Page 2
Safety Precautions Before installing the unit, thoroughly read the following safety precautions. Observe these safety precautions for your safety. WARNING This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid the risk of serious injury or death.
Page 3
WARNING Securely attach the terminal block cover (panel) to the After completing the service work, check for a gas unit. leak. If the terminal block cover (panel) is not installed properly, If leaked refrigerant is exposed to a heat source, such as a dust and/or water may infiltrate and pose a risk of electric fan heater, stove, or electric grill, poisonous gases may be shock, smoke, and/or fire.
Page 4
Precautions for handling units for use with R410A CAUTION Do not use the existing refrigerant piping. Use a vacuum pump with a reverse-flow check valve. A large amount of chlorine that is contained in the residual If a vacuum pump that is not equipped with a reverse-flow refrigerant and refrigerator oil in the existing piping may check valve is used, the vacuum pump oil may flow into the cause the refrigerator oil in the new unit to deteriorate.
Page 5
Before installing the unit WARNING Do not install the unit where a gas leak may occur. When installing the unit in a hospital, take appropriate measures to reduce noise interference. If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
Page 6
Before installing the unit (moving and reinstalling the unit) and performing electrical work CAUTION Properly ground the unit. Periodically check the installation base for damage. Do not connect the grounding wire to a gas pipe, water pipe, If the unit is left on a damaged platform, it may fall and lightning rod, or grounding wire from a telephone pole.
Page 7
Before the test run CAUTION Turn on the unit at least 12 hours before the test run. Do not operate the unit without panels and safety guards. Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc- Rotating, high-temperature, or high-voltage parts on the unit tions.
CONTENTS I Read Before Servicing [1] Read Before Servicing......................3 [2] Necessary Tools and Materials ....................4 [3] Piping Materials ........................5 [4] Storage of Piping ........................6 [5] Pipe Processing........................6 [6] Brazing............................7 [7] Air Tightness Test........................8 [8] Vacuum Drying (Evacuation) ....................
Page 9
CONTENTS [6] Compressor Replacement Instructions................. 357 [7] Servicing the BC controller ....................366 [8] Troubleshooting Using the Heat source Unit LED Error Display .......... 369 X LED Monitor Display on the Heat source Unit Board [1] How to Read the LED on the Service Monitor ..............373 HWE15150...
Page 10
I Read Before Servicing [1] Read Before Servicing .......................3 [2] Necessary Tools and Materials..................4 [3] Piping Materials ......................... 5 [4] Storage of Piping ....................... 6 [5] Pipe Processing ......................... 6 [6] Brazing..........................7 [7] Air Tightness Test ......................8 [8] Vacuum Drying (Evacuation) .....................
[ I Read Before Servicing ] I Read Before Servicing [1] Read Before Servicing 1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type Multi air conditioner for building application CITY MULTI WY/WR2 TLMU-A/YLMU-A series: R410A 2.
[ I Read Before Servicing ] [2] Necessary Tools and Materials Prepare the following tools and materials necessary for installing and servicing the unit. Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C) 1.
[ I Read Before Servicing ] [3] Piping Materials Do not use the existing piping! 1. Copper pipe materials O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands. 1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed) at the same radial thickness.
[ I Read Before Servicing ] [4] Storage of Piping 1. Storage location Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe. 2.
[ I Read Before Servicing ] [6] Brazing No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system. Example: Inside the brazed connection Use of oxidized solder for brazing Use of non-oxidized solder for brazing 1.
[ I Read Before Servicing ] [7] Air Tightness Test No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak. Halide torch R22 leakage detector 1. Items to be strictly observed Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight- ness, taking temperature variations into account.
[ I Read Before Servicing ] [8] Vacuum Drying (Evacuation) (Photo1) 15010H (Photo2) 14010 Recommended vacuum gauge: ROBINAIR 14010 Thermistor Vacuum Gauge 1. Vacuum pump with a reverse-flow check valve (Photo1) To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve.
Page 19
[ I Read Before Servicing ] 7. Notes To evacuate air from the entire system Applying a vacuum through the check joints at the refrigerant service valve (BV1 and 2) is not enough to attain the desired vacuum pressure. Be sure to apply a vacuum through the check joints at the refrigerant service valve (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2).
[ I Read Before Servicing ] [9] Refrigerant Charging Cylinder with a siphon Cylinder without a siphon Cylin- Cylin- Cylinder color R410A is pink. Refrigerant charging in the liquid state Valve Valve liquid liquid 1. Reasons R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22.
[ I Read Before Servicing ] [11] Characteristics of the Conventional and the New Refrigerants 1. Chemical property As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia.
[ I Read Before Servicing ] [12] Notes on Refrigerating Machine Oil 1. Refrigerating machine oil in the HFC refrigerant system HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil. Refrigerant Refrigerating machine oil Mineral oil...
[ I Read Before Servicing ] [13] Precautions for servicing Control boxes house high-voltage and high-temperature electrical parts. They may still remain energized or hot after the power is turned off. When opening or closing the front cover of the control box, keep out of contact with the internal parts. Before inspecting the inside of the control box, turn off the power, leave the unit turned off for at least 10 minutes, and check that the voltage of the electrolytic capacitor (inverter main circuit) has dropped to 20 VDC or less.
II Restrictions [1] System configuration ....................... 17 [2] Types and Maximum allowable Length of Cables ............19 [3] Switch Settings and Address Settings ................21 [4] Sample System Connection..................... 27 [5] An Example of a System to which an MA Remote Controller is connected..... 28 [6] An Example of a System to which an ME Remote Controller is connected.....
[ II Restrictions ] II Restrictions [1] System configuration 1. Table of compatible indoor units <PQHY> The table below summarizes the types of indoor units that are compatible with different types of heat source units. Heat Composing units Maximum total capacity Maximum number Types of connectable in- source...
Page 27
[ II Restrictions ] 1. Table of compatible indoor units <PQRY> The table below summarizes the types of indoor units that are compatible with different types of heat source units. Heat Composing units Maximum total capacity Maximum number Types of connectable in- source of connectable indoor of connectable in-...
[ II Restrictions ] [2] Types and Maximum allowable Length of Cables 1. Wiring work (1) Notes 1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man- ual. 2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.) 3) Provide grounding for the heat source unit as required.
Page 29
[ II Restrictions ] 1) M-NET transmission line Facility All facility types type Type Shielded cable CVVS, CPEVS, MVVS Cable type Number of 2-core cable cores Cable size Larger than 1.25mm [AWG16], or ø1.2mm or above Maximum transmission line distance between the 200 m [656ft] max.
[ II Restrictions ] [3] Switch Settings and Address Settings 1. Switch setting Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected" before performing wiring work. Set the switches while the power is turned off.
Page 31
[ II Restrictions ] 2. M-NET Address settings (1) Address settings table The need for address settings and the range of address setting depend on the configuration of the system. Unit or controller Sym- Address Setting method Factory setting address range setting CITY MULTI...
Page 32
[ II Restrictions ] *6. No address settings are required for units in a system with a single heat source unit (with some exceptions). Address setting is required if a sub BC controller is connected. (2) Power supply switch connector connection on the heat source unit (Factory setting: The male power supply switch connector is connected to CN41.) There are limitations on the total number of units that are connectable to each refrigerant system.
Page 33
[ II Restrictions ] (5) Various start-stop controls (Indoor unit settings) Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10. *4 *5 Setting (SW1) Operation of the indoor unit when the operation is resumed after the unit Function was stopped Power ON/OFF by the...
Page 34
[ II Restrictions ] *3. Low-noise mode is valid when Dip SW6-8 on the heat source unit is set to OFF. When DIP SW6-8 is set to ON, 4 levels of on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2 or more heat source units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.
Page 35
[ II Restrictions ] (8) Demand control 1) General outline of control Demand control is performed by using the external signal input to the 1-2 and 1-3 pins of CN3D on the heat source units (OC, OS1, and OS2). Between 2 and 12 steps of demand control is possible by setting DIP SW6-8 on the heat source units (OC, OS1, and OS2). Table.1 DipSW6-8 Demand control switch...
[ II Restrictions ] 8-step demand control (When SW6-8 is set to ON on two heat source units) Demand capacity is shown below. 8-step demand No.2 CN3D 1-2P Open Short-circuit No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Open 100% Short-circuit Short-circuit...
[ II Restrictions ] [5] An Example of a System to which an MA Remote Controller is connected 1. System with one heat source unit (automatic address setup for both indoor and heat source units) <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Leave the male...
Page 38
[ II Restrictions ] Set one of the MA remote controllers to sub. (Refer to (4) Wiring method MA remote controller function selection or the installation 1) Indoor-heat source transmission line manual for the MA remote controller for the setting meth- od.) Daisy-chain terminals M1 and M2 on the terminal block for indoor-heat source transmission line (TB3) on the...
Page 39
[ II Restrictions ] 2. An example of a system with one heat source unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and heat source units) <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male...
Page 40
[ II Restrictions ] 4) LOSSNAY connection (4) Wiring method Connect terminals M1 and M2 on the terminal block 1) Indoor-heat source transmission line (TB5) on the indoor unit (IC) to the appropriate terminals Same as [5] 1. on the terminal block (TB5) on LOSSNAY (LC). (Non-po- larized two-wire) Shielded cable connection Same as [5] 1.
Page 41
[ II Restrictions ] 3. Group operation of units in a system with multiple heat source units <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male Group Group from CN41 to CN40.
Page 42
[ II Restrictions ] whose power jumper was moved from CN41 to CN40, (4) Wiring method central control is not possible, even if TB7's are daisy- 1) Indoor-heat source transmission line chained.) Same as [5] 1. Only use shielded cables. Only use shielded cables.
Page 43
[ II Restrictions ] 4. A system in which a system controller is connected to the transmission line for centralized control and which is pow- ered from a heat source unit <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male...
Page 44
[ II Restrictions ] was moved from CN41 to CN40, central control is not pos- (4) Wiring method sible, even if TB7's are daisychained.) 1) Indoor-heat source transmission line Only use shielded cables. Shielded cable connection Same as [5] 1. Daisy-chain the S terminal on the terminal block (TB7) on Only use shielded cables.
Page 45
[ II Restrictions ] 5. An example of a system in which a system controller is connected to the indoor-heat source transmission line (ex- cept LM adapter) <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male from CN41 to CN40.
Page 46
[ II Restrictions ] line for the central control system to TB7 of the OC. (Note (4) Wiring method a).To maintain the central control even during an OC fail- 1) Indoor-heat source transmission line ure or a power failure, connect TB7 on OC and OS to- gether.
Page 47
[ II Restrictions ] 6. System with one heat source unit (automatic address setup for both indoor and heat source units) <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male Group Group connector on connector on CN41 as it is.
Page 48
[ II Restrictions ] remote controllers. (4) Wiring method Set one of the MA remote controllers as a sub controller. 1) Indoor-heat source transmission line (Refer to the Instruction Manual for the MA remote con- Daisy-chain terminals M1 and M2 of the terminal block troller for the setting method.) for indoor-heat source transmission line (TB3) on the Group operation of indoor units...
Page 49
[ II Restrictions ] 7. An example of a system with one heat source unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and heat source units) <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male Group...
Page 50
[ II Restrictions ] 2) Transmission line for centralized control (4) Wiring method No connection is required. 1) Indoor-heat source transmission line Daisy-chain terminals M1 and M2 of the terminal block 3) MA remote controller wiring for indoor-heat source transmission line (TB3) on the Same as [5] 6.
Page 51
[ II Restrictions ] 8. Group operation of units in a system with multiple heat source units <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male from CN41 to CN40. Group Group Group connector on...
Page 52
[ II Restrictions ] ure or a power failure, connect TB7 on OC and OS to- (4) Wiring method gether. (If there is a problem with the heat source unit 1) Indoor-heat source transmission line whose power jumper was moved from CN41 to CN40, central control is not possible, even if TB7's are daisy- Same as [5] 7.
Page 53
[ II Restrictions ] 9. A system in which a system controller is connected to the transmission line for centralized control and which is pow- ered from a heat source unit <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male from CN41 to CN40.
Page 54
[ II Restrictions ] is a problem with the heat source unit whose power jumper (4) Wiring method was moved from CN41 to CN40, central control is not pos- sible, even if TB7's are daisychained.) 1) Indoor-heat source transmission line Only use shielded cables.
Page 55
[ II Restrictions ] 10. An example of a system in which a system controller is connected to the indoor-heat source transmission line (ex- cept LM adapter) <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector . from CN41 to CN40.
Page 56
[ II Restrictions ] not daisy-chained, connect the transmission line for the central con- (4) Wiring method trol system to TB7 of the OC. (Note a).To maintain the central control even during an OC failure or a power failure, connect TB7 on OC 1) Indoor-heat source transmission line and OS together.
Page 57
[ II Restrictions ] 11. A system with multiple BC controller connections (with a system controller connected to the centralized control line) <PQRY> (1) Sample control wiring Leave the male Move the male connector connector on from CN41 to CN40 CN41 as it is.
Page 58
[ II Restrictions ] not daisy-chained, connect the transmission line for the central con- (4) Wiring method trol system to TB7 of the OC. (Note a).To maintain the central control even during an OC failure or a power failure, connect TB7 on OC Indoor-heat source transmission line and OS together.
[ II Restrictions ] [6] An Example of a System to which an ME Remote Controller is connected 1. A system in which a system controller is connected to the centralized control transmission line <PQHY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male...
Page 60
[ II Restrictions ] When 2 remote controllers are connected to the sys- (4) Wiring method 1) Indoor-heat source transmission line Refer to the section on Switch Setting. Same as [5] 1. Performing a group operation (including the group Shielded cable connection operation of units in different refrigerant circuits).
Page 61
[ II Restrictions ] 2. A system in which a system controller is connected to the centralized control transmission line <PQRY> (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male from CN41 to CN40. connector on SW5-1 OFF ON CN41 as it is.
Page 62
[ II Restrictions ] When 2 remote controllers are connected to the sys- (4) Wiring method 1) Indoor-heat source transmission line Refer to the section on Switch Setting. Same as [5] 8. Performing a group operation (including the group Shielded cable connection operation of units in different refrigerant circuits).
[ II Restrictions ] [7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected 1. PQHY (1) Sample control wiring Leave the male Leave the male Move the male connector Group connector on connector on from CN41 to CN40.
Page 64
[ II Restrictions ] Same as [5] 1. (4) Wiring method Group operation of indoor units 1) Indoor-heat source transmission line Same as [5] 1. Same as [5] 1. 4) ME remote controller wiring Shielded cable connection Same as [6] Same as [5] 1.
Page 65
[ II Restrictions ] 2. PQRY (1) Sample control wiring Move the male connector Leave the male from CN41 to CN40. Group Group connector on SW5-1 OFF ON CN41 as it is. SW5-1 OFF ON TB15 TB15 TB15 TB02 M1M2 M1M2 M1M2 M1M2...
Page 66
[ II Restrictions ] Group operation of indoor units (4) Wiring method Same as [5] 6. 1) Indoor-heat source transmission line 4) ME remote controller wiring Same as [5] 8. When 2 remote controllers are connected to the sys- Shielded cable connection Same as [5] 6.
Page 67
[ II Restrictions ] (5) Address setting method Pro- dress Facto- Unit or controller set- Setting method Notes ry set- dure ting ting range Opera- Main 01 to Assign the smallest address to Assign an address smaller than that of the main unit in the group.
[ II Restrictions ] [8] Restrictions on Pipe Length (1) End branching <PQHY> P72 - P192 models Heat source unit Branch header First branch (Twinning kit) Indoor Indoor Indoor Twinning kit Indoor Indoor Indoor Unit: m [ft] Allowable length of Operation Pipe sections pipes...
Page 69
[ II Restrictions ] P144 - P360 models Provide a trap on the pipe (gas pipe only) within 2 m from the Note1 Install the pipe that connects the branch pipe and the heat source units joint pipe if the total length of the pipe that connects the joint in the way that it has a downward inclination toward the branch pipe.
Page 70
[ II Restrictions ] 1. Refrigerant pipe size <PQHY> (1) Diameter of the refrigerant pipe between the heat source unit and the first branch (heat source unit pipe size) Heat source unit set Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch] name P72 model ø9.52 [3/8"]...
Page 71
[ II Restrictions ] (5) Size of the refrigerant pipe between the first distributor or the second distributor and heat source units Heat source unit Composing unit models Liquid pipe (mm) [inch] Gas pipe (mm) [inch] model P144 ø9.52 [3/8"] ø19.05 [3/4"] P168 ø9.52 [3/8"]...
Page 72
[ II Restrictions ] (1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con- troller> <PQRY> Heat source unit *Use a main BC controller when connecting the heat source units of P144 model or above.
Page 73
[ II Restrictions ] 1) To connect the P72 or P96 model of indoor units, use an optional junction pipe kit (Model: CMY-R160C-J) and merge the two ports before connecting them. 2) Do not connect the P72 or P96 model of indoor units and other models of indoor units at the same port. 3) All the units that are connected to the same ports can only be operated in the same operation mode (cooling/heating).
Page 74
[ II Restrictions ] (2) System that requires more than 16 BC controller ports or with multiple BC controllers <Heat source unit P120 model or below> Heat source unit Twinning kit Indoor (CMY-Y202S-G2) (CMY-Y102LS-G2) (CMY-Y102SS-G2) BC controller (sub) BC controller (main) Twinning kit (CMY-Y102SS-G2) BC controller (sub)
Page 75
[ II Restrictions ] 1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel.
Page 76
[ II Restrictions ] (3) System that requires more than 16 BC controller ports or with multiple BC controllers <Heat source unit P144 model or above> Heat source unit Heat source unit Twinning kit Heat source unit CMY-Q100CBK2 : P144-P240 CMY-Q200CBK : P288-P336 On the low-pressure side, the twinning kit connects to the pipes on site inside the heat source unit.
Page 77
[ II Restrictions ] 1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel.
Page 78
[ II Restrictions ] 2. Refrigerant pipe size <PQRY> (1) Between heat source unit and the first twinning pipe (Part A) Unit : mm [inch] Refrigerant pipe size Heat source unit High-pressure pipe Low-pressure pipe ø15.88 [5/8"] ø19.05 [3/4"] ø19.05 [3/4"] ø22.2 [7/8"] P120 P144 - P192...
Page 79
[ II Restrictions ] 3. Connecting the BC controller <PQRY> (1) Size of the pipe that fits the standard BC controller ports P72 - P120 models Connection: Brazed connection To heat source unit BC controller Reducer Twinning kit (Model name:CMY-Y102SS-G2) Junction pipe kit (Standard (Optional accessory)
Page 80
[ II Restrictions ] 1) To connect P06 - P18 models of indoor units use 2) To connect P72 - P96 models of indoor units (or when the the reducer that is supplied with the BC controller. total capacity of indoor units exceeds P31), use a junction pipe kit and merge the two nozzles.
Page 81
[ II Restrictions ] (2) Size of the pipe that fits the main BC controller ports P72 - P336 models Twinning kit (Model name:CMY-Y102SS-G2) (Optional accessory) To heat Connection: Brazed connection source unit BC controller (main) Reducer (Standard supplied parts) Junction pipe kit (Model name: CMY-R160C-J)
Page 82
[ II Restrictions ] (3) Size of the pipe that fits the sub BC controller ports Twinning kit (Model name:CMY-Y102SS-G2) (Optional accessory) Connection: Brazed connection To Main BC controller Junction pipe kit BC controller (sub) (Model name: CMY-R160C-J) (Optional accessory) Reducer (Standard supplied parts) Indoor...
III Heat source Unit Components [1] Heat source Unit Components and Refrigerant Circuit............ 77 [2] Control Box of the Heat source Unit ................83 [3] Heat source Unit Circuit Board ..................85 [4] BC Controller Components ....................90 [5] Control Box of the BC Controller..................93 [6] BC Controller Circuit Board....................
[ III Heat source Unit Components ] III Heat source Unit Components [1] Heat source Unit Components and Refrigerant Circuit 1. Front view of a heat source unit (1) PQHY-P72, 96, 120ZLMU-A, PQRY-P72, 96, 120ZLMU-A Top panel Control box Front panel - 77 - HWE15150...
Page 87
[ III Heat source Unit Components ] (2) PQHY-P144, 168, 192ZLMU-A, PQRY-P144, 168, 192ZLMU-A Top panel Control box Front panels - 78 - HWE15150...
[ III Heat source Unit Components ] [2] Control Box of the Heat source Unit 1. Control Box <HIGH VOLTAGE WARNING> Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Page 93
[ III Heat source Unit Components ] 2. Transformer Box Transformer (T02) Transformer (T03) - 84 - HWE15150...
[ III Heat source Unit Components ] [3] Heat source Unit Circuit Board 1. Heat source unit control board CN61 17 VDC Serial communication 17 VDC signal input Serial communication CN801 Pressure switch connection (Inverter board) 5 VDC CNDC Bus voltage input (325 VDC) Actuator drive signal output...
Page 95
[ III Heat source Unit Components ] 2. M-NET board CNS2 CNIT CN102 Input 12VDC Transmission line Power supply output for centralized input/output for control system (30VDC) Input 5VDC centralized control CN04 Indoor-heat source transmission line Power supply system (30VDC) Bus voltage input input/output (30VDC) detection output...
Page 96
[ III Heat source Unit Components ] 3. INV board Serial communication signal output LED4 GND (Control board) Lit during normal CPU operation GND (Control board) LED1 Open: No-load operation setting 17 VDC input Inverter in normal operation (Lit) /Error (blinking) Short-circuited: Normal setting 17 VDC input SC-P10...
Page 97
[ III Heat source Unit Components ] 4. I/O board CNPW Pump interlock signal output Pump interlock signal output CNOUT2 12 VDC input Operation ON signal input (X25) CNAC4 Operation ON signal output Power Input (24 VAC or 24 VDC) (non-polar) 230 VAC input L1 phase Operation ON signal output...
Page 98
[ III Heat source Unit Components ] 5. Noise Filter Fuse Fuse 600 VAC 6A F 600 VAC 6A F CNTR CAUTION FOR 575 VAC output HIGH VOLTAGE Surge absorber circuit Short circuit TB11 TB21 TB31 Input/output (L1) Input/output (L2) Input/output (L3) 325 VDC output 230 VAC Input...
[ III Heat source Unit Components ] [5] Control Box of the BC Controller 1. CMB-P1016NU-G1, GA1, HA1 Transformer Terminal block for power supply Terminal block for transmission line Relay board BC board - 93 - HWE15150...
IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers ........99 [2] Group Settings and Interlock Settings via the ME Remote Controller ......100 [3] Interlock Settings via the MA Remote Controller ............104 [4] Using the built-in Temperature Sensor on the Remote Controller ......... 105 - 97 - HWE15150...
[ IV Remote Controller ] IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers There are two types of remote controllers: ME remote controller, which is connected on the indoor-heat source transmis- sion line, and MA remote controller, which is connected to each indoor unit. 1.
[ IV Remote Controller ] [2] Group Settings and Interlock Settings via the ME Remote Controller 1. Group settings/interlock settings Make the following settings to perform a group operation of units that are connected to different heat source units or to manually set up the indoor/heat source unit address.
Page 110
[ IV Remote Controller ] Repeat steps in the previous page to interlock all the indoor units in a group with the LOSSNAY unit. (C) To return to the normal display When all the group settings and interlock settings are made, take the To go back to the normal display, To search for an address, follow step...
Page 111
[ IV Remote Controller ] (A) To delete group settings (B) To delete interlock settings <Successful completion of deletion> If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will (Displayed alternately) will be displayed in the room temperature display window. appear in the unit type display - If a transmission error occurs, the selected setting will not be window.
Page 112
[ IV Remote Controller ] [Operation Procedures] 1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display). 2. Press buttons [CHECK] and [MODE] simultaneously for 2 seconds to go into the operation mode display selection mode under the remote controller function selection mode.
[ IV Remote Controller ] [3] Interlock Settings via the MA Remote Controller 1. LOSSNAY interlock setting (Make this setting only when necessary.) * When the upper controller is connected, make the setting using the upper controller. NOTE: When using LOSSNAY units in conjunction, interlock the addresses of all indoor units within the group and address of LOSSNAY units. Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to search and delete registered information.
[ IV Remote Controller ] 2. Search Procedures > To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it. <Indoor unit address> Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
V Electrical Wiring Diagram [1] Electrical Wiring Diagram of the Heat source Unit............109 [2] Electrical Wiring Diagram of the BC Controller .............. 110 [3] Electrical Wiring Diagram of Transmission Booster............120 - 107 - HWE15150...
[ V Electrical Wiring Diagram ] [3] Electrical Wiring Diagram of Transmission Booster Terminal block for power supply (TB1) 250V 5A Red Red Red Black White White Green/Yellow 100V/200VAC Varistor Noise filter Black White White White White Varistor Green Black Stabilized power supply Blue Black...
VI Refrigerant Circuit [1] Refrigerant Circuit Diagram ................... 123 [2] Principal Parts and Functions ..................128 - 121 - HWE15150...
[ VI Refrigerant Circuit ] [2] Principal Parts and Functions 1. Heat source unit Part Symbols Notes Usage Specifications Check method name (functions) Com- Adjusts the amount of circulating Low-pressure shell scroll pressor (Comp1) refrigerant by adjusting the oper- compressor ating frequency based on the op- Wirewound resistance erating pressure data...
Page 138
[ VI Refrigerant Circuit ] Part Symbols Notes Usage Specifications Check method name (functions) Thermis- PQHY LEV1 is controlled based on the Degrees Celsius Resistance only TH2, TH3, and TH6 values check = 15k = 3460 0/80 PQHY Controls defrosting during heat- R = 15 3460 (Pipe...
Page 139
[ VI Refrigerant Circuit ] Part Symbols Notes Usage Specifications Check method name (functions) Sole- SV1a 1) High/low pressure bypass at AC208 - 230V Continuity check noid Discharge-suc- Open while being powered/ with a tester start-up and stopping, and valve tion closed while not being pow- capacity control during low-...
Page 140
[ VI Refrigerant Circuit ] 2. Indoor Unit Part Symbol Notes Usage Specification Check method Name (functions) Linear 1) Adjusts superheat at the DC12V Refer to the section expan- Opening of stepping motor "Continuity Test with a indoor heat exchanger sion valve driving valve 0-(1400) puls- Tester".
Page 141
[ VI Refrigerant Circuit ] 3. BC controller (1) G type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa]...
Page 142
[ VI Refrigerant Circuit ] (2) GA type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa] Con-...
Page 143
[ VI Refrigerant Circuit ] (3) GB type Symbols Part Part name Usage Specifications Check method (functions) code Thermistor TH12 LEV control (Superheat) (Bypass = 15k outlet tem- = 3460 0/80 perature) R = 15 3460 TH15 LEV control (Superheat) 0°C[32°F] : 15kohm (Bypass in- 10°C[50°F] :9.7kohm...
Page 144
[ VI Refrigerant Circuit ] (4) HA type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa] Con-...
Page 145
[ VI Refrigerant Circuit ] (5) HB type Symbols Part Part name Usage Specifications Check method (functions) code Thermistor TH12 LEV control (Superheat) (Bypass = 15k outlet tem- = 3460 0/80 perature) R = 15 3460 TH15 LEV control (Superheat) 0°C[32°F] : 15kohm (Bypass in- 10°C[50°F] :9.7kohm...
VII Control [1] Functions and Factory Settings of the Dipswitches ............139 [2] Controlling the Heat source Unit ..................145 [3] Controlling BC Controller ....................162 [4] Operation Flow Chart..................... 163 - 137 - HWE15150...
[ VII Control ] VII Control [1] Functions and Factory Settings of the Dipswitches 1. Heat source unit (1) Control board Function according to switch setting Units that require Switch Function Switch setting timing switch setting (Note 2) Unit address set- Set to 00 or 51-100 with the dial switch Before power on ting...
Page 149
[ VII Control ] Function according to Units that switch setting require Switch Function Switch setting timing switch setting (LED3 Unlit) (LED3 Lit) (Note 2) Refer to the LED monitor display Self-diagnosis/opera- SW6-10: 1-10 on the heat source unit heat Anytime after power on tion monitor source unit board.
Page 150
[ VII Control ] (2) INV board Functions are switched with the following connector. Function according to connec- Setting timing Connector Function Enabled Disabled Enabled Disabled CN6 short- Enabling/disabling the following error Error detec- Error detec- Anytime after power on circuit con- detection functions;...
Page 151
[ VII Control ] 2. Function of the switch (Indoor unit) (1) Dipswitches 1) SW1,3 Function according to switch setting Switch setting timing Switch Function Notes Set to ON (built-in sensor on the remote controller) Room temperature Built-in sensor on Indoor unit inlet on All Fresh (PEFY-P-NMHU-E-F) model units detection position...
Page 152
[ VII Control ] (2) Address switch Actual indoor unit address setting varies in different systems. Refer to the installation manual for the heat source unit for details on how to make the address setting. Each address is set with a combination of the settings for the 10's digit and 1's digit. (Example) When setting the address to "3", set the 1's digit to 3, and the 10's digit to 0.
Page 153
[ VII Control ] (2) ME remote controller (PAR-F27MEA-US) Set the address of the remote controller with the rotary switch. Rotary switch 10's digit 1's digit (left) (right) Remote controller unit Example: In case of address 108 Address setting range Setting method Main remote controller 101-150...
[ VII Control ] [2] Controlling the Heat source Unit -1- Outline of Control Method The heat source units are designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Page 155
[ VII Control ] -5- Bypass Control Bypass solenoid valves, which bypass the high- and low- pressure sides, perform the following functions. (1) Bypass solenoid valve (SV1a) (ON = Open) SV1a Operation When the compressor on each heat source ON for 4 minutes. unit starts up After the restoration of thermo or 3 minutes ON for 4 minutes.
Page 156
[ VII Control ] -6- Compressor Frequency Control Depending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature (0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi]) during heating operation.
Page 157
[ VII Control ] -7- Refrigerant Recovery Control <PQHY> Recovery of refrigerant is performed during heating operation to prevent the refrigerant from accumulating inside the unit while it is stopped (unit in fan mode), or inside the indoor unit that is in cooling mode or in heating mode with thermo off. It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the heat source heat exchanger.
Page 158
[ VII Control ] (2) Heat source unit heat exchanger capacity control patterns Operation mode Solenoid valve Operation Model pattern PQRY PQHY SV4a SV4b SV4d SV7a SV7b LEV6 LEV7 P72-P120 Cooling- 41 pulses 41-3000 pulses models only Cooling- main Cooling- Cooling only Heating-...
Page 159
[ VII Control ] Operation mode Solenoid valve Operation Model pattern PQRY PQHY SV4a SV4b SV4d SV7a SV7b LEV6 LEV7 P144- Cooling- 41 pulses 41-3000 pulses P192 only (SV7c models Cooling- main Cooling- Cooling only Heating- Heating 41-3000 pulses PQRY: only 41 pulses Heating-...
Page 160
[ VII Control ] -10- Subcool Coil Control (Linear Expansion Valve <LEV1>) <PQHY only> The OC, OS1, and OS2 controls the subcool coil individually. The LEV is controlled every 30 seconds to maintain constant the subcool at the heat source unit heat exchanger outlet that is calculated from the values of high pressure (63HS1) and liquid piping temperature (TH3), or the superheat that is calculated from the values of low pressure (63LS) and the bypass outlet temperature (TH2) of the subcool coil.
Page 161
[ VII Control ] (2) System with two heat-source units Initial startup mode starts. The compressor on the OC starts up. 60Hz The total operating load of the indoor unit after 5 minutes of operation is P96 or above. (*1 Qj The compressor on the OC starts up.
Page 162
[ VII Control ] (3) System with three heat-source units <PQHY only> Initial startup mode starts. The compressor on the OC starts up. 60Hz The total operating load of the indoor unit after 5 minutes of operation is P96 or above. ( *1 The total operating load of the indoor unit after 5 minutes of operation is between P96 and P400.
Page 163
[ VII Control ] -13- Emergency Operation Mode 1. Problems with the heat source unit Emergency operation mode is a temporary operation mode in which the heat source unit that is not in trouble operates when one of the heat source units in the system with two heat-source units is in trouble or when one or two of the heat source units in the system with three heat-source units are in trouble.
Page 164
[ VII Control ] (2) Ending the emergency operation 1) End conditions When one of the following conditions is met, emergency operation stops, and the unit makes an error stop. When the integrated operation time of compressor in cooling mode has reached four hours. When the integrated operation time of compressor in heating mode has reached two hours.
Page 165
[ VII Control ] Emergency operation pattern (2 heat source units) OC failure OS failure pattern pattern Trouble Normal Normal Trouble Cooling Emergency Permitted Permitted operation Heating Permitted Permitted Capacity that matches Maximum total capacity the total capacity of the of indoor units (Note 1) operable heat source units...
Page 166
[ VII Control ] -14- Control Method <PQRY only> The control system configuration for the PQRY models is shown in the chart below. Daisy-chained Non-polar 2-wire Data signal exchange non-polar 2-wire serial communication between system equipment method transmission line 16-bit CPU Calculation, processing microcomputer operation processing...
Page 167
[ VII Control ] -15- Cooling/heating Circuit Control and General Function of System Equipment Operation Schematic diagram of refrigerant circuit Schematic diagram of refrigerating cycle Two-phase status Liquid 4-way valve Check valve Selector valve Low- Pressure pressure Low-pressure two-phase pipe Low-pressure Liquid Cooling...
Page 168
[ VII Control ] -16- Operation Mode <PQHY> (1) Indoor unit operation mode The operation mode can be selected from the following 5 modes using the remote controller. Cooling mode Heating mode Dry mode Fan mode Stopped mode (2) Heat source unit operation mode Cooling mode All indoor units in operation are in cooling mode.
Page 169
[ VII Control ] -17- Operation Mode <PQRY> (1) Indoor unit operation mode The operation mode can be selected from the following 6 modes using the remote controller. Cooling mode Heating mode Dry mode Automatic cooling/heating mode Fan mode Stopping mode (2) Heat source unit operation mode Cooling only mode All indoor units in operation are in cooling mode.
Page 170
[ VII Control ] -18- DEMAND Control Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the heat source units. When DIP SW6-8 is set to ON, the 4-step DEMAND control is enabled. Eight-step demand control is possible in the system with two heat source units. Twelve-step demand control is possible in the system with three heat source units.
[ VII Control ] [3] Controlling BC Controller 1. Control of SV A, SV B, and SV A, SV B, and SV C turn on or off depending on the operation mode of the branch. Mode Cooling Heating Stopped Defrost SV A Port SV B...
[ VII Control ] [4] Operation Flow Chart 1. Mode determination flowchart <PQHY> (1) Indoor unit (cooling, heating, dry, fan mode) Start Normal operation Error Breaker Unit in the stopped state turned on From heat source unit Operation SW turned on 1.
Page 173
[ VII Control ] (2) Heat source unit (cooling and heating modes) Start Normal operation Error Breaker Unit in the stopped state turned on "HO" / "PLEASE WAIT" blinks on the remote controller *Note 1 Indoor units registered to the remote controller From indoor unit Operation...
Page 174
[ VII Control ] 2. Operations in each mode (1) Cooling operation Cooling operation Normal operation During test run mode 4-way valve OFF Unit in the stopped state Indoor unit fan *Note 1 operation Test run mode Thermostat ON 3-minute restart prevention 1.
Page 175
[ VII Control ] (2) Heating operation Normal operation Heating operation Unit in the stopped state During test run mode 4-way valve ON Test run mode Thermostat ON 3-minute restart prevention 1. Indoor unit fan operation at 1. Indoor-heat source unit fan control 2.
Page 176
[ VII Control ] (3) Dry operation Dry operation Normal operation Thermostat ON 4-way valve OFF Unit in the stopped state Test run mode *Note 2 Thermostat ON Suction temperature 18°C[64°F] *Note 1 1. Heat source unit (compressor) 1. Indoor unit fan stop intermittent operation 2.
Page 177
[ VII Control ] 1. Mode determination flowchart <PQRY> (1) Indoor unit (cooling, heating, dry, fan mode) Start Normal operation Error Breaker Stop turned on Operation SW turned on *Note 1 1. Protection function self-holding cancelled. 2. Indoor unit LEV fully closed. *Note 2 Remote controller Error mode...
Page 178
[ VII Control ] (2) Heat source unit (cooling only, heating only, cooling main and heating main modes) Start Normal operation Error Breaker turned on Unit in the stopped state "HO" / "PLEASE WAIT" blinks *Note 1 on the remote controller Indoor units registered to the remote controller...
Page 179
[ VII Control ] (3) BC controller (cooling only, heating only, cooling main and heating main modes) Start Normal operation Error Breaker turned on Unit in the stopped state Operation command 1. Determination of operation mode Protection function (Cooling only, Heating only, Mixture self-holding cancelled.
Page 180
[ VII Control ] 2. Operations in each mode (1) Cooling operation Cooling operation Normal operation During test run mode 4-way valve OFF Unit in the stopped state Indoor unit fan *Note 1 operation Test run mode Thermostat 3-minute restart prevention 1.
Page 181
[ VII Control ] (2) Heating operation Normal operation Heating operation Unit in the stopped state During test run mode 4-way valve ON Test run mode Thermostat 3-minute restart prevention 1. Indoor unit fan operation at 1. Indoor-heat source unit fan control Very Low speed 2.
Page 182
[ VII Control ] (3) Dry operation Dry operation Normal operation Thermostat ON 4-way valve OFF Unit in the stopped state Test run mode *Note 2 Thermostat ON Suction temperature 18 C[64 F] *Note 1 1. Heat source unit (compressor) 1.
VIII Test Run Mode [1] Items to be checked before a Test Run ................. 177 [2] Test Run Method ......................178 [3] Operating Characteristic and Refrigerant Amount ............181 [4] Adjusting the Refrigerant Amount .................. 181 [5] Refrigerant Amount Adjust Mode................... 186 [6] The following symptoms are normal.
[ VIII Test Run Mode ] VIII Test Run Mode [1] Items to be checked before a Test Run (1) Check for refrigerant leak and loose cables and connectors. (2) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
[ VIII Test Run Mode ] [2] Test Run Method 1. MA Remote Controller (PAR-30MAAU) (1) Remote controller button functions Function button The assignment of the function buttons varies depending on the screen. Follow the guide screen that will appear at the bottom of the screen (from the left, F1, F2, F3, and F4).
Page 188
[ VIII Test Run Mode ] (3) Entering the maintenance information occurs. Step 1: Switching the remote controller screen to "Maintenance information" (Requires the maintenance password. This screen is not accessible while the controller is under centralized control.) On the Service Menu screen, select "Input maintenance Service menu Maintenance information Model name input...
Page 189
[ VIII Test Run Mode ] 2. MA Remote Controller (PAR-21MAAU) The figure shows an MA remote controller (PAR-21MAAU). ON/OFF button Set Temperature buttons Down Fan Speed button TIME SUN MON TUE WED THU FRI SAT TIMER AFTER AFTER ERROR CODE FUNCTION FILTER WEEKLY...
[ VIII Test Run Mode ] [3] Operating Characteristic and Refrigerant Amount It is important to have a clear understanding of the characteristics of refrigerant and the operating characteristics of air conditioners before attempting to adjust the refrigerant amount in a given system. 1.
Page 191
[ VIII Test Run Mode ] 3. Amount of refrigerant to be added<PQHY> The amount of refrigerant that is shown in the table below is factory-charged to the heat source units. The amount necessary for extended pipe (field piping) is not included and must be added on site. Heat source unit model P120 P144...
Page 192
[ VIII Test Run Mode ] (2) Example: PQHY-P144ZLMU-A 9.52 9.52 (3 m) (1 m) 9.52 (10 m) 15.88 (10 m) Liquid separator 9.52 9.52 9.52 9.52 6.35 (10 m) (20 m) (10 m) (10 m) (10 m) 15.88 (30 m) model model model...
Page 193
[ VIII Test Run Mode ] 4. Amount of refrigerant to be added <PQRY> The amount of refrigerant that is shown in the table below is factory-charged to the heat source units. The amount necessary for extended pipe (field piping) is not included and must be added on site. Heat source unit model P120 P144...
Page 194
[ VIII Test Run Mode ] (2) Example Heat source unit 1 Heat source unit 2 Twinning kit Indoor Twinning kit (CMY-Y202S-G2) (CMY-Y102LS-G2) BC controller(HB) (CMY-Y102SS-G2) BC controller(HA) H H′ Twinning kit Reducer (P06 - P18) BC controller(HB) (CMY-Y102SS-G2) (Supplied with the BC Controller) Junction pipe kit (CMY-R160C-J) (Optional accessory)
[ VIII Test Run Mode ] [5] Refrigerant Amount Adjust Mode 1. Procedures <PQHY> Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode. When the function switch SW4 No.922 (SW6-10: ON) on the main board on the heat source unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.
Page 196
[ VIII Test Run Mode ] Start Turn on SW4 No.922 (SW6-10: ON) on the OC. Put all indoor units in the test run mode *Refer to the previous page for *Notes 1-4 in the chart. and run the units in cooling mode. Has the initial start-up mode been completed? Has it been at least...
Page 197
[ VIII Test Run Mode ] 2. Procedures <PQRY> Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode. When the function switch SW4 No.922 (SW6-10: ON) on the main board on the heat source unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.
Page 198
[ VIII Test Run Mode ] Start Turn on SW4 No.922 (SW6-10: ON) on the OC. Put all indoor units in the test run mode *Refer to the previous page for *Notes 1-4 in the chart. and run the units in cooling mode. Has the initial start-up mode been completed? Has it been at least...
[ VIII Test Run Mode ] [6] The following symptoms are normal. Remote controller Symptoms Cause display The indoor unit does not start "Cooling (heating)" The unit cannot perform a heating (cooling) operation when other indoor after starting cooling (heating) icon blinks on the units are performing a cooling (heating) operation.
[ VIII Test Run Mode ] [7] Standard Operation Data (Reference Data) 1. Single unit <PQHY> (1) Cooling operation Heat source unit model Item PQHY-P72ZLMU-A PQHY-P96ZLMU-A 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80°F/67°F] [80°F/67°F] Heat source water temperature °C [ °F] 29.4[85]...
Page 201
[ VIII Test Run Mode ] Heat source unit model Item PQHY-P120ZLMU-A PQHY-P144ZLMU-A 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80°F/67°F] [80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 29.4[85] 5.76 7.20 Heat source water flow rate [G/h] [1522] [1902] [gpm] [25.4] [31.7] No.
Page 202
[ VIII Test Run Mode ] Heat source unit model Item PQHY-P168ZLMU-A PQHY-P192ZLMU-A 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80°F/67°F] [80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 29.4[85] 7.20 7.20 Heat source water flow rate [G/h] [1902] [1902] [gpm] [31.7] [31.7] No.
Page 203
[ VIII Test Run Mode ] (2) Heating operation Heat source unit model Item PQHY-P72ZLMU-A PQHY-P96ZLMU-A Indoor temperature DB/WB 21.1°C/- [70°F/-] 21.1°C/- [70°F/-] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 5.76 5.76 Heat source water flow rate [G/h]...
Page 204
[ VIII Test Run Mode ] Heat source unit model Item PQHY-P120ZLMU-A PQHY-P144ZLMU-A Indoor temperature DB/WB 21.1°C/- [70°F/-] 21.1°C/- [70°F/-] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 5.76 7.20 Heat source water flow rate [G/h] [1522] [1902] [gpm] [25.4] [31.7] No.
Page 205
[ VIII Test Run Mode ] Heat source unit model Item PQHY-P168ZLMU-A PQHY-P192ZLMU-A Indoor temperature DB/WB 21.1°C/- [70°F/-] 21.1°C/- [70°F/-] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 7.20 7.20 Heat source water flow rate [G/h] [1902] [1902] [gpm] [31.7] [31.7] No.
Page 206
[ VIII Test Run Mode ] 2. 2-unit combination <PQHY> (1) Cooling operation 2-unit combination Item PQHY-P144ZSLMU-A PQHY-P72ZLMU-A PQHY-P72ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 207
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P168ZSLMU-A PQHY-P96ZLMU-A PQHY-P72ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 208
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P192ZSLMU-A PQHY-P96ZLMU-A PQHY-P96ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 209
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P216ZSLMU-A PQHY-P120ZLMU-A PQHY-P96ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 210
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P240ZSLMU-A PQHY-P120ZLMU-A PQHY-P120ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 211
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P288ZSLMU-A PQHY-P144ZLMU-A PQHY-P144ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 212
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P312ZSLMU-A PQHY-P168ZLMU-A PQHY-P144ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 213
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P336ZSLMU-A PQHY-P168ZLMU-A PQHY-P168ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 214
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P360ZSLMU-A PQHY-P192ZLMU-A PQHY-P168ZLMU-A Indoor temperature DB/WB 26.7°C/19.4°C[80°F/67°F] Heat source water temperature °C [ °F] 29.4[85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 215
[ VIII Test Run Mode ] (2) Heating operation 2-unit combination Item PQHY-P144ZSLMU-A PQHY-P72ZLMU-A PQHY-P72ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units...
Page 216
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P168ZSLMU-A PQHY-P96ZLMU-A PQHY-P72ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 217
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P192ZSLMU-A PQHY-P96ZLMU-A PQHY-P96ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 218
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P216ZSLMU-A PQHY-P120ZLMU-A PQHY-P96ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 219
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P240ZSLMU-A PQHY-P120ZLMU-A PQHY-P120ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4] [25.4] No. of connected units Unit Indoor No.
Page 220
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P288ZSLMU-A PQHY-P144ZLMU-A PQHY-P144ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 221
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P312ZSLMU-A PQHY-P168ZLMU-A PQHY-P144ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 222
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P336ZSLMU-A PQHY-P168ZLMU-A PQHY-P168ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 223
[ VIII Test Run Mode ] 2-unit combination Item PQHY-P360ZSLMU-A PQHY-P192ZLMU-A PQHY-P168ZLMU-A Indoor temperature DB/WB 21.1°C/-[70°F/-] Heat source water temperature °C [ °F] 21.1[70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7] [31.7] No. of connected units Unit Indoor No.
Page 224
[ VIII Test Run Mode ] 3. Single unit <PQRY> (1) Cooling only operation Heat source unit model Item PQRY-P72ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P104NU-G1 CMB-P104NU-G1 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80 °F/67 °F] [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4[85] 29.4[85]...
Page 225
[ VIII Test Run Mode ] Heat source unit model Item PQRY-P120ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P104NU-G1 CMB-P108NU-GA1 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80 °F/67 °F] [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4[85] 29.4[85] 5.76 7.20 Heat source water flow rate...
Page 226
[ VIII Test Run Mode ] Heat source unit model Item PQRY-P168ZLMU-A PQRY-P192ZLMU-A Model name of BC controller CMB-P108NU-GA1 CMB-P108NU-GA1 26.7°C/19.4°C 26.7°C/19.4°C Indoor temperature DB/WB [80 °F/67 °F] [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4[85] 29.4[85] 7.20 7.20 Heat source water flow rate...
Page 227
[ VIII Test Run Mode ] (2) Heating only operation Heat source unit model Item PQRY-P72ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P104NU-G1 CMB-P104NU-G1 21.1°C/ 21.1°C/ Indoor temperature DB/WB [70 °F/ ] [70 °F/ ] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 5.76...
Page 228
[ VIII Test Run Mode ] Heat source unit model Item PQRY-P120ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P104NU-G1 CMB-P108NU-GA1 21.1°C/ 21.1°C/ Indoor temperature DB/WB [70 °F/ ] [70 °F/ ] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 5.76 7.20 Heat source water flow rate...
Page 229
[ VIII Test Run Mode ] Heat source unit model Item PQRY-P168ZLMU-A PQRY-P192ZLMU-A Model name of BC controller CMB-P108NU-GA1 CMB-P108NU-GA1 21.1°C/ 21.1°C/ Indoor temperature DB/WB [70 °F/ ] [70 °F/ ] Heat source water temperature °C [ °F] 21.1[70] 21.1[70] 7.20 7.20 Heat source water flow rate...
Page 230
[ VIII Test Run Mode ] 4. 2-unit combination <PQRY> (1) Cooling only operation 2-unit combination Item PQRY-P144ZSLMU-A PQRY-P72ZLMU-A PQRY-P72ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 5.76 5.76...
Page 231
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P168ZSLMU-A PQRY-P96ZLMU-A PQRY-P72ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 232
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P192ZSLMU-A PQRY-P96ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 233
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P216ZSLMU-A PQRY-P120ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P1013NU-GA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 234
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P240ZSLMU-A PQRY-P120ZLMU-A PQRY-P120ZLMU-A Model name of BC controller CMB-P1013NU-GA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 235
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P288ZSLMU-A PQRY-P144ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
Page 236
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P312ZSLMU-A PQRY-P168ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
Page 237
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P336ZSLMU-A PQRY-P168ZLMU-A PQRY-P168ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 26.7°C/19.4°C [80 °F/67 °F] Heat source water temperature °C [ °F] 29.4 [85] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
Page 238
[ VIII Test Run Mode ] (2) Heating only operation 2-unit combination Item PQRY-P144ZSLMU-A PQRY-P72ZLMU-A PQRY-P72ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 239
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P168ZSLMU-A PQRY-P96ZLMU-A PQRY-P72ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 240
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P192ZSLMU-A PQRY-P96ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P108NU-GA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 241
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P216ZSLMU-A PQRY-P120ZLMU-A PQRY-P96ZLMU-A Model name of BC controller CMB-P1013NU-GA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 242
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P240ZSLMU-A PQRY-P120ZLMU-A PQRY-P120ZLMU-A Model name of BC controller CMB-P1013NU-GA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 5.76 5.76 Heat source water flow rate [1522] [1522] [25.4]...
Page 243
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P288ZSLMU-A PQRY-P144ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
Page 244
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P312ZSLMU-A PQRY-P168ZLMU-A PQRY-P144ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
Page 245
[ VIII Test Run Mode ] 2-unit combination Item PQRY-P336ZSLMU-A PQRY-P168ZLMU-A PQRY-P168ZLMU-A Model name of BC controller CMB-P1016NU-HA1 Indoor temperature DB/WB 21.1°C/- [70 °F/-] Heat source water temperature °C [ °F] 21.1 [70] 7.20 7.20 Heat source water flow rate [1902] [1902] [31.7]...
IX Troubleshooting [1] Error Code Lists ......................239 [2] Responding to Error Display on the Remote Controller..........243 [3] Investigation of Transmission Wave Shape/Noise............317 [4] Troubleshooting Principal Parts ..................320 [5] Refrigerant Leak ......................353 [6] Compressor Replacement Instructions................357 [7] Servicing the BC controller ....................
[ IX Troubleshooting ] IX Troubleshooting [1] Error Code Lists Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code 0403 4300 Serial communication error/Panel communication error 0404 Indoor unit EEPROM abnormality 1102 1202 Discharge temperature fault 1301...
Page 249
[ IX Troubleshooting ] Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code Backup operation [101] IPM error [104] Short-circuited IPM/Ground fault 4250 4350 [105] Overcurrent error due to short-circuited motor [106] Instantaneous overcurrent [107] Overcurrent...
Page 250
[ IX Troubleshooting ] Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code Liquid inlet temperature 5111 (TH11) Bypass outlet temperature 5112 Temperature sensor (TH12) fault LEV3 outlet temperature (BC controller) 5115 (TH15) LEV3 inlet temperature 5116...
Page 251
Overload protection Imax Current effective value error Current peak value error Temperature protec- INV board model (Arms) (Arms) (Apeak) tion TOL (°C) PQHY-P72ZLMU-A PQHY-P96ZLMU-A PQHY-P120ZLMU-A INV34Y PQHY-P144ZLMU-A PQHY-P168ZLMU-A PQHY-P192ZLMU-A Overload protection Imax Current effective value error Current peak value error...
[ IX Troubleshooting ] [2] Responding to Error Display on the Remote Controller 1. Error Code 0403 Serial communication error 2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor. Detail code 01: Between the control board and the INV board 3.
Page 253
[ IX Troubleshooting ] 1. Error Code 0404 A control communication reception error 2. Error definition and error detection method Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board. 3. Cause, check method and remedy Cause Check method and remedy Defective indoor controller board...
Page 254
[ IX Troubleshooting ] 1. Error Code 1102 Discharge temperature fault 2. Error definition and error detection method 1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the heat source unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
Page 255
[ IX Troubleshooting ] 1. Error Code 1301 Low pressure fault 2. Error definition and error detection method When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before start-up, the operation immediately stops. 3.
Page 256
[ IX Troubleshooting ] 1. Error Code 1302 High pressure fault 1 (Heat source unit) 2. Error definition and error detection method 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the heat source stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
Page 257
[ IX Troubleshooting ] 1. Error Code 1302 High pressure fault 2 (Heat source unit) 2. Error definition and error detection method If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an abnormal stop, and error code "1302"...
Page 258
[ IX Troubleshooting ] 1. Error Code 2000 Pump interlock error 2. Error definition and error detection method 1) This error is detected by the pump interlock circuit (TB8 3-4). 2) If it is detected that the pump interlock circuit (TB8 3-4) is open (first detection) during operation or immediately before startup, the heat source unit stops and goes into the 10-minute restart delay mode.
Page 259
[ IX Troubleshooting ] 1. Error Code 2134 Abnormal water temperature 2. Error definition and error detection method 1) If a water inlet pipe temperature (TH7) of 5°C[41ºF] or below OR 50°C[122ºF] or above is detected (first detection) during op- eration, the heat source unit stops, goes into the 3-minute restart delay mode, and automatically restarts after three minutes.
Page 260
[ IX Troubleshooting ] 1. Error Code 2135 Water heat exchanger freeze up 2. Error definition and error detection method 1) If either of the following conditions is detected (first detection) during operation, the heat source unit stops, goes into the 3- minute restart delay mode, and automatically restarts after three minutes.
Page 261
[ IX Troubleshooting ] 1. Error Code 2500 Drain sensor submergence (Models with a drain sensor) 2. Error definition and error detection method 1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
Page 262
[ IX Troubleshooting ] 1. Error Code 2500 Drain sensor submergence (Models with a float switch) 2. Error definition and error detection method 1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
Page 263
[ IX Troubleshooting ] 1. Error Code 2502 Drain pump fault (Models with a drain sensor) 2. Error definition and error detection method 1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water.
Page 264
[ IX Troubleshooting ] 1. Error Code 2502 Drain pump fault (Models with a float switch) 2. Error definition and error detection method 1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch. Submergence of the sensor When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water.
Page 265
[ IX Troubleshooting ] 1. Error Code 2503 Drain sensor (Thd) fault 2. Error definition and error detection method If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode.
Page 266
[ IX Troubleshooting ] 1. Error Code 2600 Water leakage 2. Cause, check method and remedy Check that water does not leak from the pipes in such as the humidifier. 1. Error Code 2601 Water supply cutoff 2. Cause, check method and remedy Cause Check method and remedy The water tank of the humidifier is empty.
Page 267
[ IX Troubleshooting ] 1. Error Code 4102 Open phase 2. Error definition and error detection method An open phase of the power supply (L1 phase, L2 phase) was detected at power on. The L3 phase current is outside of the specified range. The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
Page 268
[ IX Troubleshooting ] 1. Error Code 4106 <Transmission power supply fault error detail FF (Heat source unit)> 2. Error definition and error detection method Transmission power output failure 3. Cause 1) Wiring failure 2) Transmission power supply cannot output voltage because overcurrent was detected. 3) Voltage cannot be output due to transmission power supply problem.
Page 269
[ IX Troubleshooting ] 1. Error Code 4115 Power supply signal sync error 2. Error definition and error detection method The frequency cannot be determined when the power is switched on. 3. Cause, check method and remedy Cause Check method and remedy Power supply error Check the voltage of the power supply terminal block (TB1).
Page 270
[ IX Troubleshooting ] 1. Error Code 4121 Function setting error 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Heat source Dip switch setting error on the control board Check the SW6-1 setting on the control board. unit Connector connection error on the control Check that nothing is connected to the connector...
Page 271
[ IX Troubleshooting ] 1. Error Code 4124 Electric system not operate due to damper abnormality 2. Error definition and error detection method When the damper is not located at the designated position. 3. Cause, check method and remedy When the damper is not located at the designated position. 1) Check there is something that interferes the opening or closing movement of the damper.
Page 272
[ IX Troubleshooting ] 1. Error Code 4220 Abnormal bus voltage drop (Detail code 108) 2. Error definition and error detection method If Vdc 437V or less is detected during Inverter operation. (S/W detection) 3. Cause, check method and remedy (1) Power supply environment Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs.
Page 273
[ IX Troubleshooting ] 1. Error Code 4220 Abnormal bus voltage rise (Detail code 109) 2. Error definition and error detection method If Vdc 1010V is detected during inverter operation. 3. Cause, check method and remedy (1) Different voltage connection Check the power supply voltage on the power supply terminal block (TB1).
Page 274
[ IX Troubleshooting ] 1. Error Code 4230 Heatsink overheat protection 2. Error definition and error detection method When the heat sink temperature (THHS) remains at or above TOH is detected. Model PQHY 105°C [221°F] PQRY 100°C [212°F] 3. Cause, check method and remedy Cause Check method and remedy Air passage blockage...
Page 275
[ IX Troubleshooting ] 1. Error Code 4250 IPM error (Detail code 101) 2. Error definition and error detection method Overcurrent is detected by the overcurrent detection resistor (RSH) on the INV board. 3. Cause, check method and remedy Cause Check method and remedy Inverter output related Refer to IX [4] -6- (2) [1]-[5].
Page 276
[ IX Troubleshooting ] 1. Error Code 4250 Short-circuited IPM/Ground fault (Detail code 104) 2. Error definition and error detection method When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter. 3. Cause, check method and remedy Cause Check method and remedy Grounding fault compressor...
Page 277
[ IX Troubleshooting ] 1. Error Code 5101 Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit) 5102 Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit) 5103 Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)
Page 278
[ IX Troubleshooting ] 1. Error Code 5102 HIC bypass circuit outlet temperature sensor (TH2) fault (Heat source unit) 5103 Heat exchanger outlet temperature sensor (TH3) fault (Heat source unit) 5104 Discharge temperature sensor (TH4) fault (Heat source unit) 5105 Accumulator inlet temperature sensor (TH5) fault (Heat source unit) 5106 HIC circuit outlet temperature sensor (TH6) fault (Heat source unit)
Page 279
[ IX Troubleshooting ] 3. Cause, check method and remedy Cause Check method and remedy Thermistor failure Check thermistor resistance. Pinched lead wire Check for pinched lead wire. Torn wire coating Check for wire coating. A pin on the male connector is missing or Check connector.
Page 280
[ IX Troubleshooting ] 1. Error Code 5201 High-pressure sensor fault (63HS1) 2. Error definition and error detection method If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the heat source unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more.
Page 281
[ IX Troubleshooting ] 1. Error Code 5301 ACCT sensor fault (Detail code 115) 2. Error definition and error detection method When the formula "output current < 2.0 Arms" remains satisfied for 10 seconds while the inverter is in operation. 3.
Page 282
[ IX Troubleshooting ] 1. Error Code 5301 Open-circuited IPM/Loose ACCT connector (Detail code 119) 2. Error definition and error detection method Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup. 3. Cause, check method and remedy Cause Check method and remedy Inverter output wiring problem...
Page 283
[ IX Troubleshooting ] 1. Error Code 5701 Loose float switch connector 2. Error definition and error detection method Detection of the disconnected float switch (open-phase condition) during operation 3. Cause, check method and remedy (1) CN4F disconnection or contact failure Check for disconnection of the connector (CN4F) on the indoor unit control board.
Page 284
[ IX Troubleshooting ] 1. Error Code 6600 Address overlaps 2. Error definition and error detection method An error in which signals from more than one indoor units with the same address are received The address and attribute that appear on the remote controller indicate the controller that detected the error. 3.
Page 285
[ IX Troubleshooting ] 1. Error Code 6602 Transmission processor hardware error 2. Error definition and error detection method Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 286
[ IX Troubleshooting ] 1. Error Code 6603 Transmission line bus busy error 2. Error definition and error detection method Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 287
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 288
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 289
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 290
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 291
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 292
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 293
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 294
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 295
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 296
[ IX Troubleshooting ] 1. Error Code 6608 No response error 2. Error definition and error detection method When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect- When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 297
[ IX Troubleshooting ] 1. Error Code 6831 MA controller signal reception error (No signal reception) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 3 minutes. 3.
Page 298
[ IX Troubleshooting ] 1. Error Code 6832 MA remote controller signal transmission error (Synchronization error) 2. Error definition and error detection method MA remote controller and the indoor unit is not done properly. Failure to detect opening in the transmission path and unable to send signals Indoor unit : 3 minutes Remote controller : 6 seconds 3.
Page 299
[ IX Troubleshooting ] 1. Error Code 6833 MA remote controller signal transmission error (Hardware error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. An error occurs when the transmitted data and the received data differ for 30 times in a row. 3.
Page 300
[ IX Troubleshooting ] 1. Error Code 6834 MA controller signal reception error (Start bit detection error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 2 minutes. 3.
Page 301
[ IX Troubleshooting ] 1. Error Code 6841 A control communication synchronism not recover 2. Error definition and error detection method Indoor/heat source unit communication error (Transmitting error) (Heat source unit) Abnormal if "0" receiving is detected 30 times continuously though heat source controller circuit board has transmitted "1". Abnormal if heat source controller circuit board could not find blank of transmission path for 3 minutes.
Page 302
[ IX Troubleshooting ] 1. Error Code 6843 A control communication start bit detection error 2. Error definition and error detection method Indoor/heat source unit communication error (Signal receiving error) Abnormal if indoor controller board could not receive any signal normally for 6 minutes after turning the power on. Abnormal if indoor controller board could not receive any signal normally for 3 minutes.
Page 303
[ IX Troubleshooting ] 1. Error Code 6846 Start-up time over 2. Error definition and error detection method Start-up time over The unit cannot finish start-up process within 4 minutes after power on. 3. Cause, check method and remedy Cause Check method and remedy Contact failure of indoor/heat source unit connecting wire Check disconnection or looseness or polarity...
Page 304
[ IX Troubleshooting ] 1. Error Code 7100 Total capacity error 2. Error definition and error detection method The model total of indoor units in the system with one heat source unit exceeds limitations. 3. Error source, cause, check method and remedy, Error source Cause Check method and remedy...
Page 305
[ IX Troubleshooting ] 1. Error Code 7101 Capacity code setting error 2. Error definition and error detection method Connection of incompatible (wrong capacity code) indoor unit or heat source unit 3. Error source, cause, check method and remedy Error source Cause Check method and remedy Heat source...
Page 306
[ IX Troubleshooting ] 1. Error Code 7102 Wrong number of connected units 2. Error definition and error detection method The number of connected indoor units is "0" or exceeds the allowable value. 3. Error source, cause, check method and remedy Error source Cause Check method and remedy...
Page 307
[ IX Troubleshooting ] 1. Error Code 7105 Address setting error 2. Error definition and error detection method Erroneous setting of OC unit address Erroneous setting of BC controller address 3. Cause, check method and remedy Error source Cause Check method and remedy Heat source Erroneous setting of OC unit address Check that the heat source unit and BC con-...
Page 308
[ IX Troubleshooting ] 1. Error Code 7107 Port setting error 2. Error definition and error detection method The port with wrong number is connected to the indoor unit.The model total connected to the port is greater than the specifi- cation.
Page 309
[ IX Troubleshooting ] 1. Error Code 7110 Connection information signal transmission/reception error 2. Error definition and error detection method The given indoor unit is inoperable because it is not properly connected to the heat source unit in the same system. 3.
Page 310
[ IX Troubleshooting ] 1. Error Code 7113 Function setting error (improper connection of CNTYP) 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Heat source Wiring fault (Detail code 15) unit Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
Page 311
[ IX Troubleshooting ] 1. Error Code 7117 Model setting error 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Heat source Wiring fault (Detail code 15) unit Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
Page 312
[ IX Troubleshooting ] 1. Error Code 7130 Incompatible unit combination 2. Error definition and error detection method The check code will appear when the indoor units with different refrigerant systems are connected. 3. Error source, cause, check method and remedy Error source Cause Check method and remedy...
Page 313
[ IX Troubleshooting ] -1- Troubleshooting according to the remote controller malfunction or the external input error In the case of MA remote controller 1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start run- ning.(Power indicator does not appear on the screen.) (1) Cause...
Page 314
[ IX Troubleshooting ] In the case of MA remote controller 2. Phenomena When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off, and the display lights out immediately, and the unit stops. (1) Cause 1) The power for the M-NET transmission line is not supplied from the heat source unit.
Page 315
[ IX Troubleshooting ] In the case of MA remote controller 3. Phenomena "HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.) (1) Cause 1) The power for the M-NET transmission line is not supplied from the heat source unit.
Page 316
[ IX Troubleshooting ] Flow chart Even if the operation button on the remote controller is pressed, the indoor and the heat source units do not start running. - 307 - HWE15150...
Page 317
[ IX Troubleshooting ] In case of ME remote controller 1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running. (Power indicator does not appear on the screen.) (1) Cause 1) The power for the M-NET transmission line is not supplied from the indoor unit.
Page 318
[ IX Troubleshooting ] In case of ME remote controller 2. Phenomena When the remote controller operation SW is turned on, a temporary operation display is indicated, and the display lights out immediately. (1) Cause 1) The power is not supplied to the indoor unit. The main power of the indoor unit (AC208/230V) is not on.
Page 319
[ IX Troubleshooting ] In case of ME remote controller 3. Phenomena "HO" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. (1) Cause Without using MELANS 1) Heat source unit address is set to "00" 2) A wrong address is set.
Page 320
[ IX Troubleshooting ] In case of ME remote controller 4. Phenomena "88" appears on the remote controller when the address is registered or confirmed. (1) Cause, check method and remedy Cause Check method and remedy An error occurs when the address is registered or con- firmed.
Page 321
[ IX Troubleshooting ] Both for MA remote controller and ME remote controller 1. Phenomena Although cooling operation starts with the normal remote controller display, the capacity is not enough (1) Cause, check method and remedy Cause Check method and remedy Compressor frequency does not rise sufficiently.
Page 322
[ IX Troubleshooting ] Cause Check method and remedy Indoor unit LEV malfunction Refer to the page of LEV troubleshooting ([4] -4- ). Insufficient refrigerant flows due to LEV malfunc- tion (not enough opening) or protection works and compressor frequency does not rise due to pres- sure drop.
Page 323
[ IX Troubleshooting ] 2. Phenomena Although heating operation starts with the normal remote controller display, the capacity is not enough. (1) Cause, check method and remedy Cause Check method and remedy Compressor frequency does not rise sufficiently. Check pressure difference between the detected pressure by the pressure sensor and the actual Faulty detection of pressure sensor.
Page 324
[ IX Troubleshooting ] Cause Check method and remedy Indoor unit LEV malfunction Refer to the page of LEV troubleshooting Insufficient refrigerant flows due to LEV malfunction ( [4] -4- ). (not enough opening). Temperature reading error on the indoor unit piping Check the thermistor.
Page 325
[ IX Troubleshooting ] 3. Phenomena Heat source unit stops at times during operation. (1) Cause, check method and remedy Cause Check method and remedy The first stop is not considered as an error, as the Check the mode operated in the past by displaying unit turns to anti-restart mode for 3 minutes as a pre- preliminary error history on LED display with SW4.
[ IX Troubleshooting ] [3] Investigation of Transmission Wave Shape/Noise 1. M-NET transmission Control is performed by exchanging signals between the heat source unit and the indoor unit (ME remote controller) through M-NET transmission. Noise interference on the transmission line will interrupt the normal transmission, leading to erroneous operation.
Page 327
[ IX Troubleshooting ] (3) Check method and remedy 1) Measures against noise Check the followings when noise exists on the wave or the errors described in (1) occur. Error code definition Remedy Check that the wiring 1. The transmission line and Isolate the transmission line from the power line (5cm [1-31/32"] or work is performed ac- the power line are not...
Page 328
[ IX Troubleshooting ] 2. MA remote controller transmission The communication between the MA remote controller and the indoor unit is performed with current tone burst. (1) Symptoms caused by noise interference on the transmission line If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.
[ IX Troubleshooting ] [4] Troubleshooting Principal Parts -1- High-Pressure Sensor (63HS1, PS1, PS3) 1. Compare the pressure that is detected by the high pressure sensor, and the high-pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW4 (when SW6-10 is set to OFF)) as shown in the figure below, the pressure as measured by the high-pressure sensor appears on the LED1 on the control board.
Page 330
[ IX Troubleshooting ] -2- Low-Pressure Sensor (63LS) 1. Compare the pressure that is detected by the low pressure sensor, and the low pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW4 (when SW6-10 is set to OFF)) as shown in the figure below, the pressure as measured by the low-pressure sensor appears on the LED1 on the control board.
Page 331
[ IX Troubleshooting ] -3- Solenoid Valve Check whether the output signal from the control board and the operation of the solenoid valve match. Setting the self-diagnosis switch (SW4) as shown in the figure below causes the ON signal of each relay to be output to the LED's. Each LED shows whether the relays for the following parts are ON or OFF.
Page 332
[ IX Troubleshooting ] Refrigerant Circuit diagram <PQHY> Solenoid valve block SV4a SV4b SV4d SV7a SV7b Water heat exchanger (plate type) THINV LEVINV Water circuit INV-HEX LEV7 63LS LEV6 LEV1 Solenoid valve block(three compartments) 1 is located behind 3 - 323 - HWE15150...
Page 333
[ IX Troubleshooting ] Refrigerant Circuit diagram <PQRY> Solenoid valve block SV4a SV4b SV4d SV7a SV7b Water heat exchanger (plate type) THINV LEVINV Water circuit INV-HEX ST13 LEV7 CV2a CV5a LEV6 63LS SV6a CV3a ST18 Solenoid valve block(three compartments) 1 is located behind 3 (4) In the case of SV9 (Bypass valve) (PQRY only) This solenoid valve opens when energized (when the relay is on) This valve turns on when the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation...
Page 334
[ IX Troubleshooting ] -4- LEV LEV operation The LEV on the indoor unit and LEV1, LEVINV, LEV6, and LEV7 on the heat source unit are driven by the pulse signal from the circuit board on the indoor and heat-source units and are controlled by a stepping motor (1) Indoor LEV and heat source LEV (LEV6,LEV7), and BC controller LEV (LEV1, LEV2, LEV3) The valve opening changes according to the number of pulses.
Page 335
[ IX Troubleshooting ] 3) Pulse signal output and valve operation Output pulses change in the following orders when the Output Output state Valve is closed; 1 (phase) number Valve is open; *1. When the LEV opening angle does not change, all the output phases will be off.
Page 336
[ IX Troubleshooting ] (2) Heat source LEV (LEV1,LEVINV) The valve opening changes according to the number of pulses. 1) Connections between the heat source control board and LEV Control board DC 12V Brown Drive circuit Blue Orange Yellow White 2) Pulse signal output and valve operation Output state Output pulses change in the following orders when the...
Page 337
[ IX Troubleshooting ] (3) Judgment methods and possible failure mode The specifications of the heat source unit (heat source LEV), indoor unit (indoor LEV),and BC controller (BC controller LEV) differ.Therefore, remedies for each failure may vary. Check the remedy specified for the appropriate LEV as indicated in the right column.
Page 338
[ IX Troubleshooting ] (4) Heat source unit LEV (LEV1,LEVINV) coil removal procedure 1) LEV component As shown in the figure, the heat source LEV is made in such a way that the coils and the body can be separated. Body Coils Stopper...
Page 339
[ IX Troubleshooting ] (5) Heat source unit LEV (LEV6,LEV7) coil removal procedure 1) Components The heat source unit LEV consists of a coil and a valve body that can be separated from each other. Body Stopper Coil Lead wire 2) Removing the coil Securely hold the LEV at the bottom (as indicated by A in the figure), and turn the coil.
Page 340
[ IX Troubleshooting ] (6) Indoor unit LEV, BC controller LEV coil removal procedure Motor Driver Locknut Bellows Valve assembling Refrigerant Circuit Valve body side Orifice Notes on the procedure 1) Do not put undue pressure on the motor. 2) Do not use motors if dropped. 3) Do not remove the cap until immediately before the procedure.
Page 341
[ IX Troubleshooting ] Replacement procedure 1) Stop the air conditioner. After checking that the air conditioner is stopped, turn off the power of the heat source unit. 2) Prepare two spanners. Hold the valve body with one spanner and loosen the locknut with another one. Turning the locknut counter-clockwise from motor side view can loosen it.
Page 342
[ IX Troubleshooting ] -5- Troubleshooting Principal Parts of BC Controller 1. Pressure sensor Troubleshooting flow chart for pressure sensor START Note 1 Check whether the pressure sensor or the connectors of P1 and P3 are connected, properly Repair the fault. Operating at the moment? Note 2 On the self-diagnosis monitor, measure...
Page 343
[ IX Troubleshooting ] 1) BC controller: Phenomena when the pressure sensor is connected wrongly (reverse connection of P1 and P3) to the board. Symptoms Cooling-only Cooling-main Heating only Heating main Non-cooling Indoor heating SC small Normal Non-cooling SC11 large SC11 large SC11 large Indoor heating SC small...
Page 344
[ IX Troubleshooting ] 2. Temperature sensor Troubleshooting instructions for thermistor START Note 1 Pull out the thermistor connector in trouble from the board. Note 2 Measure the temperature of the thermistor in trouble. (actual measurement value) Note 2 Check the thermistor resistor. Compare the temperature corresponding to the resistance measured by the thermistor and the temperature measured by a commercially...
Page 345
[ IX Troubleshooting ] 1) For the connectors on the board, TH11 and TH12 are connected to CN10, and TH15 and TH16 are connected to CN11. Dis- connect the connector in trouble, and check the sensor of each number. Pull out the sensor connector from the I/O board, Do not pull the sensor by holding the lead wire. Measure the resistance with such as a tester.
Page 346
[ IX Troubleshooting ] 3. Troubleshooting flow chart for LEV Solenoid valve (1) LEV No cooling capacity No heating capacity Note 1 Check whether the electric expansion valve and the solenoid valve connector are not disconnected or not loose. Repair the fault. Fault is found.
Page 347
[ IX Troubleshooting ] 1) BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the board. Phenomena Cooling-only Cooling-main Heating only Heating main Non-cooling Non-cooling and non-heating Indoor heating SC small Non-cooling SH12 small, SC11 small SH12 small, SC11 small PHM large Indoor heating SC small...
Page 348
[ IX Troubleshooting ] Self-diagnosis LED Measurement data Symbol SW4 setting value LEV1 opening 9 10 LEV2 opening 9 10 G, GA, HA LEV3 opening (Standard 9 10 / main) BC controller bypass SH12 outlet superheat 9 10 BC controller intermediate SC16 part subcool 9 10...
Page 349
[ IX Troubleshooting ] Troubleshooting flow chart for solenoid valve body Start Check for pins not fully inserted on the connector and check the colors of the lead wires visually. Intermediate connector Control board When LEV is fully closed : tick sound When LEV is fully open : no sound Brown Brown...
Page 350
[ IX Troubleshooting ] (2) Solenoid valve (SVA, SVB, SVC) Faulty judgment of solenoid valve Stop the operation of the applied BC remote controller system. Stop the operation Check whether the wire to the solenoid valve is not connected wrongly, or the connector is not loose. No fault Repair the fault.
Page 351
[ IX Troubleshooting ] Check whether the BC board output signal corresponds with the solenoid valve operation correspond. 1) SVA, SVB, SVC SVA, SVB, and SVC turn on or off according to the indoor unit operation mode. Mode Cooling Heating Stopped Defrost Port...
Page 352
[ IX Troubleshooting ] 4. BC controller transformer BC controller control board CNTR CN03 White Normal Abnormal CNTR(1)-(3) about 58 ohm. Open-phase or shorting CN03(1)-(3) about 1.6 ohm. * Before measuring the resistance, pull out the connector. - 343 - HWE15150...
Page 353
[ IX Troubleshooting ] -6- Inverter Replace only the compressor if only the compressor is found to be defective.(Overcurrent will flow through the inverter if the compressor is damaged, however, the power supply is automatically cut when overcurrent is detected, protecting the inverter from damage.
Page 354
[ IX Troubleshooting ] Error display/failure condition Measure/inspection item Inverter related errors Check the details of the inverter error in the error log in X LED Monitor 4250, 4220, 4230, 4240,4260, 5301, 0403 Display on the Heat source Unit Board. Take appropriate measures to the error code and the error details in ac- cordance with IX.
Page 355
[ IX Troubleshooting ] (2) Inverter output related troubles Items to be checked Phenomena Remedy Remove power sup- Overcurrent error Replace the INV board. Check the ply. Error code: 4250 INV board er- Detail code: No. 101, 104, 105, ror detection 106, and 107 circuit.
Page 356
[ IX Troubleshooting ] Items to be checked Phenomena Remedy Put the heat source unit into Overcurrent-related problems oc- a. Check items [1] through Check whether operation. cur immediately after compressor [3] for problems. the inverter is Check the inverter output volt- startup.
Page 357
[ IX Troubleshooting ] (3) Trouble treatment when the main power breaker is tripped Items to be checked Phenomena Remedy Check the breaker capacity. Use of a non-specified break- Replace it with a specified breaker. Perform Meg check between the Zero to several ohm, or Meg Check each part and wiring.
Page 358
[ IX Troubleshooting ] (5) Simple checking procedure for individual components of main inverter circuit Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. Part name Judgment method IGBT module...
Page 360
[ IX Troubleshooting ] Control Circuit (1) Control power source function block Power source system (AC 230 / 575 V) Control system (DC 5 ~ 30 V) INV board Noise filter Smoothing capacitor Inverter Compressor Noise filter Rectifier AC 575V Fuse Terminal block for Inverter drive...
Page 361
[ IX Troubleshooting ] (2) Troubleshooting transmission power circuit of heat source unit Check the voltage at the indoor/heat source transmission terminal block (TB3) of heat source unit. Check whether the transmission line is disconnected, DC 24 ~ 30 V check for contact failure, and repair the problem.
[ IX Troubleshooting ] [5] Refrigerant Leak For information about how to set SW4 on the control board, refer to the following page(s). 1. Leak spot: In the case of extension pipe for indoor unit (Cooling season)<PQHY> 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the liquid service valve (BV2) inside the heat source unit while the compressor is being stopped.
Page 363
[ IX Troubleshooting ] (3) Stop all the indoor units, and stop the compressor. 1) Set SW4 No. 769 (SW6-10: ON) on the control board of the heat-source unit from ON to OFF to stop all indoor units and the compressors.
Page 364
[ IX Troubleshooting ] 5. Leak spot: In the case of extension pipe for indoor unit (Cooling season)<PQRY> 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the high-pressure side refrigerant service valve (BV2) on the heat source unit while the compressor is being stopped.
Page 365
[ IX Troubleshooting ] 7. Leak spot: In the case of extension pipe for indoor unit (Heating season)<PQRY> (1) Run all the indoor units in heating test run mode. 1) Set SW4 No. 769 (SW6-10: ON) on the control board of the heat-source unit to ON to operate all indoor units in the test-run mode.
[ IX Troubleshooting ] [6] Compressor Replacement Instructions 1. Compressor Replacement Instructions Follow the procedures below (Steps 1 through 5) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor. 1. Remove the service panel (front panels). 2.
Page 367
[ IX Troubleshooting ] Acoustic insulation on the compressor Thermal insulation on the accumulator Remove the acoustic insulation from the compressor. Remove or protect the wiring around the compressor and the thermal insulation on the accumulator, unbraze the pipe from the compressor, and replace the compressor.
Page 368
[ IX Troubleshooting ] Follow the procedures below (Steps 1 through 4) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor. Service panels 1. Remove the front service panels (top and bottom). 2.
Page 369
[ IX Troubleshooting ] 1. Explained below are procedures for replacing water-cooled heat exchanger assembly parts. 1. Applicable models • PQHY-P72, 96, 120ZLMU-A • PQRY-P72, 96, 120ZLMU-A 2. Parts to be serviced The procedures apply to the service parts listed in the table below. Parts to be replaced Required materials Qty.
Page 370
[ IX Troubleshooting ] 2) Remove all wiring from the unit to the control box, 6) Remove the top panel. 4) Remove the rear panel. and remove the control box from the unit. 7) Remove the frame FU at above the control box and on the rear at the top.
Page 371
[ IX Troubleshooting ] 1. Explained below are procedures for replacing water-cooled heat exchanger assembly parts. 2. Applicable models • PQHY-P144, P168, P192ZLMU-A 3. Service parts list 4. Procedures *Precautions for starting replacement • Check that the main power supply is OFF. •...
Page 372
[ IX Troubleshooting ] 2) To remove the Frame M After removing Frame M. Remove the screw. (total 4 places) Turn FRAME M Right Side, Pull out. 3) To remove the Water Heat Exchanger and Front Panel Remove the screw (total 2 places) and pipe cover, and then remove the Front Panel according to the 1-5 procedures on the figure below.
Page 373
[ IX Troubleshooting ] 1. Explained below are procedures for replacing water-cooled heat exchanger assembly parts. 2. Applicable models • PQRY-P144, P168, P192ZLMU-A 3. Service parts list 4. Procedures *Precautions for starting replacement • Check that the main power supply is OFF. •...
Page 374
[ IX Troubleshooting ] 2) To remove the Frame M After removing Frame M. Remove the screw. (total 4 places) Turn Frame M Right Side, Pull out. 3) To remove the Water Heat Exchanger and Front Panel Remove the screw (total 2 places) , pipe cover and cable tie (total 2 places), and then remove the Front Panel according to the 1-5 procedures on the figure below.
[ IX Troubleshooting ] [7] Servicing the BC controller 1. Service panel *Special care must be taken when replacing heavy parts. Work procedure Explanatory figure 1) Remove the two lock nuts on the control box, loosen the other two, and remove the control box. 2) Remove the three fixing screws on the service panel, Ceiling panel Loosen...
Page 376
[ IX Troubleshooting ] 3. Thermistor (liquid pipe/gas pipe temperature detection) *Special care must be taken when replacing heavy parts. Work procedure Explanatory figure (1) Remove the service panel. 1) For TH11, TH12, and TH15, refer to 1. 1) - 2). 2) For TH16, refer to 1.
Page 377
[ IX Troubleshooting ] 5. LEV Work procedure Explanatory figure (1) Remove the service panel.(Refer to 1. 1) - 3) (2) Replace the LEV in trouble. LEV3 LEV1 Secure enough service space in the ceiling for welding operation, and conduct the work carefully.If required, dismount the unit from the ceiling, and conduct the work.
[ IX Troubleshooting ] [8] Troubleshooting Using the Heat source Unit LED Error Display If the LED error display appear as follows while all the SW4 switches and SW6-10 are set to OFF, check the items under the ap- plicable item numbers below. 1.
Page 379
[ IX Troubleshooting ] - 370 - HWE15150...
[ X LED Monitor Display on the Heat source Unit Board ] X LED Monitor Display on the Heat source Unit Board [1] How to Read the LED on the Service Monitor 1. How to read the LED By setting the DIP SW 4-1 through 4-10 (SW6-10: OFF) (Switch number 10 is represented by 0), the operating condition of the unit can be monitored on the service monitor.
Page 383
[ X LED Monitor Display on the Heat source Unit Board ] How to convert HP capacity to Model name /Ton HP capacity is the capacity of outdoor unit that is shown on LED display at initial setting. Please refer to the following table to convert from HP capacity to Model name/Ton. Model Model P240...
Page 384
[ X LED Monitor Display on the Heat source Unit Board ] - 375 - HWE15150...
Page 385
[ X LED Monitor Display on the Heat source Unit Board ] - 376 - HWE15150...
Page 386
[ X LED Monitor Display on the Heat source Unit Board ] - 377 - HWE15150...
Page 387
[ X LED Monitor Display on the Heat source Unit Board ] - 378 - HWE15150...
Page 388
[ X LED Monitor Display on the Heat source Unit Board ] - 379 - HWE15150...
Page 389
[ X LED Monitor Display on the Heat source Unit Board ] - 380 - HWE15150...
Page 390
[ X LED Monitor Display on the Heat source Unit Board ] - 381 - HWE15150...
Page 391
[ X LED Monitor Display on the Heat source Unit Board ] - 382 - HWE15150...
Page 392
[ X LED Monitor Display on the Heat source Unit Board ] - 383 - HWE15150...
Page 393
[ X LED Monitor Display on the Heat source Unit Board ] - 384 - HWE15150...
Page 394
[ X LED Monitor Display on the Heat source Unit Board ] - 385 - HWE15150...
Page 395
[ X LED Monitor Display on the Heat source Unit Board ] - 386 - HWE15150...
Page 396
[ X LED Monitor Display on the Heat source Unit Board ] - 387 - HWE15150...
Page 397
[ X LED Monitor Display on the Heat source Unit Board ] - 388 - HWE15150...
Page 398
[ X LED Monitor Display on the Heat source Unit Board ] - 389 - HWE15150...
Page 399
[ X LED Monitor Display on the Heat source Unit Board ] - 390 - HWE15150...
Page 400
[ X LED Monitor Display on the Heat source Unit Board ] - 391 - HWE15150...
Page 401
[ X LED Monitor Display on the Heat source Unit Board ] - 392 - HWE15150...
Page 402
[ X LED Monitor Display on the Heat source Unit Board ] - 393 - HWE15150...
Page 403
[ X LED Monitor Display on the Heat source Unit Board ] - 394 - HWE15150...
Page 404
[ X LED Monitor Display on the Heat source Unit Board ] - 395 - HWE15150...
Page 405
[ X LED Monitor Display on the Heat source Unit Board ] - 396 - HWE15150...
Page 406
[ X LED Monitor Display on the Heat source Unit Board ] - 397 - HWE15150...
Page 407
[ X LED Monitor Display on the Heat source Unit Board ] - 398 - HWE15150...
Page 408
[ X LED Monitor Display on the Heat source Unit Board ] - 399 - HWE15150...
Page 409
[ X LED Monitor Display on the Heat source Unit Board ] - 400 - HWE15150...
Page 410
[ X LED Monitor Display on the Heat source Unit Board ] - 401 - HWE15150...
Page 411
[ X LED Monitor Display on the Heat source Unit Board ] - 402 - HWE15150...
Page 412
[ X LED Monitor Display on the Heat source Unit Board ] - 403 - HWE15150...
Page 413
[ X LED Monitor Display on the Heat source Unit Board ] - 404 - HWE15150...
Page 414
[ X LED Monitor Display on the Heat source Unit Board ] - 405 - HWE15150...
Page 415
[ X LED Monitor Display on the Heat source Unit Board ] - 406 - HWE15150...
Page 416
[ X LED Monitor Display on the Heat source Unit Board ] - 407 - HWE15150...
Page 417
[ X LED Monitor Display on the Heat source Unit Board ] - 408 - HWE15150...
Page 418
[ X LED Monitor Display on the Heat source Unit Board ] - 409 - HWE15150...
Page 419
[ X LED Monitor Display on the Heat source Unit Board ] - 410 - HWE15150...
Page 420
Service Handbook Model PQHY-P72, P96, P120, P144, P168, P192ZLMU-A PQHY-P144, P168, P192, P216, P240, P288, P312, P336, P360ZSLMU-A PQRY-P72, P96, P120, P144, P168, P192ZLMU-A PQRY-P144, P168, P192, P216, P240, P288, P312, P336ZSLMU-A www.MitsubishiElectric.com New publication effective Feb. 2016 Specifications subject to change without notice HWE15150...