Instruction Manual • SJ100 Series • L100 Series • SJ200 Series • L200 Series NOTE: REFER ALSO TO THE PERTINENT INVERTER INSTRUCTION MANUAL Manual Number: HAL1052 After reading this manual, December 2005 keep it handy for future reference. Hitachi America, Ltd.
Chapter1 Chapter 1 – General Description The SJ/L-EN module is an Ethernet communication interface for the Hitachi SJ200, L200, SJ100 and L100 series of AC Variable Frequency Inverters. The module is mounted externally to the inverter. The SJ/L-EN uses the open MODBUS/TCP communication protocol. It utilizes a 10Base-T physical interface with a 10 Mbps data transfer rate.
Chapter1 SAFETY PRECAUTIONS HIGH VOLTAGE: This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully. WARNING: Indicates a potentially hazardous situation that, if not avoided, can result in serious injury or death.
Page 7
Chapter1 CAUTION: Be sure not to touch the surface or terminals of the SJ/L-EN Ethernet module while the inverter is energized; otherwise there is the danger of electric shock. CAUTION: The software lock modes described in the inverter manuals are NOT supported via the SJ/L-EN module.
Chapter2 Chapter 2 – Installation and Wiring Orientation to Product Features Figure 2-1 below shows the physical layout of the SJ/L-EN Ethernet module. In particular, note the location of status LEDs and DIP-switches. RTS LED TXD LED RXD LED STATUS LEDs •...
Chapter2 Installing the Module Gently push the SJ/L-EN board into the supplied piece of SNAP-TRACK until it is securely seated. If mounting the SJ/L-EN on a DIN-Rail, attach the two DIN-Rail Clips to the back of the SNAP-TRACK. The assembly can then be affixed to a DIN rail using the clips.
Chapter2 User Interface The SJ/L-EN has seven LEDs to convey module status and activity. Four LEDs next to the RJ45 connector: • STATUS (GREEN) – This LED will be ON whenever the SJ/L-EN is receiving proper power from the inverter and the self diagnostics have shown the board to be functioning normally. •...
Chapter3 Chapter 3 – Configuration Install NetEdit3 Software NetEdit3 Software is provided on the CD-R enclosed with the SJ/L-EN module. This software is required to configure the board. It can also be used to update the SJ/L-EN firmware in the event of a future update. NetEdit3 ®...
Page 14
NetEdit3. You can also input a Name for the device, and a Description. The default Name will be “Hitachi Drive”, and the default Description will be “SJ/L-EN”. The device’s IP Address will also be shown. Change this to the desired IP address for your Modbus/TCP network.
Page 15
Chapter3 Figure 3-2 NetEdit3 Screen after Scan of Network Figure 3-3 NetEdit3 General Settings Dialog Box Page 15 of 36...
Chapter 4 Chapter 4 – Operation Setting Up the Inverter for Ethernet Network Operation Once the SJ/L-EN board has been properly configured and connected to a network as described in Chapter 3, it is capable of reading data from and writing data to the inverter. However if it is desired to have either the RUN command and/or the speed reference come from the Ethernet master, you must change two inverter parameters as shown in the following table.
Chapter 5 Chapter 5 – Troubleshooting In general, the first step to troubleshooting should be to inspect the status LEDs on the SJ/L-EN board, in addition to the inverter operator/keypad display. These will give valuable clues to the nature of the problem. Refer to the description of the proper LED indications on page 11.
Appendix Appendix – Parameter List Note: Parameters in BOLDFACE can be edited while inverter is in the RUN mode. “RO” means the parameter is Read Only, and “R/W” means the value can be read or written. Please refer to page 32 for a key to other symbols used in these tables.
Page 30
Appendix H – Motor Constants and Functions H001 5001 5002 Auto–tuning setting (SJ100 only) 0 – 2 Motor data selection, 1 motor H002 5003 5004 0 – 1 (SJ100 only) Motor data selection, 2 motor H202 5403 5404 0 – 1 (SJ100 only) L200/SJ200 0 –...
Page 31
Appendix Motor constant R2, 1 motor (Auto) H031 5061 5062 X1000 0 – 65535 (SJ200 Only) Motor constant R2, 2 motor (Auto) H231 5461 5462 X1000 0 – 65535 (SJ200 Only) Inductance L, 1 motor (Auto) H032 5063 5064 X100 0 –...
Page 32
Appendix * Data Range depends on Model and/or Rating. Verify that data you are writing is valid for the inverter model and rating you are writing to. ‡ These special parameters are NOT accessible via the standard keypads. They can only be accessed by the SJ/L-EN board.