Installation & Operation Manual - Model ISO LIMITED WARRANTY Accutrol LLC, having its principal place of business at 21 Commerce Drive, Danbury, CT USA ® ("Manufacturer") warrants its Iso-Tek Room Pressure Monitor, as follows: 1. Limited Warranty. Manufacturer warrants that the Products sold hereunder will be free from defects in material and workmanship for a period of twelve (12) months from the date of purchase.
IO Module, and an advanced pressure sensor kit that is designed to measure ultra-low- differential pressures with a high degree of precision and excellent long-term stability. Field ™ configuration of the Iso-Tek is made simple using the Accutrol Insight configuration software. 1.1 Theory of Operation ®...
Page 6
Installation & Operation Manual - Model ISO 1.2 Model Code OPTIONS NUMBER OF ROOM SENSOR KITS BLANK = No Options 1 = 1 Room Sensor Kit M = BACnet MS/TP 2 = 2 Room Sensor Kits W = Wireless Bluetooth 3 = 3 Room Sensor Kits 4 = 4 Room Sensor Kits DISPLAY CABLE LENGTH...
1 K-ohm load Door Switch Input Dry Contact Input for Primary Room Door Switch (software configurable) Accutrol Sensor Port 5-pos. pluggable screw terminal Note: connect to Pressure Sensor Network using Windy City Wire # 042003 only Accutrol Display Port...
Installation & Operation Manual - Model ISO SECTION 4 – INSTALLATION 4.1 Display Module The Iso-Tek Display Module is designed to be installed onto a double or triple-gang e-box (provided by others) typically located at eye level directly outside of the room being monitored. 4.1.1 Installation Steps 1.
Page 10
Installation & Operation Manual - Model ISO 4.3 Sensor Probe and Reference Probe The Sensor and Reference Probes are designed to be installed onto a single-gang electrical box (e-box). The Sensor Probe shall be installed inside the pressurized space and the Reference Probe shall be installed outside the pressurized space in a location designated as the reference pressure zone for the space.
• Bluetooth v4.2 or later required for Iso-Tek with “-W” wireless option. 6.2 Installing the Iso-Tek Insight Software 1. If the Accutrol Software Manager (ASM) is already installed on your Windows Device, skip to Step 3. Otherwise, download the ASM from using the following link: https://www.accutrolllc.com/accuvalve-software-downloads/...
Page 13
1. Open the Accutrol Software Manager and select the ISO Insight application. 2. The yellow registration window shown below will appear. 3. Copy the Product Key provided in the email from Accutrol and paste it into the “Enter Product Key” field provided and select the “Click to Activate” button.
Page 14
Installation & Operation Manual - Model ISO 6.5.2.1 Installing USB Drivers 1. Navigate to the file folder titled “ISO Insight” which is included in the Iso-Tek Install Zip file previously downloaded. 2. Within this folder is another Zip file called CP210x_Windows_Drivers. 3.
Installation & Operation Manual - Model ISO SECTION 7 – CONFIGURING ISO-TEK USING INSIGHT 7.1 Power Up 7.2 Configure Iso-Tek A. Select the number of rooms to be monitored by this Iso-Tek system. B. Enter a name for each room associated with its corresponding room sensor. NOTE: The LED on the Insight screen will flash at the same rate as the LED on the room sensor that it is associated with.
Page 16
Installation & Operation Manual - Model ISO 7.4 Room Configuration At the bottom of each room panel on the dashboard you will find a room configuration button which provides access to the Display, Door Switch and Alarm Configuration screens for each room. 7.4.1 Display Configuration Set switch to right to show value on Display.
Page 17
Installation & Operation Manual - Model ISO 7.4.2.1 Room Pressure Alarm Setpoints Click Enable box to enable/disable alarm. If enabled, enter the alarm setpoint in the box provided. The example shown is a Positive Room with a low pressure alarm setpoint of 0.02”wc and a high pressure alarm setpoint of 0.08”wc.
Page 18
Installation & Operation Manual - Model ISO 7.5 Analog Output Configuration The Iso-Tek has two independent analog outputs which can be configured to provide an analog signal representing room pressure for any two rooms connected to the Iso-Tek. The analog signal can be configured for voltage or current and scaled per the application requirements.
Page 19
Installation & Operation Manual - Model ISO BACnet MSTP: The BACnet selection is only available when a BACnet Card is installed in the IO Module. The BACnet window shown below is used to configure the BACnet communication settings for the unit. o Device Configuration: Enter the BACnet Instance Number, MAC Address and Baud Rate.
Page 20
Administrator. o Admin Password: Every Iso-Tek is shipped with a default Admin Password of “Accutrol”. When the Admin Password is set to “Accutrol”, anyone with ISO Insight will have open access to enable, view and assign user pins.
Page 21
Installation & Operation Manual - Model ISO 7.6 Tools Menu Close Window After Update: Selecting will result in any window will be automatically closed after selecting the update device button. Measurement Units: Set the units of Measurement for Flow, Temperature, and Pressure from this window.
Page 22
Installation & Operation Manual - Model ISO 7.7 Device Info 7.7.1 Device Identification Provides information associated with the identification of the Iso-Tek as shown below. 7.7.2 Device System Info Selecting Device System Info will provide the connection status of the Iso-Tek IO Module. A Green indicator implies the device is connected to the IO Module and is operational.
Installation & Operation Manual - Model ISO SECTION 8 – TOUCHSCREEN NAVIGATION 8.1 Menu Navigation Because all configuration is accomplished using the Iso-Tek Insight Software, the touchscreen display navigation is simple. The basic menu hierarchy for the Iso-Tek touchscreen display is shown below. VIEW VIEW BACNET...
Page 24
Installation & Operation Manual - Model ISO 8.3.1 Visual Alarm Status Each individual pressure relationship supports up to 4 different alarm statuses. Each status has its own unique appearance that may override the operating image or background color that was used to configure the space. 8.3.2 Room Door Position Status The room door position status indicator can be viewed from the home screen and room screen.
Page 25
Installation & Operation Manual - Model ISO 8.5 The Info Screen: Selecting the info icon provides access to the tile menu shown below. 8.5.1 BACNET opens a viewing-only screen that provides the general BACnet settings for the Iso-Tek shown below. Changes to the BACnet config must be made using ISO Insight software. 8.5.2 DATE/TIME enables the user to adjust the date and time of the Iso-Tek’s RTC in addition to setting the RTC format to either “Standard”...
Page 26
Installation & Operation Manual - Model ISO 8.5.4 ROOM provides a summary of all room data. The example below is for a single room application. Isolation Room 0.0450" WC POSITIVE 11 ACH 450 CFM In 390 CFM Out 62% RH 72°...
Installation & Operation Manual - Model ISO SECTION 9 – MAINTENANCE The Iso-Tek system does not require any preventative maintenance. Sensor Certification Sensor Probes can be returned to the factory for recertification if required. Contact your local representative for details. Cleaning the Touchscreen Display The touchscreen display can be wiped down with a damp cloth to remove smudges or surface dirt.
Installation & Operation Manual - Model ISO APPENDIX A – BACnet MS/TP BACnet® is a standard data communication protocol designed specifically for building automation and control networks. The Iso-Tek uses the BACnet MS/TP (Master-Slave/Token Passing) protocol which is a type of MAC layer implemented using the EIA-485 signaling standard.
Page 29
Installation & Operation Manual - Model ISO A.2 Iso-Tek Room Pressure Monitor BACnet Point List OBJECT UNITS DESCRIPTION TYPE Device Object Dexxx Analog Inputs Room1 Pressure Measurement AI-1 Pressure Room2 Pressure Measurement AI-2 Pressure Room3 Pressure Measurement AI-3 Pressure Room4 Pressure Measurement AI-4 Pressure Flash Writes Remaining (Ref Section A.2.1)
To Connect to the Iso-Tek with Bluetooth Launch the Iso-Tek Insight application and select “Locate BT Devices”. Only Bluetooth enabled Accutrol devices within range will be discovered and listed by their TAG names. Double-click on the appropriate device to connect.