hit counter script
Download Print this page
Siemens RDF301.50H Operating Instructions
Hide thumbs Also See for RDF301.50H:

Advertisement

s

Operating Instructions

RDF301.50H – the room thermostat with KNX communications allows you to set the ideal room temperature.
The thermostat provides Comfort, Economy and Protection mode and can operate in Auto timer mode using a time
schedule provided via bus.
The fan operates either in Auto mode or at a speed selected in Manual mode.
You can either take advantage of the thermostat's factory settings or adjust it as needed.
Protection mode
Auto Timer mode
Comfort mode
Economy mode
Measured room temperature,
setpoints and parameters
Current time of day or additional
user information
Actual room temperature
Outdoor temperature
Fault indicator *
Operating mode button
**
**
Notes:
The thermostat goes back to Auto
Timer mode if a time schedule via
bus changes the operating mode.
User operations are ignored if a
time schedule via bus sets the
operating
mode
to
protection.
When you press a button, "OFF"
flashes on the LCD.
Auto mode is not available if there
is no time schedule via bus.
*
Needs to be configured by your HVAC installer
** Needs to be enabled via parameter P02
CE1B3171.1en / 02 September 2013
Condensation in the room *
Cooling demand / mode
Heating demand / mode
Electrical heater active
Extended Comfort mode *
Automatic fan
Low fan speed
Medium fan speed
High fan speed
Buttons are locked
Weekday 1...7
(1 = Monday / 7 = Sunday)
Fan mode button
– Automatic fan (
– Manual fan (
4 buttons for notifications
– Make Up Room
– Do Not Disturb
Colder / Warmer
Change room temperature
+ / –
Press + or – to increase or decrease the current room temperature setpoint for
RDF301.50H
Comfort mode. The thermostat changes to Comfort
The setting range is 5...40 °C, unless limited by parameters P09 and P10.
Adjust fan speed / fan mode
Press the
In Auto mode, the thermostat automatically selects the fan speed based on set-
point and actual room temperature. The fan continues to run at low speed
(factory setting) after the room temperature reaches the setpoint .
In manual mode, the fan always runs at the speed that you select:
Low fan speed
Medium fan speed
High fan speed
For a single-speed fan, you can change the mode between
Change the operating modes
Press operating mode button
In protection mode, the plant stops operating. However, if the room
temperature drops below 8 °C, heating is switched on to protect the room
against frost.
Your HVAC installer can change the frost protection limit and set a heat pro-
tection limit as needed:
Changes made by installer:
In Comfort mode, the thermostat maintains the room temperature on the
setpoint which can be readjusted using the + and – buttons.
In Economy mode, the room temperature is maintained at a lower or higher
setpoint, thus saving energy and money. Adjust parameters P11 and P12 to
change the preselected setpoints.
The thermostat can be set to Economy mode either by pressing the operating
)
mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus
)
command) such as window contact, keycard or presence detector.
In Auto timer mode, the thermostat automatically switches between Comfort
and Energy Saving mode according to the time schedule via KNX bus.
*
,
Change from heating to cooling mode
/
Changeover between cooling and heating is either automatic using a heating /
cooling changeover sensor or a remote changeover switch or via instruction
from the central management station via KNX bus, or manual by pressing
operating mode button
configured for cooling only or heating only, (see parameter P01).
Display for automatic changeover or heating only / cooling only:
Heating valve is open
Cooling valve is open
Display for manual changeover:
Thermostat is in heating mode
Thermostat is in cooling mode
Subject to change
button until you reach the desired fan mode.
to change the operating mode display.
Frost protection:
........... C
Heat protection:
........... C
. No changeover is possible if the thermostat is