hit counter script
Download Print this page
Sanyo 18KHS22 Submittal Sheet
Sanyo 18KHS22 Submittal Sheet

Sanyo 18KHS22 Submittal Sheet

Wall mounted heat pump

Advertisement

Quick Links

SUBMITTAL SHEET
SUBMITTAL SHEET
SUBMITTAL SHEET
SUBMITTAL SHEET
SYSTEM
INDOOR/OUTDOOR
18KHS22
KHS1822/CH1822
WALL MOUNTED HEAT PUMP
GENERAL DATA (AT 230V)
POWER V/PH/HZ
230-208/1/60
Circuit Ampacity, Min. (A)
30
Fuse size, Max.
(A)
30
COMPRESSOR
Rotary-Hermetic
No. used
1
R.L. Amps - L.R. Amps (A)
7.1 - 52.0
Crankcase Heater
(W)
30
OUTDOOR FAN - TYPE
Propeller
Dia. (in.) - No. used
15 3/4 - 1
Type Drive - No. speeds
Direct - 2
No. Poles - RPM (High)
6 - 1,020
No. Motors - HP
1 - 1/12
CFM (High)
1,190
F.L. Amps. (A)
0.5
OUTDOOR COIL – TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe Type
Slit Plate - Inner Riffled
Rows - F.P.I.
2 - 15.9
Face Area (sq.ft.)
5.34
Tube Size (in.)
3/8
INDOOR FAN - TYPE
Cross - Flow
Dia. & Length (in.) - No. used
4 & 30-1
No. speeds
3 & Auto
No. Poles -RPM (High)
4-1,600
No. Motors - HP
1 - 1/75
CFM (HI/MED/LOW)
440/380/320
F.L. Amps (A)
0.4
INDOOR COIL – TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe type
Slit Plate - Inner Riffled
Rows - F.P.I.
2 - 14.1
Face Area (sq. ft.)
2.08
Tube Size (in.)
3/8
Drain Connection Size (in.)
1 - 1/4
REFRIGERANT
R22
Lbs. - R22 (O.D. Unit)
4.25
Control
Capillary Tube
Connection
Flare
Line Length, Max (ft.)
65
Lift difference, Max (ft.)
23
Line Size - in. O.D. Discharge 1/4
Line Size - in. O.D. Suction
5/8
DIMENSIONS (in.)
H
Indoor Unit
-Uncrated
14- 3/16 x 39
-Crated
18
Outdoor unit
-Uncrated
24-13/16 x 32-11/16 x 12-13/32
-Crated
28- 3/32 x 39- 5/32 x 16- 9/32
WEIGHT
INDOOR
Net
(lbs.)
29.8
Shipping (lbs.)
37.5
Shipping Volume
(cu.ft.)
4.8
x
W
x
D
x 7-13/16
x 42-17/32 x 10-23/32
OUTDOOR
134.5
143.3
10.3
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity
(BTU/H)
Sensible Capacity (BTU/H)
Latent Capacity
(BTU/H)
SEER
Dehumidification (Pints/H)
Amps
(A)
Power Inputs (W)
HEATING
Total Capacity
(BTU/H)
HSPF
Amps
(A)
Power Inputs (W)
Back-up Strip Heater
(KW)
Outdoor Sound Rating (bels)
FEATURE
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louve
(Horizontal)
(Vertical)
Power Failure Automatic Restart
Self Diagnosis
Heating/Cooling Automatic Changeover
OPTION
Refrigerant Line Set
Low Ambient Control
Fresh Air Intake
Central Remote ON-OFF Control
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removable Remo-con Bracket
OPERATING RANGE
Cooling
Indoor Air
Intake Temp.
Maximum
95 F DB/71 F WB
Minimum
67 F DB/57 F WB
Heating
Maximum
80 F DB/67 F WB
Minimum
- F DB/ - F WB
CERTIFICATION
AIRCONDITIONING PRODUCTS
SS18KHS22-1
16,500/16,000
10,390/10,060
6,110/5,940
10.0/10.0
5.3/5.2
8.0/8.6
1,810/1,760
18,000/17,600
6.8/6.8
8.0/8.6
1,810/1,760
1.80/1.47
7.8
Microprocessor
LCD Wireless type
IC Thermostat
ON/OFF, 24 hours
Built-In
Manual
Automatic
Built-In
Built-In
Built-In
AP2507BH (20 ft)
AP2510BH (30 ft)
AP2515BH (50 ft)
N/A
N/A
Available
N/A
PLB 182
Available
Available
Outdoor Air
Intake Temp.
115 F DB
67 F DB
75 F DB / 65 F WB
17 F DB/ 15 F WB
18KHS22

Advertisement

loading

Summary of Contents for Sanyo 18KHS22

  • Page 1 SUBMITTAL SHEET SUBMITTAL SHEET SUBMITTAL SHEET SUBMITTAL SHEET SYSTEM AIRCONDITIONING PRODUCTS INDOOR/OUTDOOR 18KHS22 KHS1822/CH1822 WALL MOUNTED HEAT PUMP SS18KHS22-1 GENERAL DATA (AT 230V) PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V) POWER V/PH/HZ 230-208/1/60 COOLING Circuit Ampacity, Min. (A) Total Capacity...
  • Page 2: Dimensional Data

    11-7/32 2-3/8 3-3/4 WARRANTY Full specific warranty rights, conditions, exclusions and obligations are specified in the SANYO products are warranted against defects in materials and workmanship for the warranty packed with each products. period below; LABOR PARTS Compressor...

This manual is also suitable for:

Khs1822Ch1822