Fujitsu AIRSTAGE ASEG09KETF Design & Technical Manual
Fujitsu AIRSTAGE ASEG09KETF Design & Technical Manual

Fujitsu AIRSTAGE ASEG09KETF Design & Technical Manual

Wall mounted type
Hide thumbs Also See for AIRSTAGE ASEG09KETF:

Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASEG07KETF
ASEG09KETF
ASEG12KETF
ASEG14KETF
OUTDOOR
AOEG07KETA
AOEG09KETA
AOEG12KETA
ASEG07KETF-B
ASEG09KETF-B
ASEG12KETF-B
ASEG14KETF-B
AOEG14KETA
DR_AS194ES_03
2023.12.18

Advertisement

loading

Summary of Contents for Fujitsu AIRSTAGE ASEG09KETF

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASEG07KETF ASEG07KETF-B ASEG09KETF ASEG09KETF-B ASEG12KETF ASEG12KETF-B ASEG14KETF ASEG14KETF-B OUTDOOR AOEG07KETA AOEG14KETA AOEG09KETA AOEG12KETA DR_AS194ES_03 2023.12.18...
  • Page 2 App Store is a service mark of Apple Inc., registered in the U.S. and other countries. IOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license. Copyright © 2023 Fujitsu General Limited. All rights reserved.
  • Page 3 CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Wireless LAN control ..................4 2-1. System requirement......................4 2-2. Wireless LAN function list ....................5 3. Dimensions....................6 3-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF- B, ASEG09KETF-B, ASEG12KETF-B, and ASEG14KETF-B ..........6 4. Wiring diagrams ....................8 4-1.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............49 1. Specifications....................50 2. Dimensions....................51 2-1. Models: AOEG07KETA, AOEG09KETA, and AOEG12KETA ........51 2-2. Model: AOEG14KETA ....................52 3. Installation space ..................53 3-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA....53 4. Refrigerant circuit ..................56 4-1. Models: AOEG07KETA, AOEG09KETA, and AOEG12KETA ........56 4-2.
  • Page 5 Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASEG07KETF ASEG09KETF ASEG12KETF ASEG14KETF ASEG07KETF-B ASEG09KETF-B ASEG12KETF-B ASEG14KETF-B...
  • Page 6 1. Specifications Wall mounted Type Inverter, Heat pump ASEG07KETF ASEG09KETF ASEG12KETF ASEG14KETF Model name ASEG07KETF-B ASEG09KETF-B ASEG12KETF-B ASEG14KETF-B Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Rated Btu/h 6,800 8,500 11,600 14,300 Cooling 0.9—3.0 0.9—3.2...
  • Page 7 Wall mounted Type Inverter, Heat pump ASEG07KETF ASEG09KETF ASEG12KETF ASEG14KETF Model name ASEG07KETF-B ASEG09KETF-B ASEG12KETF-B ASEG14KETF-B Remote controller Wireless (Option: Wired, Mobile app* [AIRSTAGE Mobile]) NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB. –...
  • Page 8 After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 4 - 2-1. System requirement...
  • Page 9 2-2. Wireless LAN function list NOTE: To use the wireless LAN control, user registration in advance and access to the wireless home network are required. Attached Wireless Item Mobile app Remote Controller Air conditioning Operation on/off ○ ○ control function Operation mode setting ○...
  • Page 10 3. Dimensions 3-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF-B, ASEG09KETF-B, ASEG12KETF-B, and ASEG14KETF-B Unit: mm 373.5 417.5 (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 6 - 3-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF- 3.
  • Page 11 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 12 4. Wiring diagrams 4-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF-B, ASEG09KETF-B, ASEG12KETF-B, and ASEG14KETF-B - 8 - 4-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF- 4. Wiring diagrams B, ASEG09KETF-B, ASEG12KETF-B, and ASEG14KETF-B...
  • Page 13 5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1.
  • Page 14 ¢ Models: ASEG14KETF and ASEG14KETF-B Indoor temperature °CDB °CWB °CDB 3.77 3.49 0.67 4.11 3.62 0.66 4.34 3.70 0.66 4.57 3.79 0.65 4.85 3.86 0.65 5.03 3.95 0.65 5.37 4.08 0.64 3.59 3.39 0.88 3.92 3.51 0.88 4.14 3.60 0.87 4.35 3.68 0.87...
  • Page 15 5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Models: ASEG07KETF and ASEG07KETF-B Indoor temperature °CDB °CWB 1.85 0.95 1.83 0.97 1.81 0.98 1.80 1.02 1.78 1.04 2.22 1.00 2.20 1.02 2.17 1.03 2.16 1.07...
  • Page 16 6. Fan performance 6-1. Air velocity distributions ¢ Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG07KETF-B, ASEG09KETF-B, and ASEG12KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 17 ¢ Models: ASEG14KETF and ASEG14KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 18 6-2. Airflow ¢ Models: ASEG07KETF and ASEG07KETF-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 14 - 6-2. Airflow 6. Fan performance...
  • Page 19 ¢ Models: ASEG09KETF and ASEG09KETF-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 15 - 6-2. Airflow 6. Fan performance...
  • Page 20 ¢ Models: ASEG12KETF and ASEG12KETF-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 16 - 6-2. Airflow 6. Fan performance...
  • Page 21 ¢ Models: ASEG14KETF and ASEG14KETF-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 17 - 6-2. Airflow 6. Fan performance...
  • Page 22 7. Operation noise (sound pressure) 7-1. Noise level curve ¢ Models: ASEG07KETF and ASEG07KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15...
  • Page 23 ¢ Models: ASEG12KETF and ASEG12KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 24 7-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 20 - 7-2. Sound level check point 7. Operation noise (sound pressure)
  • Page 25 8. Safety devices Model Type of Protection form ASEG07KETF ASEG09KETF ASEG12KETF protection ASEG07KETF-B ASEG09KETF-B ASEG12KETF-B Circuit Current fuse (PCB*) 250 V, 3.15 A protection More than 85°C Activate Fan motor speed down Fan motor Thermistor protection protection 85°C or less Reset Fan motor speed recover Model...
  • Page 26 9. External input and output External Input and Output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Connecting point Input/Output Function Input select Input signal Operation/Stop CN46 Input...
  • Page 27 9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 28 ¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 29 ¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External Input and Output PCB.
  • Page 30 9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 31 ¢ External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Setting of external input and output"...
  • Page 32 9-3. Setting of external input and output • Indoor unit Input Connection point Function setting number 46 Function Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) CN46 Forced stop mode Operation/Stop mode 2 (R.C. disabled) Output Connection point Function setting number 60 Function Operation/Stop 01 to 08...
  • Page 33 9-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Off → On Operation — Input of indoor unit CN46 On →...
  • Page 34 ¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Forced stop Off → On (R.C. disabled) — Input of indoor unit CN46 Normal On → Off (R.C.
  • Page 35 ¢ Operation/Stop mode 2 • In the case of “Edge” input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Operation Off → On (R.C. enabled) — Input of indoor unit CN46 Stop On → Off (R.C.
  • Page 36 ¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D CN313 Output PCB On → Off Normal operation CN313 Compressor Room temp. Set temp. - 32 - 9-4.
  • Page 37 9-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 1, 2 Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
  • Page 38 ¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
  • Page 39 10. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 40 11. Remote controller 11-1. Wireless remote controller ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 41 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 42 12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 12-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 43 NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 39 - 12-1.
  • Page 44 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Filter sign 30/31...
  • Page 45 2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 46 3) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 47 6) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 48 10) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status (Setting prohibited) - 44 -...
  • Page 49 12-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 50 13. Accessories 13-1. Models: ASEG07KETF, ASEG09KETF, ASEG12KETF, ASEG14KETF, ASEG07KETF-B, ASEG09KETF-B, ASEG12KETF-B, and ASEG14KETF-B Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters...
  • Page 51 14. Optional parts 14-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wired Remote Wire type: Non-polar 2-wire UTY-RNRYZ* Controller Optional Communication Kit is necessary for installation. High visibility and easy operation.
  • Page 52 14-2. Others Exterior Part name Model name Summary Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZX Connect Kit Connecting point: CN46 and CN47 on Main PCB Required when external device is connected. External UTY-XWZXZ5 Connect Kit Connecting point: CN46 and CN47 on Main PCB Use to connect with external devices...
  • Page 53 Part 2. OUTDOOR UNIT SINGLE TYPE: AOEG07KETA AOEG09KETA AOEG12KETA AOEG14KETA...
  • Page 54 1. Specifications Type Inverter, Heat pump Model name AOEG07KETA AOEG09KETA AOEG12KETA AOEG14KETA Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,650 1,700 1,680 Airflow rate Heating 1,450 1,470 1,580 Type ×...
  • Page 55 2. Dimensions 2-1. Models: AOEG07KETA, AOEG09KETA, and AOEG12KETA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 51 - 2-1. Models: AOEG07KETA, AOEG09KETA, and AOEG12KETA 2.
  • Page 56 2-2. Model: AOEG14KETA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 52 - 2-2. Model: AOEG14KETA 2. Dimensions...
  • Page 57 3. Installation space 3-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 58  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 59  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 60 4. Refrigerant circuit 4-1. Models: AOEG07KETA, AOEG09KETA, and AOEG12KETA Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 56 -...
  • Page 61 4-2. Model: AOEG14KETA Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 57 - 4-2.
  • Page 62 5. Wiring diagrams 5-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA - 58 - 5-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA 5. Wiring diagrams...
  • Page 63 6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOEG07KETA and AOEG09KETA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 64 6-2. Model: AOEG12KETA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
  • Page 65 7. Additional charge calculation 7-1. Models: AOEG07KETA and AOEG09KETA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Model: AOEG12KETA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.)
  • Page 66 8. Airflow 8-1. Model: AOEG07KETA  Cooling 1,650  Heating 1,450 8-2. Model: AOEG09KETA  Cooling 1,650  Heating 1,450 8-3. Model: AOEG12KETA  Cooling 1,700 1,001  Heating 1,470 - 62 - 8-1. Model: AOEG07KETA 8. Airflow...
  • Page 67 8-4. Model: AOEG14KETA  Cooling 1,680  Heating 1,580 - 63 - 8-4. Model: AOEG14KETA 8. Airflow...
  • Page 68 9. Operation noise (sound pressure) 9-1. Noise level curve ¢ Model: AOEG07KETA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 69 ¢ Model: AOEG12KETA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 70 9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 66 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 71 10. Electrical characteristics Model name AOEG07KETA AOEG09KETA AOEG12KETA AOEG14KETA Voltage 230~ Power supply Frequency Max operating current * Starting current Circuit breaker current Power cable Cross- Wiring sectional spec. * Connection area cable * Limited wiring length NOTES: • *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 72 11. Safety devices Model Type of protection Protection form AOEG07KETA AOEG09KETA 250 V, 20 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 85—122 °C Activate Fan motor stop Fan motor Terminal protection protection program 77—114 °C Reset Fan motor restart 110 °C Activate...
  • Page 73 12. Accessories 12-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA Part name Exterior Part name Exterior Installation manual Drain pipe - 69 - 12-1. Models: AOEG07KETA, AOEG09KETA, AOEG12KETA, and AOEG14KETA 12. Accessories...