.5 DIP switch configuration when installing Ekip Signalling 10K module At installation, the module must be con- figured to communicate via Local Bus or...
  • Page 99: Auxiliary Contact Blocks

    Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB. The auxiliary contact blocks in both Source 2...
  • Page 100: Heater

    Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 9.5 Heater Heater is used for prevention of conden- Thermostat is factory set at 10 °C (50 °F)
  • Page 101: Meter

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — 9.6 Meter The multifunction power meter is an ac- Features: cessory, it is designed to be used in elec- •...
  • Page 102: Protection Devices

    Fuse Disconnector is needed for OVR factory. Surge Protection Device. The recom- mended type is: 9.7.1 Surge Protection Device OVR • ABB Fuse Disconnector E93/50 OVR range is designed to prevent electri- - 2CSM277962R1801 E93/50 cal systems and equipment against tran-...
  • Page 103: Integrated Spd, Type Tpme

    3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 9.7.3 Integrated SPD, Type TPME_ 9.7.3.1 Other Features of TPME_ •...
  • Page 104 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 105 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1 — Dimension drawings Bypass/Isolation Automatic Transfer Switches Zenith ZBTS T-series 100–600 A 10.
  • Page 106 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 10.
  • Page 107 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1...
  • Page 108 Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Fig. 10.2 ZENITH ZBTS T-Series 100–600 A, dimension drawings, cabinet inside...
  • Page 109 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1...
  • Page 110 With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of infor- mation in this document.
  • Page 111 3 4 Z B T S _ 1 0 0 – 6 0 0 A r e v. B / 1 S C C 3 0 3 0 4 4 M 0 2 0 1...
  • Page 112 — Contact us ABB Zenith Controls, Inc. 305 Gregson Drive Cary, NC 27511 24-hour support: ABB Technical Services +1 (800) 637-1738 epis.pqservice@abb.com abb.com/lowvoltage © Copyright 2023 ABB. All rights reserved. Specifications subject to change without notice.