Some features and functions described in this document depend on the firmware loaded into the device and host software. Make sure that the controller is updated to the firmware version provided with the host system. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Figure 3.1: The extension AMC2-16IOE The API-AMC2-16IOE has 16 analog inputs and 16 relay outputs. The analog inputs can be wired with potential-free contacts, such as door or relay contacts. The relay outputs can be actively connected with the internal voltage, as well as used potential free.
DIL switch for setting the board address. Jumper: Equalization of potential between different systems and earth ground (shield) for the extension module bus. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
In the example, the power is supplied via the controller. If necessary, it is also possible to use a separate power supply for an extension. Figure 3.4: System overview Host computer Access Modular Controller Card reader Communication and power supply Extension Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
For information on how to install the device in an enclosure, refer to the separate instruction manual of the enclosure AEC-AMC2-UL01 or AEC-AMC2-UL02. After installing the device, keep the door of the enclosure closed. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Push down the extension until the lower edge snaps out of the mounting rail [1]. Pull the lower end of the extension from the mounting rail [2]. Figure 4.2: Unmounting the AMC2 device on a mounting rail Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
The extension’s case consists of a top cover mounted with a two-point snap-in closure on a chassis. To open the case, push down the two snap-ins with a screwdriver, then swing the cover down. Figure 4.3: Opening the AMC2-16IOE case 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Insert the hooks on the lower edge of the front cover into the lugs on lower edge of the plastic back cover [1]. Ensure that the BOSCH logo is not upside-down. The upper edge of the front cover now aligns with the two-point snap-in closures on the upper edge of the back cover [2], and may thus be clicked gently into place.
These specifications apply to power supply, relay outputs, and extension interface. Regarding inputs, specific voltage-drop values need to be taken into account. Refer to chapter Connecting analog input devices, page 24. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
If the devices have their own power supplies, the shielding is applied to one side only. The free end should be insulated to avoid inadvertent connections. If one device is fed power by another, the cable shielding should be applied to both sides. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Jumper A connects the internal ground of the controller to the RS-485 ground of the slave interface. Only set jumper A (A2) if the controller powers all other peripheral devices directly connected to it. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Connect an external power supply (10 VDC - 30 VDC) to the extension at pin 1 (positive) and pin 3 (0 V) of the pluggable screw connector. Bosch recommends using the Bosch APS-PSU-60 power supply unit. This power supply can also be used as an Uninterruptible Power Supply (UPS) when using the appropriate batteries.
PSU + controller + 60VA 3 x 5VA 45VA 15VA 2 x extension PSU + controller + 60VA 4 x 5VA 40VA 10VA 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Page 19
This leaves 55VA to support external devices. 25VA of these 55VA can be used for constant load (e.g. a card reader) leaving 30VA for occasional peak usage (e.g. a door opener). Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
When configuring the system, ensure that the order of boards in the access control software corresponds to the addresses set when using this switch. Figure 4.11: Location of the selector for host settings Address DIP switches none 1 (delivery status) Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
(e.g. Wieland flare move) on the outputs. - Note that the coupling relays must be selected according to the supply voltage (12 V, 24 V) of the controller. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Page 23
When you use the recovery diode, make sure to use it in the reverse direction. 14 13 12 11 10 14 13 E 1: E 2: Figure 4.15: Location of relay output jumpers (bottom side) Delivery status Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
The controller can also detect the wiring conditions ‘short circuit’ and ‘broken’, and hence trigger an alarm if the appropriate devices are connected. Figure 4.17: Circuit diagram AMC2 analog input Monitoring / door contact Resistor parallel (R Resistor serial (R Broken wire Short circuit 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Page 25
Table 4.2: Maximum values of cable resistance per used resistor combination in Ohm Notice! We recommend using serial resistors (R ) no higher than 5K6 in order to obtain clear measurements. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Since the extension does not have its own display, the status information of the input and output signals is shown on the display of the connected controller. For further information, refer to the installation manual of the respective controller. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
The enclosures AMC2-UL01 (for one device) or AMC2-UL02 (for two devices). – For every enclosure, a power supply Bosch APS-PSU-60 is necessary, and must be located in the same room as the connected AMC2 device. Recommended maximum distance between power supply unit and AMC2 is 3 m (9.84 ft).
It may not be used for connection to readers or other accessories. – All units are to be powered by the Bosch APS-PSU-60 power supply for UL installations. The power supply must be located in the same room as the connected AMC2 device.
Page 29
HVAC system. The standby power system for the HVAC system may be supplied by an engine driven generator alone. A standby battery is not required to be used. For UL compliance, use only UL Listed readers. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Page 30
| UL requirements Extension board with 16-input 16-output AMC2 extension Figure 5.1: Example of mountings with extensions Position Description Position Description Black / brown Battery connection Earth cable Blue R-485 extension connection 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
10 VDC to 30 VDC, maximum of 3 A Power consumption 5 VA Total combined output 3 A @ 10 VDC - 12 VDC 2.5 A @ 24 VDC - 30 VDC Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Door opener or signal is not – Check the display of the activated. controller to make sure the signal is set. Check the configuration settings within AMS or ACE system. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Page 33
Extension board with 16-input 16-output Troubleshooting | en Problem Cause Solution – Make sure that the internal power supply jumpers are set correctly. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Upon completion of service or repair work on the controller, ask the service technician to perform safety checks to ensure that the controller operates properly. After sales support For more information, visit www.boschsecurity.com/xc/en/support/. 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
The controller has a CF card as storage medium. When disposing of the controller, ensure that the CF card or the complete controller is destroyed or disposed of in accordance with the Local Data Protection Ordinance. Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
IP30 RoHS Compliant Capacity Number of analog inputs Number of relay outputs Connectivity Extension interface RS485 Electrical Input voltage (VDC) 10 VDC – 30 VDC Power consumption (VA) 5 VA 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Power supply (0V) UPS (power good signal) - AC UPS (power good signal) - Battery UPS (power good signal) - DC UPS (power good signal) - Common Table 10.3: Power supply Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Page 38
Relay Output, normally closed Table 10.5: Relay output Power supply (10V - 30V) Power supply GND Shield Data RxTx+ Data RxTx- Table 10.6: Extension module bus Tamper Contact Tamper Contact Table 10.7: External tamper contact 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...
Page 39
Troubleshooting – Repair & Exchange – Product Security Bosch Building Technologies Academy Visit the Bosch Building Technologies Academy website and have access to training courses, video tutorials and documents: www.boschsecurity.com/xc/en/support/training/ Bosch Security Systems B.V. 2024-01 | V02 | Installation manual...
Page 40
| Appendices Extension board with 16-input 16-output 2024-01 | V02 | Bosch Security Systems B.V. Installation manual...