Device Specifications
I/O Modules > Digital I/O Modules
Remarks:
1
)
2
)
3
)
4
)
State LEDs
LED
Technical Data
The System Data of AC500-eCo apply
on page 1192
Only additional details are therefore documented below.
Parameter
Process supply voltage UP
Current consumption from 24 VDC power
supply at the L+/UP and M/ZP terminals of the
CPU/bus module
228
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
With "Device" the following allocation applies:
31 = module itself, 1...10 = decentralized communication interface module
1...10, ADR = hardware address (e. g. of the DC551-CS31)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or PNIO = module type (2 = DO); COM1/COM2: 1...10 =
expansion 1...10
In case of module errors, with channel "31 = Module itself" is output.
Outputs
O0...O7
Connections
Rated value
Current consumption via UP terminal
Max. ripple
Inrush current
Protection against reversed voltage
Rated protection fuse for UP
3ADR010121, 13, en_US
State
Color
Digital output Yellow
Ä Chapter 2.5.1 "System Data AC500-eCo"
Value
Terminal 19 for UP (+24 VDC) and terminal 20
for ZP (0 VDC)
24 VDC
5 mA + max. 0.5 A per output
5 %
0.000002 A
Yes
Recommended; the outputs must be pro-
tected by an 3 A fast fuse
Ca. 10 mA
LED = OFF
LED = ON
Output is
Output is ON
OFF
(the output voltage is
only displayed if the
supply voltage of the
module is ON)
2
s
2019/04/17