INSTALLATION MANUAL

For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing
the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Anwendung vor Installation der Klimaanlage die vorliegende Bedie-
nungsanleitung und das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Avant d'installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d'installation de l'appareil exté-
rieur pour une utilisation sûre et correct.
INSTALLATIEHANDLEIDING
Lees deze handleiding en de installatiehandleiding van het buitenapparaat zorgvuldig door voordat u met het
installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de
aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, prima di installare il condizionatore d'aria leggere attentamente il presente manuale
ed il manuale d'installazione dell'unità esterna.
ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για σωστή και ασφαλή χρήση, διαβάστε προσεκτικά αυτό το εγχειρίδιο, καθώς και το εγχειρίδιο εγκατάστασης
της εξωτερικής μονάδας, πριν από την εγκατάσταση της μονάδας κλιματιστικού.
MANUAL DE INSTALAÇÃO
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade exte-
rior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af udendørsenheden grundigt, før du
installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och utomhusenhetens installationshandbok noga innan luftkonditioneringen installeras så
att den används på ett säkert och korrekt sätt.
MONTAJ ELKİTABI
Emniyetli ve doğru kullanım için, klima cihazını monte etmeden önce bu kılavuzu ve dış ünite montaj kılavuzunu
tamamıyla okuyun.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для обеспечения безопасной и надлежащей эксплуатации внимательно прочтите данное руководство и
руководство по установке наружного прибора перед установкой кондиционера.
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
ΓΙΑ ΑΥΤΟΝ ΠΟΥ ΚΑΝΕΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ
PARA O INSTALADOR
TIL INSTALLATØREN
FÖR INSTALLATÖREN
MONTÖR İÇİN
ДЛЯ УСТАНОВИТЕЛЯ
English
Deutsch
Français
Nederlands
Español
Italiano
Ελληνικά
Português
Dansk
Svenska
Türkçe
Русский

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric Mr.Slim PLA-RP-BA Series

  • Page 1: Installation Manual

    Air-Conditioners PLA-RP·BA Series INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE Deutsch Aus Sicherheitsgründen und zur richtigen Anwendung vor Installation der Klimaanlage die vorliegende Bedie- nungsanleitung und das Installationshandbuch gründlich durchlesen.
  • Page 2: Table Of Contents

    • The terminal block cover panel of the unit must be fi rmly attached. incorrectly installed unit may fall down and cause damage or injuries. • Use only accessories authorized by Mitsubishi Electric and ask a dealer or • The unit must be securely installed on a structure that can sustain its weight.
  • Page 3: Installation Location

    2. Installation location Refer to the outdoor unit installation manual. 3. Installing the indoor unit 3.1. Check the indoor unit accessories (Fig. 3-1) The indoor unit should be supplied with the following accessories. Accessory name Q'ty Installation template Washers (with insulation) Washers (without insulation) Pipe cover (for refrigerant piping joint) Small diameter...
  • Page 4 3. Installing the indoor unit 3.4. Branch duct hole and fresh air intake hole (Fig. 3-4) At the time of installation, use the duct holes (cut out) located at the positions shown in Fig3-4, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. 120˚...
  • Page 5: Installing The Refrigerant Piping

    4. Installing the refrigerant piping 4.1. Precautions For devices that use R410A refrigerant • Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigera- tion oil applied to the fl ared sections. • Use C1220 copper phosphorus for copper and copper alloy seamless pipes, to connect the refrigerant pipes.
  • Page 6: Drainage Piping Work

    4. Installing the refrigerant piping 4.3. Indoor unit (Fig. 4-3) Heat insulation for refrigerant pipes: 1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure Refrigerant pipe and that the end of the pipe cover touches the side of the unit. insulating material 2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure Pipe cover (large)
  • Page 7: Electrical Work

    6. Electrical work 6.1. Indoor unit (Fig. 6-1) 1. Remove the electrical wiring service panel. 2. Remove the electrical box cover. 3. Wire the power cable and control cable separately through the respective wiring entries given in the diagram. • Do not allow slackening of the terminal screws. •...
  • Page 8 6. Electrical work 6.1.2. Separate indoor unit/outdoor unit power supplies (For PUHZ application only) The following connection patterns are available. The outdoor unit power supply patterns vary on models. 1:1 System 1:1 System * The indoor power supply terminal kit is required. A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch...
  • Page 9: Remote Controller

    6. Electrical work 6.2. Remote controller 6.2.1. For wired remote controller 1) Installing procedures (1) Select an installing position for the remote controller. (Fig. 6-2) The temperature sensors are located on both remote controller and indoor unit. ► Procure the following parts locally: 2 piece switch box Thin copper conduit tube Lock nuts and bushings...
  • Page 10: Function Settings

    6. Electrical work 5) Assigning a remote controller to each unit (Fig. 6-8) Each unit can be operated only by the assigned remote controller. Make sure each pair of an indoor unit PC board and a remote controller is assigned MODEL SELECT to the same pair No.
  • Page 11 6. Electrical work Function table Select unit number 00 Mode Settings Mode no. Setting no. Initial setting setting Power failure automatic recovery Not available Ο Available Ο Indoor temperature detecting Indoor unit operating average Set by indoor unit’s remote controller Remote controller’s internal sensor Ο...
  • Page 12 6. Electrical work Operation buttons (During the fi xed airfl ow direction mode) Press the button with either refrigerant address No., unit No. or outlet No. blinking, ... ON/OFF button Resets the fixed airflow direction mode. Fan Speed button Press for 2 Only the air conditioner with the No.
  • Page 13 6. Electrical work ■ Adjust to the next unit No. with Set Temperature button 5 . How to fi nd air conditioner No. Each air conditioner has its own refrigerant address No. and unit No. (refrigerant address No.00 is remained.) (Example below).
  • Page 14: Test Run

    7. Test run 7.1. Before test run ► After completing installation and the wiring and piping of the indoor and ► Do not carry out this test on the control wiring (low voltage circuit) termi- outdoor units, check for refrigerant leakage, looseness in the power sup- nals.
  • Page 15 7. Test run • Refer to the following tables for details on the check codes. (Wireless remote controller) [Output pattern A] Beeper sounds Beep Beep Beep Beep Beep Beep Beep OPERATION · · · Repeated INDICATOR lamp blinking pattern Approx. 2.5 sec. 0.5 sec.
  • Page 16 7. Test run • If the unit cannot be operated properly after test run, refer to the following table to fi nd the cause. Symptom Cause Wired remote controller LED 1, 2 (PCB in outdoor unit After LED 1, 2 are lighted, LED 2 is turned •For about 2 minutes after power-on, operation of the remote For about 2 minutes PLEASE WAIT...
  • Page 17: System Control

    8. System control Refer to the outdoor unit installation manual. 9. Installing the grille 9.1. Checking the contents (Fig. 9-1) • This kit contains this manual and the following parts. Accessory name Q’ty Remarks Grille 950 × 950 (mm) Screw with captive washer M5 ×...
  • Page 18 9. Installing the grille 9.4.2. Temporary installation of the grille (Fig. 9-6) • Temporarily secure the grille using the bell shaped holes by putting the socket of Main unit the grille marked G on the corner drain pipe area of the main unit. Corner drain pipe area * Make sure that the lead wiring of the grille does not get pinched between the Screw with washer...
  • Page 19: Easy Maintenance Function

    9. Installing the grille 9.7. Locking the up/down airfl ow direction (Fig. 9-11) The vanes of the unit can be set and locked in up or down orientations depending upon the environment of use. • Set according to the preference of the customer. The operation of the fixed up/down vanes and all automatic controls cannot be performed using the remote controller.
  • Page 20 This product is designed and intended for use in the residential, commercial and light-industrial environment. • Low Voltage Directive 2006/95/EC The product at hand is • Electromagnetic Compatibility Directive based on the following 2004/108/EC EU regulations: Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

Table of Contents