3.3 Diagnosis / status indications

Faults can occur in the load circuit and in the controller itself or from the mains.
Diagnosis of unexpected operating behaviour is performed by LEDs on the front
panel of the control device.
Description
Frequency fault
SYNC fault
Temperature monitoring
Load fault
Flash values invalid
Correction values invalid
Undervoltage
Overvoltage
Pulse lock active
U-limitation
I-limitation
P-limitation
(H RLP)
Tab 3 Allocation of message register

4. External connections

4.1 Power supply for Thyro-A

Connecting the power supply is carried out as shown in the figures and technical
data. With Thyro-A 2A a right rotational field in the power circuit is required.

4.2 Power supply for the control device

The control device is supplied directly from the power section (terminals U1, X1.1
and X1.2). This voltage also serves as mains synchronization. The mains connection
is equipped for input voltages of U
of 47Hz to 63Hz. Both terminals (X1.1 and X1.2
bridged. If a phase is connected to X1, a fused connection is necessary
(figs. 3,7).
LEDs
Relay K1
PULSE INHIBIT blinks
open
PULSE INHIBIT blinks
open
LOAD FAULT blinks
open
LOAD FAULT on
open
2 red LEDs
open
synchron. blinks
open
--
PULSE INHIBIT
closed
2 red LEDs blink
none
slowly, alternatively
2 red LEDs blink
none
slowly, alternatively
2 red LEDs blink
none
slowly, alternatively
-15% to +10% and nominal frequencies
Nnom
Description
Outside 47Hz to 63 Hz
when switching on or
Zero crossing outside
permissible tolerance range
in operation
Temp. monitoring responded
(control board or control
section)
Load fault: none or under current
Controller fault
Mains fault
Mains fault
Bridge X2: 1.2
opened
U limit value exceeded
I limit value exceeded
P limit value exceeded
1.5mm
grid 3.81) are internally
2
83