Job Name:
Drawing Reference:
System No.:
GENERAL FEATURES
• R410A refrigerant
• Seven sizes from 6,000 to 30,000 Btu/h
• Powerful airflow (CFM)
• Compact, lightweight, shiny-white, flat-panel design
• Quiet operation
• Multiple fan-speed settings
• Intake grille filter is easily removed for cleaning
• Built-in receiver is standard
• IT Terminal plug
SPECIFICATIONS
Capacity*
Cooling.......................................................24,000 Btu/h
Heating.......................................................27,000 Btu/h
Power
Power Source............................208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling.............................................................0.07 kW
Heating.............................................................0.07 kW
Current
Cooling........................................................................0.50 A
Heating........................................................................0.50 A
Minimum Circuit Ampacity (MCA).................................0.63 A
Maximum Overcurrent Protection (MOCP) Fuse.................15 A
External Finish...............................Munsell No. 1.0Y 9.2 / 0.2
External Dimensions
Inches.............................14-3/8 H x 46-1/16 W x 11-5/8 D
mm...........................................365 H x 1,170 W x 295 D
Notes:
PKFY-P24NKMU-E2
Model:
Location:
Schedule No.
Date:
Net Weight
Unit...........................................................46 lbs. / 21 kg
Coil Type.................................................................Cross Fin
Fan
Type x Quantity...................................Line Flow Fan x 1
Airflow Rate (Low-High)................................570 - 920 CFM
Motor
Type............................................Direct-drive DC Motor
Output...........................................................0.056 kW
Air Filter....................................Polypropylene Honeycomb
Refrigerant Piping Dimensions
Liquid (High Pressure).....................3/8" / 9.52 mm (Flare)
Gas (Low Pressure).......................5/8" / 15.88 mm (Flare)
Drainpipe Dimension..................................I.D. 5/8" / 16 mm
Sound Pressure Levels
Low-High................................................39 - 49 dB(A)
OPTIONS
□ External Heat Adapter...............................PAC-YU25HT
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
(35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB
Note: Ventilation air: Providing sufficient ventilation air is an impor-
tant part of every building design. ASHRAE Standard 62 provides
the minimum ventilation air requirement. Also, check local codes.
(Aluminum Plate Fin and Copper Tube)