UPS OPERATING INSTRUCTIONS
PROTECT A.
PROTECT A. 500
PROTECT A. 700

Advertisement

Table of Contents
loading

Summary of Contents for AEG PROTECT A. 500

  • Page 1 UPS OPERATING INSTRUCTIONS PROTECT A. PROTECT A. 500 PROTECT A. 700...
  • Page 3 Thank you for deciding to purchase the PROTECT A. UPS from AEG Power Solutions. The following safety instructions are an important part of the operating instructions are will protect you against problems from operating errors and possible dangers. Please read...
  • Page 4: Notes On These Operating Instructions

    Uninterruptible Power Supply (UPS), PROTECT A. 500 or PROTECT A. 700 - referred to as PROTECT A. in this document - safely and properly, and for its intended purpose. These operating instructions contain important information for avoiding dangers. Please read these instructions carefully prior to...
  • Page 5 AEG or its representatives without prior notice in the event of maintenance and repair work being carried out with anything other than original AEG parts or spare parts purchased from AEG.
  • Page 6: Table Of Contents

    Table of Contents Notes on these Operating Instructions ........4 System Overview ..............7 Brief Overview ..............7 Principle of Operation............8 Safety ................10 General Safety Instructions ..........10 Safety Instructions for PROTECT A........10 CE Certificate ..............14 Technical Data ..............15 Set-up................17 Unpacking and Inspection ..........17 Installation Site ..............18 Connections, Operating and Display Elements ....19 Installation and Operation..........20...
  • Page 7: System Overview

    The PROTECT A. series is a compact, interactively operating UPS available with nominal power output ratings 500, 700, 1000 and 1400 VA. This document describes both types, PROTECT A. 500 and PROTECT A. 700. Brief Overview LED display and a pushbutton switch are located on the front of the UPS for straightforward monitoring and operation.
  • Page 8: Principle Of Operation

    ♦ Overvoltage protection (RJ11) for fax, modem and phone ♦ CompuWatch software for shutdown, status messages and measurement values for all major operating systems (incl. Windows, Mac, Linux) ♦ Compact design / without fan Principle of Operation The UPS is connected to a shockproof socket between the public utility’s mains and the loads to be protected.
  • Page 9 The static bypass switch is activated in the event of a mains failure. The inverter then takes over the voltage supply of the connected loads, in order to prevent the risk of data loss or damage to the loads. PROTECT A. supplies voltage until the battery is discharged or your IT system has been shut down and switched off properly.
  • Page 10: Safety

    Safety General Safety Instructions Read these operating instructions carefully prior commissioning of the PROTECT A. UPS and observe the safety instructions! Only use the unit if it is in a technically perfect condition and always in accordance with its intended purpose, while being aware of safety and danger aspects, and in accordance with the operating instructions! Immediately eliminate any faults that could be detrimental to safety.
  • Page 11 The output may be live, even if the UPS is not connected to the mains supply, as the UPS has its own internal power supply (battery)! For health and safety reasons, the unit must be earthed correctly! PROTECT A. may only be operated with or connected to a 220 / 230 / 240 VAC mains with protective grounding using a mains connection cable with PE conductor (included in the delivery) that has been tested in accordance with German...
  • Page 12 ♦ Condensation may occur if the UPS is brought from a cold environment into the room where it is to be installed. The UPS must be absolutely dry prior to start- up. As a result, leave it to acclimatise for at least two hours.
  • Page 13 When replacing the battery, the following must be observed: Only ever use an identical, maintenance-free sealed lead battery with the same data as the original battery. Danger! Explosive! Never throw batteries into open fire. Never open or damage batteries. (Electrolyte may leak out and damage skin and eyes.
  • Page 14: Ce Certificate

    CE Certificate...
  • Page 15: Technical Data

    Frequency in battery operation 50 Hz / 60 Hz ±1 Hz Nominal output current 2.2 A ( PROTECT A. 500 ) 3.0 A ( PROTECT A. 700 ) Changeover time in the event of a mains failure 2-6 ms (typical)
  • Page 16 Housing colour Silver/black Dimensions W x H x D [mm] 100 x 140 x 330 Weight [kg] 6 kg (PROTECT A. 500) 6.5 kg (PROTECT A. 700) Cooling type Increased natural air cooling Storage temperature range -15° C to +50° C...
  • Page 17: Set-Up

    Check the shipping container for damage on arrival. If necessary, ask the transport company to check the goods and make a record of the damage in the presence of the transport company employee and report the damage to the AEG representative or dealer within eight days of delivery.
  • Page 18: Installation Site

    Check the content is complete: ♦ PROTECT A. with 500 or 700 VA ♦ Mains connection cable with shockproof plug acc. to CEE 7/7 Second mains connection cable with UK plug acc. to BS 1363 ♦ Two device connecting cables ♦...
  • Page 19: Connections, Operating And Display Elements

    Connections, Operating and Display Elements Front 1 Main switch of the UPS (mains switch) 2 LED displays: Green LED: Mains/normal operation Yellow LED: Battery operation Red LED: Warning/fault, battery renewal indication Rear 1 Load connections with overvoltage protection and UPS backup 2 Mains connection (UPS input) with input fuse and integrated back-up fuse...
  • Page 20: Installation And Operation

    Installation and Operation Check Remove the UPS from its transport packaging and check that it has not been damaged in transit. If you find any damage, pack the unit up again and send it back to where you purchased it. Installation Install the UPS unit in a protected location where there is an adequate air supply and where it will be largely free from dust...
  • Page 21: Charging

    Charging The PROTECT A. is supplied with its battery fully charged. Nevertheless, energy may have been lost during transport, so the battery should be fully recharged before it is used for the first time. Connect the input of the UPS (no. 2 in the figure in chapter 4.3 on page 19) to the mains connection cable provided and plug the mains connector into a suitable shockproof socket.
  • Page 22: Modem/Phone Connection (Data Line Protection)

    Note that the additional output socket identified in white has a special property (chapter 4.3 / no. 6 / pg.19). This is always live irrespective of the other outputs. It is not backed up by the UPS, nor can it be switched off using the main switch of the UPS.
  • Page 23: Operation

    The interfaces are mutually exclusive. There is no provision for simultaneous operation of RS232 and USB. Operation Once you have connected the UPS to a suitable mains connection, you can start operation using the UPS main switch. Switching ON and OFF: To switch on, press the main switch on the front of the UPS (chapter 4.3 / no.
  • Page 24: Battery Operation / Autonomous Operation

    The connected loads are powered using the monitored and filtered mains voltage, which is additionally stabilised by the integrated A.V.R. control unit. The green “Normal” LED shows that the unit is active. 5.7.2 Battery Operation / Autonomous Operation When there is a mains failure or if the input voltage moves outside the tolerance range, the inverter automatically switches over to autonomous mode and supplies the loads with voltage from the battery.
  • Page 25: Shutdown And Ups Management Software

    5.7.4 Shutdown and UPS Management Software The “CompuWatch” software specially developed for these purposes by AEG continuously checks the mains supply and the UPS status. In conjunction with the “intelligent” UPS, this ensures that the availability of IT components and data security are guaranteed.
  • Page 26: Displays And Troubleshooting

    Displays and Troubleshooting Warning Sounds Warning Meaning sound Sounds every 10 UPS is operating in battery mode. seconds Sounds every UPS is running in battery mode and will shortly second shut down (battery system has reached the battery undervoltage limit). Sounds every two Battery system faulty, it may have to be renewed seconds...
  • Page 27 Data backup time is UPS overload Remove loads that are less only very short on important power failure Battery voltage is too low Charge the battery for at least 8 hours Battery fault die to high Renew the battery with a temperature in the battery of the same type operating environment or...
  • Page 28: Maintenance

    Maintenance The PROTECT A. consists of state-of-the-art, non-wearing components. We do, however, recommend regular visual checks of the unit to maintain its continuous availability and operational reliability. Check whether: ♦ there is any mechanical damage or foreign bodies can be found in the system, ♦...
  • Page 29: Battery Replacement

    Battery Replacement ATTENTION: A battery can cause an electric shock, and represents a considerable hazard if handled incorrectly. The following precautions should be taken before the battery is renewed. ♦ Switch off the UPS and disconnect the mains cable from the socket. ♦...
  • Page 30: Storage And Disposal

    Storage and Disposal Storage Long storage times without charging discharging the battery at regular intervals may lead to permanent damage of the battery. If the battery is stored at room temperature (20° C to 30° C) it will automatically discharge at a rate of 3-6% per month due to internal reactions.
  • Page 31: List Of Terms

    List of Terms Technical Terminology Automatic Voltage Regulation Automatic voltage regulation against mains voltage deviations DC/DC booster Circuit technology for increasing a DC voltage to a higher voltage level Emergency Power Off Device for emergency shutdown Power Factor Correction Circuit technology for minimising system disturbances (particularly important when connecting non-linear loads) Appliance protection...
  • Page 32 Guarantee Certificate Type: …….……………….…............Unit number:…….……………….…........... Date of purchase:…….……………….…..........Dealer stamp / signature Errors and changes excepted. AEG Power Solutions GmbH Emil-Siepmann-Straße 32 59581 Warstein-Belecke Germany Operating instructions BAL 8000024070 EN...